Z207873-0A
Page 1 of 2 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 0419 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
•
Read and understand the instructions before installing this product.
• Turn o all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
If this product is used in a manner not specied by the manufacturer, the protection
provided by the product may be impaired. No responsibility is assumed by the
manufacturer for any consequences arising out of the use of this material.
TM
Installation Guide
Accessories
Product Overview
The AG06 R410a refrigerant sensing element is designed to work with the Veris GWN Series gas platform unit
to provide accurate monitoring of R410a refrigerant levels. R410a is a common refrigerant used in commercial,
residential and automotive HVAC applications. The AG06 is intended to be mounted in a xed location and will
measure the air in that xed location. The sensor is calibrated at the factory, so no eld calibration is needed. The
AG06 is warranted to meet accuracy specications for two years after the date of manufacture.
AG06
R410a Refrigerant Sensing Element
Specications
Sensor Type Non-dispersive infrared
Measurement Range 0 to 2000 ppm
Accuracy ±2% of range (60 to 2000 ppm)
Analog Output Scaling 0 to 2000 ppm
Resolution 1 ppm
Sensor Warranty 2 years from manufacture date
Low Level Setpoint 100 ppm (xed)*
High Level Setpoint 500 ppm (xed)*
Operating Temperature Range -20 to 50 °C (-4 to 122 °F)
Operating Humidity Range 0 to 90% RH non-condensing
Note: The AGxx sensors work only with Veris GWN Series gas platform devices.
*Low and high level setpoints can be adjusted between 0 and 2000 ppm if AG06 is used with a GWNP (protocol output) gas
platform.