CW Series Installation Guide
Input Voltage Class 2; 20 to 30 Vdc, 24 Vac
Analog Output CWL: 4 to 20 mA (clipped and capped)/0-5 Vdc/0-10Vdc (selectable)
CWE: 4 to 20 mA (clipped and capped)/0-10Vdc (selectable)
Sensor Current Draw 100 mA max.
Operating Temperature Range No humidity option: 0 to 50 °C (32 to 122 °F)
With humidity option**: 10 to 35 °C (50 to 95 °F)
Operating Humidity Range 0 to 95% (non-condensing)
Housing Material High impact ABS plastic
CO2TRANSMITTER
Sensor Type Non-dispersive infrared (NDIR), diusion sampling
Output Range CWL: 0 to 2000 ppm or 0 to 5000 ppm, user selectable;
CWE: 0 to 2000 ppm
Accuracy ±30 ppm ±2% of measured value*
Repeatability ±20 ppm ±1% of measured value
Response Time <60 seconds for 90% step change
RH TRANSMITTER**
HS Sensor Digitally proled thin-lm capacitive (32-bit mathematics);
U.S. Patent 5,844,138
Accuracy ±2% from 10 to 80% RH @ 25°C; Multi-point calibration NIST
Hysteresis 1.5% typical
Linearity Included in Accuracy spec.
Stability ±1% @ 20 °C (68 °F) annually for two years
Output Range 0 to 100% RH
Temperature Coecient ±0.1% RH/°C above or below 25 °C (typical)
TEMPERATURE (TRANSMITTER)**
Sensor Type Thermistor
Accuracy ±0.5 °C (±1 °F) typical
Resolution 0.1 °C (0.2 °F)
Output Range 10 to 35 °C (50 to 95 °F)
RELAY CONTACTS**
1 Form C (on models without setpoint
slider option)
1 A@30 Vdc, resistive; 30 W max.
Specified accuracy with 24 Vdc supplied power with rising humidity. RTD/Thermistors in wall packages are not compensated for
internal heating of product.
EMC Conformance: EN 61000-6-3:2007 Class B, EN 61000-6-1:2007
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION
(EN 61000-6-1:2007 specification requirements)
* Measured at NTP
** Not available on CWE
Note: Rough handling and transportation may cause a temporary reduction of CO2sensor accuracy. With time, the ABC function will
tune the readings back to the correct accuracy range. The default tuning speed is limited to 30 ppm per week.
Specications