Z
2
06
731-
0
B
Page 1 of 4 ©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 1118 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Pressure TM
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
•
Read and understand the instructions before installing this product.
• Turn o all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
If this product is used in a manner not specied by the manufacturer, the protection
provided by the product may be impaired. No responsibility is assumed by the
manufacturer for any consequences arising out of the use of this material.
Product Overview
The PWR Series remote pressure transducers are designed for dierential pressure applications. The sensors are
remotely installed on existing plumbing runs. The PWR is available with either armored (6 ft.) or shielded (10 or 20
ft) sensor cables, and it requires a 15 to 30 Vdc or 24 Vac power source to generate its output. The PWR is warranted
for a period of ve years.
PWR Series
Wet Media Remote Pressure Transducer
Specications
Media Compatibility 17-4 PH stainless steel
Input Power 15 to 30 Vdc, 24 Vac nom. 50/ 60 Hz*
Maximum Current Draw DC: 125 mA; AC: 280 mA
Output 3-wire transmitter; user-selectable 4 to 20mA/0 to 5V/0 to 10V
Status Indication Dual color LED
Proof Pressure 2x max. F.S. range**
Burst Pressure 5x max. F.S. range**
Accuracy at 25°C*** Ranges A and B: ±1% F.S. typical
Range C: ±1.5% F.S. typical
Range D: ±2% F.S. typical
(For less than or equal to 20 ft. (6.1 m) cable length)
Surge Damping Electronic; 1 or 5 second averaging
Long Term Stability ±0.25%
Zero Offset
(Bidirectional and Port
Swap Modes Only)
0.5%
Zero Adjust Pushbutton auto-zero and digital input (2-position terminal block)
Fittings ¼” NPT male thread, stainless steel 17-4 PH;
Overall thread length: 0.59” (conforms to ANSI/ASME B1.20.1 standard)
OPERATIONAL RANGES
0 to 50 psig 5/10/25/50 psid
0 to 100 psig 10/20/50/100 psid
0 to 250 psig 25/50/125/250 psid
Product Identication
PWR
Operational Range Cable Length
03 = 0 to 50 psid
04 = 0 to 100 psid
05 = 0 to 250 psid
006 = 6 ft (1.8 m)
010 = 10 ft (3.1 m)
020 = 20 ft (6.1 m)
= Standard
X
NISTDisplay
= LCD = Water
S
Media Cable
Blank = Standard†
A = Armored‡
L
† Standard cable available only in 10 ft and 20 ft lengths.
‡ Armored cable available only in 6 ft length.
Note: Extension of total cable length greater than 20 feet