Vega VEGAFLEX 67 User manual

Operating Instructions
VEGAFLEX 67
-200 …+400 °C
Profibus PA
Document ID:
32313
Guided Microwave

Contents
1About this document
1.1Function.................................. 4
1.2Target group .............................. 4
1.3Symbolism used............................ 4
2For your safety
2.1Authorised personnel ........................ 5
2.2Appropriate use ............................ 5
2.3Warning about misuse ....................... 5
2.4General safety instructions . . . . . . . . . . . . . . . . . . . . 5
2.5CE conformity ............................. 6
2.6Fulfillment of NAMUR recommendations . . . . . . . . . . 6
2.7Safety instructions for Ex areas . . . . . . . . . . . . . . . . . 6
2.8Environmental instructions..................... 6
3Product description
3.1Structure ................................. 7
3.2Principle of operation ........................ 8
3.3Operation................................. 11
3.4Packaging,transport and storage ............... 11
4Mounting
4.1General instructions ......................... 12
4.2Instructions for installation ..................... 13
5Connecting to power supply
5.1Preparing the connection ..................... 16
5.2Connection procedure........................ 17
5.3Wiring plan,single chamber housing . . . . . . . . . . . . . 18
5.4Wiring plan,double chamber housing . . . . . . . . . . . . 19
5.5Wiring plan -version IP 66/IP 68,1bar . . . . . . . . . . . 21
6Set up with the indicating and adjustment module PLICSCOM
6.1Short description ........................... 22
6.2Insert indicating and adjustment module. . . . . . . . . . . 22
6.3Adjustment system .......................... 24
6.4Setup steps ............................... 25
6.5Menu schematic ............................ 31
6.6Saving the parameter adjustment data . . . . . . . . . . . . 34
7Set up with PACTware and other adjustment programs
7.1Connect the PC ............................ 35
7.2Parameter adjustment with PACTware . . . . . . . . . . . . 36
7.3Parameter adjustment with PDM . . . . . . . . . . . . . . . . 36
7.4Saving the parameter adjustment data . . . . . . . . . . . . 36
2VEGAFLEX 67 •Profibus PA
Contents
32313-EN-120329

8Maintenance and fault rectification
8.1Maintenance .............................. 37
8.2Remove interferences ........................ 37
8.3Exchanging the electronics module . . . . . . . . . . . . . . 39
8.4Software update ............................ 39
8.5Instrument repair ........................... 40
9Dismounting
9.1Dismounting steps .......................... 42
9.2Disposal ................................. 42
10 Supplement
10.1Technical data ............................. 43
10.2Profibus PA ............................... 55
10.3Dimensions ............................... 59
Supplementary documentation
Information:
Supplementary documents appropriate to the ordered version come
with the delivery.You can find them listed in chapter "Product
description".
Instructions manuals for accessories and replacement parts
Tip:
To ensure reliable setup and operation of your VEGAFLEX 67,we
offer accessories and replacement parts.The corresponding doc-
umentations are:
l27720 -VEGADIS 61
l30207 -Electronics module VEGAFLEX series 60
l34296 -Protective cover
l31088 -Flanges according to DIN-EN-ASME-JIS-GOST
l30391 -Spacer
Editing status:2012-03-19
VEGAFLEX 67 •Profibus PA 3
Contents
32313-EN-120329

1About this document
1.1Function
This operating instructions manual provides all the information you
need for mounting,connection and setup as well as important
instructions for maintenance and fault rectification.Please read this
information before putting the instrument into operation and keep this
manual accessible in the immediate vicinity of the device.
1.2Target group
This operating instructions manual is directed to trained qualified
personnel.The contents of this manual should be made available to
these personnel and put into practice by them.
1.3Symbolism used
Information,tip,note
This symbol indicates helpful additional information.
Caution:If this warning is ignored,faults or malfunctions can
result.
Warning:If this warning is ignored,injury to persons and/or serious
damage to the instrument can result.
Danger:If this warning is ignored,serious injury to persons and/or
destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
4VEGAFLEX 67 •Profibus PA
1About this document
32313-EN-120329

2For your safety
2.1Authorised personnel
All operations described in this operating instructions manual must be
carried out only by trained specialist personnel authorised by the plant
operator.
During work on and with the device the required personal protective
equipment must always be worn.
2.2Appropriate use
VEGAFLEX 67 is a sensor for continuous interface measurement in
liquids.
You can find detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly used
according to the specifications in the operating instructions manual as
well as possible supplementary instructions.
For safety and warranty reasons,any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer.Arbitrary
conversions or modifications are explicitly forbidden.
2.3Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards,e.g.vessel overfill or damage to system
components through incorrect mounting or adjustment.
2.4General safety instructions
This is a high-tech instrument requiring the strict observance of
standard regulations and guidelines.The user must take note of the
safety instructions in this operating instructions manual,the country-
specific installation standards as well as all prevailing safety
regulations and accident prevention rules.
The instrument must only be operated in a technically flawless and
reliable condition.The operator is responsible for trouble-free
operation of the instrument.
During the entire duration of use,the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new
regulations.
VEGAFLEX 67 •Profibus PA 5
2For your safety
32313-EN-120329

2.5CE conformity
This device fulfills the legal requirements of the applicable EC
guidelines.By attaching the CE mark,VEGA provides a confirmation
of successful testing.You can find the CE conformity declaration in the
download area of "www.vega.com".
2.6Fulfillment of NAMUR recommendations
The device fulfills the requirements of the applicable NAMUR
recommendations.
2.7Safety instructions for Ex areas
Please note the Ex-specific safety information for installation and
operation in Ex areas.These safety instructions are part of the
operating instructions manual and come with the Ex-approved
instruments.
2.8Environmental instructions
Protection of the environment is one of our most important duties.That
is why we have introduced an environment management system with
the goal of continuously improving company environmental protection.
The environment management system is certified according to DIN
EN ISO 14001.
Please help us fulfil this obligation by observing the environmental
instructions in this manual:
lChapter "Packaging,transport and storage"
lChapter "Disposal"
6VEGAFLEX 67 •Profibus PA
2For your safety
32313-EN-120329

3Product description
3.1Structure
The scope of delivery encompasses:
lLevel sensor VEGAFLEX 67
lDocumentation
-this operating instructions manual
-Operating instructions manual 27835 "Indicating and adjust-
ment module PLICSCOM"(optional)
-Supplementary instructions manual 31708 "Heating for in-
dicating and adjustment module"(optional)
-Supplementary instructions manual "Plug connector for con-
tinuously measuring sensors"(optional)
-Ex-specific"Safety instructions"(with Ex versions)
-if necessary,further certificates
The VEGAFLEX 67 consists of the components:
lProcess fitting with probe
lHousing with electronics
lHousing cover,optionally available with indicating and adjustment
module
Scope of delivery
Constituent parts
VEGAFLEX 67 •Profibus PA 7
3Product description
32313-EN-120329

1
2
3
Fig.1:VEGAFLEX 67 -cable version with plastic housing
1Housing cover with integrated indicating and adjustment module (optional)
2Housing with electronics
3Process fitting
The type label contains the most important data for identification and
use of the instrument:
lArticle number
lSerial number
lTechnical data
lArticle numbers,documentation
With the serial number,you can access the delivery data of the
instrument via www.vega.com,"VEGA Tools"and "serial number
search".In addition to the type label outside,you can also find the
serial number on the inside of the instrument.
3.2Principle of operation
VEGAFLEX 67 is a level sensor with coax,rod or cable probe for
continuous interface measurment.
Type label
Application range
8VEGAFLEX 67 •Profibus PA
3Product description
32313-EN-120329

It is designed for industrial use in all areas of process technology and
can be used in liquids.
High frequency microwave impulses are guided along a steel cable or
rod or a rod inside a steel tube.When reaching the product surface,a
part of the microwave impulses is reflected.The other part passes the
upper product and is reflected a second time by the interface.The
running times to the two product layers are processed by the
instrument.
Upper medium (L2)
lThe upper medium must not be conductive
lThe dielectric figure of the upper medium must be known (input
required). Min.dielectric figure:rod version 1.7;coax version 1.4.
You can find a list with the dielectric figures on our home page:
www.vega.com
lThe composition of the upper medium must be stable,no varying
products or mixtures
lThe upper medium must be homogeneous,no stratifications within
the medium
lMin.thickness of the upper medium 100 mm
lClear separation from the lower medium,no emulsion phase,no
mull layer
lIf possible,no foam on the surface
Lower medium (L1)
lThe dielectric figure must be 10 higher than the dielectric figure of
the upper medium,preferably electrically conductive.Example:
upper medium dielectric figure 2,lower medium at least dielectric
figure 12
Functional principle
Prerequisites for inter-
face measurement
VEGAFLEX 67 •Profibus PA 9
3Product description
32313-EN-120329

TS
d1
h1
h2
d2
1
L2
L1
Fig.2:Interface measurement
1Reference plane
d1Distance to the interface
d2Distance to the level
TS Thickness of the upper medium (d1-d2)
h1Height -Interface
h2Height -Level
L1Lower medium
L2Upper medium
The interface is directly processed by the sensor and outputted as
digital output signal.
The indication of the indicating and adjustment module and PACTware
output the distance to the interface (d1)in m(d).
Power supply via the Profibus DP/PA segment coupler or VEGALOG
571 EP cards.Atwo-wire cable according to Profibus specification
serves as carrier of both power and digital data transmission for
multiple sensors.The instrument profile of VEGAFLEX 67 corresponds
to profile specification version 3.0.
The backlight of the indicating and adjustment module is powered by
the sensor.Prerequisite is a certain level of operating voltage.
The data for power supply are specified in chapter "Technical data".
The optional heating requires its own operating voltage.You can find
details in the supplementary instructions manual "Heating for indicat-
ing and adjustment module".
This function is generally not available for approved instruments.
The GSD (instrument master files)and bitmap files necessary for
planning your Profibus-DP-(PA)communication network are available
from the download section on the VEGA homepage www.vega.com
under "Services -Downloads -Software -Profibus".There you can
Output signal
Power supply and bus
communication
GSD/EDD
10 VEGAFLEX 67 •Profibus PA
3Product description
32313-EN-120329

also find the appropriate certificates.In a PDM environment,an EDD
(Electronic Device Description)is also required to enable the full range
of sensor functions (also available as a download).A CD with the
appropriate files can be ordered via e-mail under info@de.vega.com or
by phone from one of the VEGA agencies under the order number
"DRIVER.S".
3.3Operation
The instrument can be adjusted with the following adjustment media:
lWith indicating and adjustment module
lwith the suitable VEGA DTM in conjunction with an adjustment
software according to the FDT/DTM standard,e.g.PACTware and
PC
lwith the adjustment program PDM
3.4Packaging,transport and storage
Your instrument was protected by packaging during transport.Its
capacity to handle normal loads during transport is assured by a test
according to DIN EN 24180.
The packaging of standard instruments consists of environment-
friendly,recyclable cardboard.For special versions,PE foam or PE foil
is also used.Dispose of the packaging material via specialised
recycling companies.
Transport must be carried out under consideration of the notes on the
transport packaging.Nonobservance of these instructions can cause
damage to the device.
The delivery must be checked for completeness and possible transit
damage immediately at receipt.Ascertained transit damage or
concealed defects must be appropriately dealt with.
Up to the time of installation,the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated,the packages must be stored only under
the following conditions:
lNot in the open
lDry and dust free
lNot exposed to corrosive media
lProtected against solar radiation
lAvoiding mechanical shock and vibration
lStorage and transport temperature see chapter "Supplement -
Technical data -Ambient conditions"
lRelative humidity 20 …85 %
Packaging
Transport
Transport inspection
Storage
Storage and transport
temperature
VEGAFLEX 67 •Profibus PA 11
3Product description
32313-EN-120329

4Mounting
4.1General instructions
Make sure that all parts of the instrument exposed to the process,in
particular the sensor element,process seal and process fitting,are
suitable for the existing process conditions.These include above all
the process pressure,process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data"and on the
type label.
Select an installation position you can easily reach for mounting and
connecting as well as later retrofitting of an indicating and adjustment
module.The housing can be rotated by 330°without the use of any
tools.You can also install the indicating and adjustment module in four
different positions (each displaced by 90°).
Before beginning the welding work,remove the electronics module
from the sensor.By doing this,you avoid damage to the electronics
through inductive coupling.
With threaded versions,the housing must not be used to screw in the
instrument!Applying tightening forces on the housing can damage its
internal parts.
Use the hexagon for screwing in.
Use the recommended cables (see chapter "Connecting to power
supply")and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable entry.Rain and condensation water can thus drain off.This
applies mainly to outdoor mounting as well as installation in areas
where high humidity is expected (e.g.through cleaning processes)or
on cooled or heated vessels.
Suitability for the pro-
cess conditions
Mounting position
Welding work
Handling
Moisture
12 VEGAFLEX 67 •Profibus PA
4Mounting
32313-EN-120329

Fig.3:Measures against moisture penetration
The reference plane for the measuring range of the sensors is the
sealing surface of the thread or flange.
Keep in mind that a min.distance must be maintained below the
reference plane and possibly also at the end of the probe -
measurement in these areas is not possible (dead band). Particularly
the cable length cannot be used all the way to the end because
measurement in the area of the gravity weight is not possible.These
dead bands are listed in chapter "Technical data".Keep in mind for the
adjustment that the default setting for the measuring range refers to
water.
The process fitting must be sealed if there is gauge or low pressure in
the vessel.Before use,check if the seal material is resistant against
the measured product and the process temperature.
The max.permissible pressure is specified in chapter "Technical data"
or on the type label of the sensor.
4.2Instructions for installation
When mounting the cable and rod versions of VEGAFLEX 67 keep at
least a distance of 300 mm (11.81 in)to other vessel installations or to
the vessel wall.
During operation,the probe must not touch any installations or the
vessel wall.If necessary,fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel,as measurement is then possible
down to the lowest point of the bottom.When using the cable version,
Measuring range
Pressure
Mounting position
VEGAFLEX 67 •Profibus PA 13
4Mounting
32313-EN-120329

keep in mind that measurement down to the tip of the probe is not
possible.The exact value of the min.distance (lower dead band)is
stated in chapter "Technical data".
Fig.4:Vessel with conical bottom
Make sure that the probe is not subjected to strong lateral forces.
Mount VEGAFLEX 67 at a position in the vessel where no
disturbances,e.g.from filling openings,agitators,etc., can occur.
Fig.5:Lateral load
Extreme vibration caused by the system,e.g.due to agitators or
turbulence in the vessel from inflowing medium,can cause the coax
probe of VEGAFLEX 67 to vibrate in resonance.With coax probes of
Inflowing medium
14 VEGAFLEX 67 •Profibus PA
4Mounting
32313-EN-120329

more than 1m(3.281 in)length,you must secure the probe by
fastening a suitable insulated brace or guy directly above the end of
the rod.
VEGAFLEX 67 should be integrated in the vessel insulation.This
prevents the electronics from strong heating or cooling by temperature
radiation.
Make sure that with heated or cooled vessels the permissible ambient
temperature on the housing is not exceeded.The permissible ambient
temperature is stated in chapter "Technical data"under "Ambient
conditions".
1
2
Fig.6:Vessel with temperature insulation
1Temperature insulation
2Ambient temperature on the housing
Temperature insulation
VEGAFLEX 67 •Profibus PA 15
4Mounting
32313-EN-120329

5Connecting to power supply
5.1Preparing the connection
Always keep in mind the following safety instructions:
lConnect only in the complete absence of line voltage
lIf voltage surges are expected,overvoltage arresters should be
installed according to Profibus specifications
Tip:
We recommend VEGA overvoltage arrester B63-32.
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.
Power is supplied via a Profibus DP/PA segment coupler or a
VEGALOG 571 EP input card.The power supply range can differ
depending on the instrument version.
The data for power supply are specified in chapter "Technical data".
Connection is made with screened cable according to the Profibus
specification.Power supply and digital bus signal are carried over the
same two-wire connection cable.
Use cable with round cross-section.Acable outer diameter of 5…9mm
(0.2…0.35 in)ensures the seal effect of the cable gland.If you are
using cable with a different diameter or cross-section,exchange the
seal or use a suitable cable gland.
Please make sure that your installation is carried out according to the
Profibus specification.In particular,make sure that the termination of
the bus is done with appropriate terminating resistors.
On the instrument with cable entry ½NPT and plastic housing there is
a metallic ½" threaded insert moulded into the plastic housing.
Caution:
No grease should be used when screwing the NPT cable gland or
steel tube into the threaded insert.Standard grease can contain
additives that corrode the connection between threaded insert and
housing.This would influence the stability of the connection and the
tightness of the housing.
With systems with potential equalisation,connect the cable screen
directly to ground potential at the power supply unit,in the connection
box and at the sensor.The screen in the sensor must be connected
directly to the internal ground terminal.The ground terminal outside on
the housing must be connected to the potential equalisation (low
impedance).
Safety instructions
Voltage supply
Connection cable
Cable gland ½NPT
Cable screening and
grounding
16 VEGAFLEX 67 •Profibus PA
5Connecting to power supply
32313-EN-120329

In systems without potential equalisation,connect the cable screen
directly to ground potential at the power supply unit and at the sensor.
In the connection box or T-distributor,the screen of the short stub to
the sensor must not be connected to ground potential or to another
cable screen.The cable screens to the power supply unit and to the
next distributor must be connected to each other and also connected
to ground potential via a ceramic capacitor (e.g.1nF,1500 V). Low-
frequency potential equalisation currents are thus suppressed,but the
protective effect against high frequency interference signals remains.
The total capacitance of the cable and of all capacitors must not exceed
10 nFin Ex applications.
Take note of the corresponding installation regulations for Ex
applications.In particular,make sure that no potential equalisation
currents flow over the cable screen.In case of grounding on both sides
this can be achieved by the use of a capacitor or a separate potential
equalisation.
5.2Connection procedure
Proceed as follows:
1Unscrew the housing cover
2If an indicating and adjustment module is installed,remove it by
turning it to the left.
3Loosen compression nut of the cable entry
4Remove approx.10 cm (4in)of the cable mantle,strip approx.
1cm (0.4in)of insulation from the ends of the individual wires
5Insert the cable into the sensor through the cable entry
6Lift the opening levers of the terminals with a screwdriver (see
following illustration)
VEGAFLEX 67 •Profibus PA 17
5Connecting to power supply
32313-EN-120329

7Insert the wire ends into the open terminals according to the wiring
plan
Fig.7:Connection steps 6and 7
8Press down the opening levers of the terminals,you will hear the
terminal spring closing
9Check the hold of the wires in the terminals by lightly pulling on
them
10 Connect the screen to the internal ground terminal,connect the
outer ground terminal to potential equalisation
11 Tighten the compression nut of the cable entry.The seal ring must
completely encircle the cable
12 Screw the housing cover back on
The electrical connection is finished.
5.3Wiring plan,single chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-ia
version.
18 VEGAFLEX 67 •Profibus PA
5Connecting to power supply
32313-EN-120329

I²C
Display
1 2 5 6 7 8
3
4
1
2
Fig.8:Electronics and connection compartment,single chamber housing
1Plug connector for VEGACONNECT (I²Cinterface)
2Spring-loaded terminals for connection of the external indication VEGADIS
61
3Ground terminal for connection of the cable screen
4Spring-loaded terminals for voltage supply
I2C
Display
1
1 2 5 6 7 8
Fig.9:Wiring plan,single chamber housing
1Voltage supply,signal output
5.4Wiring plan,double chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-ia
version.
Electronics and connec-
tion compartment
Wiring plan
VEGAFLEX 67 •Profibus PA 19
5Connecting to power supply
32313-EN-120329

1
32
Display
1 2 5 6 7 8
I2C
Fig.10:Electronics compartment,double chamber housing
1Plug connector for VEGACONNECT (I²Cinterface)
2Internal connection cable to the connection compartment
3Terminals for VEGADIS 61
1
2
3
Display
1 2 I2C
Fig.11:Connection compartment double chamber housing
1Spring-loaded terminals for voltage supply
2Plug connector for VEGACONNECT (I²Cinterface)
3Ground terminal for connection of the cable screen
Electronics compart-
ment
Connection compart-
ment
20 VEGAFLEX 67 •Profibus PA
5Connecting to power supply
32313-EN-120329
Other manuals for VEGAFLEX 67
1
Table of contents
Other Vega Accessories manuals

Vega
Vega VEGAPULS 66 User manual

Vega
Vega VEGAPULS WL S 61 User manual

Vega
Vega VEGAFLEX 86 User manual

Vega
Vega POINTRAC 31 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGAPULS 62 User manual

Vega
Vega VEGAPULS 67 User manual

Vega
Vega VEGAMET 391 User manual

Vega
Vega VEGASON 61 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGAPULS 66 User manual

Vega
Vega VEGAPULS 67 User manual

Vega
Vega VEGAPULS 21 User manual

Vega
Vega VEGAFLEX 65 User manual

Vega
Vega VEGAPULS WL 61 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGAFLEX 82 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega SOLITRAC 31 User manual

Vega
Vega VEGAPULS 62 User manual