Vega VEGAFLEX 62 User manual

Operating Instructions
VEGAFLEX 62
Profibus PA
Guided Microwave

Content
1About this document
1.1Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2Target group . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3Symbolism used . . . . . . . . . . . . . . . . . . . . . . . 4
2For your safety
2.1Authorised personnel . . . . . . . . . . . . . . . . . . . . 5
2.2Appropriate use. . . . . . . . . . . . . . . . . . . . . . . . 5
2.3Warning about misuse . . . . . . . . . . . . . . . . . . . 5
2.4General safety instructions . . . . . . . . . . . . . . . . 5
2.5Safety approval markings and safety tips . . . . . 6
2.6CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7Fulfilling of NAMUR recommendations . . . . . . . 6
2.8Safety instructions for Ex areas . . . . . . . . . . . . 7
2.9Manufacturer declaration for zone 2. . . . . . . . . 7
2.10 Environmental instructions . . . . . . . . . . . . . . . . 7
3Product description
3.1Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2Principle of operation. . . . . . . . . . . . . . . . . . . . 9
3.3Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4Packaging,transport and storage . . . . . . . . . . . 10
4Mounting
4.1General instructions. . . . . . . . . . . . . . . . . . . . . 12
4.2Mounting instructions. . . . . . . . . . . . . . . . . . . . 13
5Connecting to power supply
5.1Preparing the connection . . . . . . . . . . . . . . . . . 21
5.2Connection steps -Instrument housing . . . . . . . 22
5.3Wiring plan,single chamber housing. . . . . . . . . 23
5.4Wiring plan,double chamber housing . . . . . . . . 25
5.5Wiring plan -version IP 66/IP 68,1bar. . . . . . . 27
6Set up with the indicating and adjustment module
PLICSCOM
6.1Short description . . . . . . . . . . . . . . . . . . . . . . . 28
6.2Insert indicating and adjustment module . . . . . . 28
6.3Adjustment system . . . . . . . . . . . . . . . . . . . . . 30
6.4Setup procedure . . . . . . . . . . . . . . . . . . . . . . . 31
6.5Menu schematic . . . . . . . . . . . . . . . . . . . . . . . 38
2VEGAFLEX 62 •Profibus PA
Content
31839-EN-080716

7Setup with PACTware and other adjustment programs
7.1Connecting the PC . . . . . . . . . . . . . . . . . . . . . 40
7.2Parameter adjustment with PACTware . . . . . . . 40
7.3Parameter adjustment with PDM. . . . . . . . . . . . 41
7.4Saving the parameter adjustment data . . . . . . . 41
8Maintenance and fault rectification
8.1Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 42
8.2Remove interferences . . . . . . . . . . . . . . . . . . . 42
8.3Exchange or shorten cable/rod . . . . . . . . . . . . . 44
8.4Exchanging the electronics module. . . . . . . . . . 46
8.5Instrument repair . . . . . . . . . . . . . . . . . . . . . . . 47
9Dismounting
9.1Dismounting steps . . . . . . . . . . . . . . . . . . . . . . 48
9.2Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10 Supplement
10.1Technical data. . . . . . . . . . . . . . . . . . . . . . . . . 49
10.2Profibus PA -Data format and status byte. . . . . 58
10.3Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
10.4Industrial property rights. . . . . . . . . . . . . . . . . . 63
10.5Trademark . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Supplementary documentation
Information:
Supplementary documents appropriate to the ordered version
come with the delivery.You can find them listed in chapter
"Product description".
Instructions manuals for accessories and replacement
parts
Tip:
To ensure reliable setup and operation of your VEGAFLEX 62,
we offer accessories and replacement parts.The associated
documents are:
l27720 -VEGADIS 61
l30207 -Electronics module VEGAFLEX series 60
l31088 -Flanges according to DIN-EN-ASME-JIS-GOST
l30391 -Spacer
VEGAFLEX 62 •Profibus PA 3
Content
31839-EN-080716

1About this document
1.1Function
This operating instructions manual provides all the information
you need for mounting,connection and setup as well as
important instructions for maintenance and fault rectification.
Please read this information before putting the instrument into
operation and keep this manual accessible in the immediate
vicinity of the device.
1.2Target group
This operating instructions manual is directed to trained
personnel.The contents of this manual should be made
available to these personnel and put into practice by them.
1.3Symbolism used
Information,tip,note
This symbol indicates helpful additional information.
Caution:If this warning is ignored,faults or malfunc-
tions can result.
Warning:If this warning is ignored,injury to persons and/or
serious damage to the instrument can result.
Danger:If this warning is ignored,serious injury to persons
and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
4VEGAFLEX 62 •Profibus PA
1About this document
31839-EN-080716

2For your safety
2.1Authorised personnel
All operations described in this operating instructions manual
must be carried out only by trained specialist personnel
authorised by the plant operator.
During work on and with the device the required personal
protection equipment must always be worn.
2.2Appropriate use
VEGAFLEX 62 is a sensor for continuous level measurement.
You can find detailed information on the application range in
chapter "Product description".
Operational reliability is ensured only if the instrument is
properly used according to the specifications in the operating
instructions manual as well as possible supplementary
instructions.
For safety and warranty reasons,any invasive work on the
device beyond that described in the operating instructions
manual may be carried out only by personnel authorised by the
manufacturer.Arbitrary conversions or modifications are
explicitly forbidden.
2.3Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards,e.g.vessel overfill or damage to
system components through incorrect mounting or adjustment.
2.4General safety instructions
This is a high-tech instrument requiring the strict observance of
standard regulations and guidelines.The user must take note
of the safety instructions in this operating instructions manual,
the country-specific installation standards as well as all
prevailing safety regulations and accident prevention rules.
The instrument must only be operated in a technically flawless
and reliable condition.The operator is responsible for trouble-
free operation of the instrument.
VEGAFLEX 62 •Profibus PA 5
2For your safety
31839-EN-080716

During the entire duration of use,the user is obliged to
determine the compliance of the required occupational safety
measures with the current valid rules and regulations and also
take note of new regulations.
2.5Safety approval markings and safety tips
The safety approval markings and safety tips on the device
must be observed.
2.6CE conformity
The protection goals of the EMC Directive 2004/108/EC (EMC)
and the Low Voltage Directive 2006/95/EC (LVD)are fulfilled.
Conformity has been judged according to the following
standards:
EMC:EN 61326-1:2006
(electrical instruments for control technology and laboratory
use -EMC requirements)
lEmission:Class B
lSusceptibility:Industrial areas
LVD:EN 61010-1:2001
(safety regulations for electrical measurement,control and
laboratory instruments -part 1:General requirements)
2.7Fulfilling of NAMUR recommendations
With respect to interference resistance and emitted interfer-
ence,the NAMUR recommendation NE 21 is fulfilled.
With respect to compatibility,the NAMUR recommendation
NE 53 is fulfilled.This applies also to the corresponding
indicating and adjustment components.VEGA instruments are
generally upward and downward compatible.
lSensor software for DTM VEGAFLEX 62 HART,PA or FF
lDTM VEGAFLEX 62 for adjustment software PACTware
lIndicating and adjustment module for sensor software
The parameter adjustment of the basic sensor functions is
independent of the software version.The range of available
functions depends on the respective software version of the
individual components.
The software version of VEGAFLEX 62 can be determined as
follows:
6VEGAFLEX 62 •Profibus PA
2For your safety
31839-EN-080716

lvia PACTware
lon the type label of the electronics
lvia the indicating and adjustment module
You can view all software histories on our website www.vega.
com.Make use of this advantage and get registered for update
information via e-mail.
2.8Safety instructions for Ex areas
Please note the Ex-specific safety information for installation
and operation in Ex areas.These safety instructions are part of
the operating instructions manual and come with the Ex-
approved instruments.
2.9Manufacturer declaration for zone 2
In conformity with DIN EN 60079-15/2005 VEGAFLEX 62 is
suitable for use in zone 2.
The operator must use the instrument as it was intended to be
used and follow the specifications of the following documents:
lthis operating instructions manual
lthe manufacturer declaration 32906 (download under
"www.vega.com")
lthe applicable installation regulations
2.10 Environmental instructions
Protection of the environment is one of our most important
duties.That is why we have introduced an environment
management system with the goal of continuously improving
company environmental protection.The environment man-
agement system is certified according to DIN EN ISO 14001.
Please help us fulfil this obligation by observing the environ-
mental instructions in this manual:
lChapter "Packaging,transport and storage"
lChapter "Disposal"
VEGAFLEX 62 •Profibus PA 7
2For your safety
31839-EN-080716

3Product description
3.1Configuration
The scope of delivery encompasses:
lVEGAFLEX 62 level sensor
lDocumentation
-this operating instructions manual
-Operating instructions manual 27835 "Indicating and
adjustment module PLICSCOM"(optional)
-Supplementary instructions manual "Plug connector for
continuously measuring sensors"(optional)
-Ex-specific"Safety instructions"(with Ex-versions)
-if necessary,further certificates
VEGAFLEX 62 consists of the following components:
lProcess fitting with probe
lHousing with electronics
lHousing cover,optionally available with indicating and
adjustment module
1
2
3
Fig.1:VEGAFLEX 62 -cable version with plastic housing
1Housing cover with integrated indicating and adjustment module (optional)
2Housing with electronics
3Process fitting
The type label contains the most important data for identi-
fication and use of the instrument:
Scope of delivery
Components
Type label
8VEGAFLEX 62 •Profibus PA
3Product description
31839-EN-080716

lArticle number
lSerial number
lTechnical data
lArticle numbers,documentation
With the serial number,you can access the delivery data of the
instrument via "www.vega.com","VEGA Tools"and "serial
number search".In addition to the type label outside,you can
also find the serial number on the inside of the instrument.
3.2Principle of operation
VEGAFLEX 62 is a level sensor with cable or rod probe for
continuous level measurement.
It is designed for industrial use in all areas of process
technology and can be used equally well in liquids or solids.
High frequency microwave pulses are guided along a steel
rope or a rod.Upon reaching the product surface,the
microwave pulses are reflected.The running time is evaluated
by the instrument and outputted as distance.
Power supply via the Profibus DP/PA segment coupler or
VEGALOG 571 EP cards.Atwo-wire cable according to
Profibus specification serves as carrier of both power and
digital data signals for multiple sensors.The instrument profile
of VEGAFLEX 62 corresponds to profile specification version
3.0.
The GSD (instrument master files)and bitmap files necessary
for planning your Profibus-DP-(PA)communication network
are available from the download section on the VEGA
homepage www.vega.com under "Services -Downloads -
Software -Profibus".There you can also find the appropriate
certificates.In a PDM environment,an EDD (Electronic Device
Description)is also required to enable the full range of sensor
functions (also available as a download).A CD with the
appropriate files can be ordered via e-mail under info@de.
vega.com or by phone from one of the VEGA agencies under
the order number "DRIVER.S".
The optional heating requires its own power supply.You can
find further details in the supplementary instructions manual
"Heating for indicating and adjustment module".
Application range
Functional principle
Power supply and bus
communication
GSD/EDD
VEGAFLEX 62 •Profibus PA 9
3Product description
31839-EN-080716

3.3Operation
VEGAFLEX 62 can be adjusted with different adjustment
media:
lwith indicating and adjustment module
lwith the suitable VEGA DTM in conjunction with an
adjustment software according to the FDT/DTM standard,
e.g.PACTware and PC
lwith the adjustment program PDM
The entered parameters are generally saved in VEGAFLEX
62,optionally also in the indicating and adjustment module or
in PACTware.
3.4Packaging,transport and storage
Your instrument was protected by packaging during transport.
Its capacity to handle normal loads during transport is assured
by a test according to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly,recyclable cardboard.For special versions,PE
foam or PE foil is also used.Dispose of the packaging material
via specialised recycling companies.
Transport must be carried out under consideration of the notes
on the transport packaging.Nonobservance of these instruc-
tions can cause damage to the device.
The delivery must be checked for completeness and possible
transit damage immediately at receipt.Ascertained transit
damage or concealed defects must be appropriately dealt
with.
Up to the time of installation,the packages must be left closed
and stored according to the orientation and storage markings
on the outside.
Unless otherwise indicated,the packages must be stored only
under the following conditions:
lNot in the open
lDry and dust free
lNot exposed to corrosive media
lProtected against solar radiation
lAvoiding mechanical shock and vibration
lStorage and transport temperature see "Supplement -
Technical data -Ambient conditions"
Packaging
Transport
Transport inspection
Storage
Storage and transport
temperature
10 VEGAFLEX 62 •Profibus PA
3Product description
31839-EN-080716

lRelative humidity 20 …85 %
VEGAFLEX 62 •Profibus PA 11
3Product description
31839-EN-080716

4Mounting
4.1General instructions
Select an installation position you can easily reach for
mounting and connecting as well as later retrofitting of an
indicating and adjustment module.The housing can be rotated
by 330°without the use of any tools.You can also install the
indicating and adjustment module in four different positions
(each displaced by 90°).
Before beginning the welding work,remove the oscillator
(electronics)from the sensor.By doing this,you avoid damage
to the electronics through inductive coupling.
With threaded versions,the housing must not be used to screw
in the instrument!Applying tightening forces on the housing
can damage its internal parts.
Use the hexagon for screwing in.
Use the recommended cables (see chapter "Connecting to
power supply")and tighten the cable gland.
You can give your instrument additional protection against
moisture penetration by leading the connection cable down-
ward in front of the cable entry.Rain and condensation water
can thus drain off.This applies mainly to outdoor mounting as
well as installation in areas where high humidity is expected (e.
g.through cleaning processes)or on cooled or heated
vessels.
Fig.2:Measures against moisture penetration
The reference plane for the measuring range of the sensors is
the sealing surface of the thread or flange.
Mounting position
Welding work
Handling
Moisture
Measuring range
12 VEGAFLEX 62 •Profibus PA
4Mounting
31839-EN-080716

Keep in mind that a min.distance must be maintained below
the reference plane and possibly also at the end of the probe -
measurement in these areas is not possible (dead band). Keep
in mind that the cable length cannot be used all the way to the
end because measurement in the area of the gravity weight is
not possible.These min.distances (dead bands)are listed in
chapter "Technical data".
The process fitting must be sealed if there is gauge or low
pressure in the vessel.Before use,check if the seal material is
resistant against the measured product and the process
temperature.
The max.permissible pressure is specified in chapter
"Technical data"or on the type label of the sensor.
4.2Mounting instructions
Mount VEGAFLEX 62 in such a way that the distance to vessel
installations or to the vessel wall is at least 300 mm (12 in).
During operation,the probe must not touch any installations or
the vessel wall.If necessary,fasten the probe end.
In vessels with conical bottom it can be advantageous to
mount the sensor in the center of the vessel,as measurement
is then possible down to the lowest point of the bottom.When
using the cable version,keep in mind that measurement down
to the tip of the probe is not possible.The exact value of the
Pressure
Mounting position
VEGAFLEX 62 •Profibus PA 13
4Mounting
31839-EN-080716

min.distance (lower dead band)is stated in chapter "Technical
data".
Fig.3:Vessel with conical bottom
In case of difficult installation conditions,the probe can be also
mounted laterally.For this purpose,adapt the rod with rod
extensions or bow-shaped segments.
Rod extensions
14 VEGAFLEX 62 •Profibus PA
4Mounting
31839-EN-080716

Lx
ø 16 mm
(5/8")
1
2
3
Fig.4:Extension rod ø16 mm (0.63 in)
1Probe
2Retaining ring
3Extension rod
L Rod length 100 …2000 mm (3.937 …78.74 in)
xThread length 60 mm (2.362 in)
Make sure that the rod of the probe is at least 300 mm
(11.811 in)away from the vessel wall
VEGAFLEX 62 •Profibus PA 15
4Mounting
31839-EN-080716

≥
300mm (11 13/16")
150mm (5 29/32")
150mm (5 29/32")
1
SW 13
Fig.5:Bow-shaped segment ø16 mm (0.63 in)
1Max.filling height
Plastic vessel/Glass vessel
The guided microwave principle requires a metal surface on
the process fitting.Therefore use in plastic vessels etc.an
instrument version with flange (from DN 50)or place a metal
sheet (ø>200 mm/8in)beneath the process fitting when
screwing it in.
Make sure that the plate has direct contact with the process
fitting.
In bypass tubes of plastic,a metal screen must be provided on
the outside.You can glue metal foil,for example,on the
outside along the entire length of the tube.This metal screen
must be connected to the ground connection of the instrument.
When installing rod or cable probes without metal vessel wall,
e.g.in plastic vessels,the measured value can be influenced
by strong electromagnetic fields (emitted interference accord-
ing to EN 61326:class A).
In this case,use a probe in coax version.
Type of vessel
16 VEGAFLEX 62 •Profibus PA
4Mounting
31839-EN-080716

1 2
Fig.6:Installation in plastic silo
1Flange
2Metal sheet
Concrete vessel
When installed in thick concrete ceilings,VEGAFLEX 62
should be mounted front flush to the lower edge.In concrete
silos,the distance to the wall should be at least 500 mm (20 in).
ø >160mm
ø >(6 19/64")
Fig.7:Installation in concrete silo
VEGAFLEX 62 •Profibus PA 17
4Mounting
31839-EN-080716

If possible,avoid sockets.Mount the sensor flush with the
vessel top.If this is not possible,use short sockets with small
diameter.
Higher sockets or sockets with a bigger diameter can generally
be used.They simply increase the upper dead band.Check if
this is relevant for your measurement.
In such cases,always carry out a gating out of false signals
after installation.You can find further information under "Setup
procedure".
h
d
dh
DN40 ... DN150 ≤ 150
>DN 150 ... DN200 ≤ 100
Fig.8:Mounting socket
When welding the socket,make sure that the socket is flush to
the vessel wall.
1 2
Fig.9:Socket must be installed flush
1Unfavourable installation
2Socket flush -optimum installation
Socket
18 VEGAFLEX 62 •Profibus PA
4Mounting
31839-EN-080716

Standpipes or bypass tubes are normally metal tubes with a
diameter of 30 …200 mm (1.18 …7.87 in). In measurement
technology such a tube corresponds to a coax probe.It does
not matter if the standpipe is perforated or slotted for better
mixing.Lateral inlets with bypass tubes also do not influence
the measurement.
Measuring probes can be mounted in bypass tubes up to
DN 200.
IfVEGAFLEX 62 is used in standpipes or bypass tubes,
contact with the tube wall should be avoided.We offer spacers
as accessories for fastening the probe in the middle of the
tube.
Depending on the tube diameter or tube length,one or several
spacers can be mounted.With cable probes,the cable can
also be strained to avoid contact with the tube.
Keep in mind that buildup can form on the spacers.Strong
buildup can influence the measurement.
For process technical reasons,plastic standpipes can always
be used.However,they offer no advantages for the
measurement.If durability is no problem,then we recommend
the use of metal standpipes.
1
Fig.10:Position of the spacer
1Spacer
Standpipes or bypass
tubes
VEGAFLEX 62 •Profibus PA 19
4Mounting
31839-EN-080716

Note:
Measurement in a standpipe is not recommended for very
adhesive products.
Make sure that the probe is not subjected to strong lateral
forces.Mount VEGAFLEX 62 at a position in the vessel where
no disturbances,e.g.from filling openings,agitators,etc., can
occur.
Fig.11:Lateral load
If there is a danger of the probe touching the vessel wall during
operation due to product movements or agitators etc., the
measuring probe should be securely fixed.
In the gravity weight there is a thread (M12), e.g.for a ring bolt
(article no.2.27424).
Make sure that the probe cable is not completely taut.Avoid
tensile loads on the cable.
Avoid undefined cable-vessel connections,i.e.the connection
must be either grounded reliably or isolated reliably.Any
deviation from this requirement can lead to measurement
errors.
Inflowing medium
Fixing
20 VEGAFLEX 62 •Profibus PA
4Mounting
31839-EN-080716
Other manuals for VEGAFLEX 62
3
Table of contents
Other Vega Accessories manuals

Vega
Vega FIBERTRAC 31 User manual

Vega
Vega VEGAFLEX 82 User manual

Vega
Vega VEGAWAVE 61 Instruction Manual

Vega
Vega vegaflex 83 User manual

Vega
Vega FIBERTRAC 31 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGAPULS WL 61 User manual

Vega
Vega VEGAPULS 66 User manual

Vega
Vega VEGAPULS 62 User manual

Vega
Vega VEGAVIB 62 User manual

Vega
Vega VEGABAR 81 User manual

Vega
Vega VEGAPULS 67 User manual

Vega
Vega VEGAPULS WL 61 User manual

Vega
Vega VEGAPULS 67 User manual

Vega
Vega B-LIFT 8120 200 Evo Series User manual

Vega
Vega VEGAPULS 61 User manual

Vega
Vega VEGAPULS 65 User manual

Vega
Vega VEGAFLEX 81 User manual

Vega
Vega VEGAFLEX 67 User manual

Vega
Vega VEGAPULS 66 User manual