environmental SenSorS inStallation GUiDe
Z202882-0T PAGE 1 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 08102
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Wet Media Differential Pressure Transducer
Installer’s Specifications
Media Compatibility 17-4 PH stainless steel
Input Power 12 to 30VDC, 24VAC nom.
Maximum Current Draw DC: 125mA; AC: 280mA
Output 3-wire transmitter; user-selectable 4-20mA/0-5V/0-10V†
Pressure Ranges:
0-50 psig 5/10/25/50 psid
0-100 psig 10/20/50/100 psid
0-250 psig 25/50/125/250 psid
0-3.5 barg 0.35/0.7/1.75/3.5 bard
0-7.0 barg 0.7/1.4/3.5/7.0 bard
0-17 barg 1.7/3.4/8.5/17.0 bard
Status Indication Dual color LED: solid green = normal, blinking green = low>high,
solid red = over range, blinking red = over pressure
Proof Pressure 2x max. F.S. range
Burst Pressure 5x max. F.S. range
Accuracy at 25°C* Ranges A, B, C: ±1% F.S.**
Range D: ±2% F.S.**
Surge Damping Electronic; 5-second averaging
Temperature Compensated Range 0° to 50°C (32° to 122°F);
TC Zero <1.5% of product F.S. per sensor;
TC Span <1.5% of product F.S. per sensor
Sensor Operating Range -20° to 85°C (-4° to 185°F)
Long Term Stability ±0.25%
Zero Adjust Pushbutton auto-zero and digital input (2-position terminal block)
Operating Environment -10° to 55°C (14° to 131°F); 10-90% RH noncondensing
Fittings psig models: 1/8” NPT female thread, stainless steel 17-4 PH
barg models: 1/8” BSPT female thread, stainless steel 17-4 PH
Physical White powder-coated aluminum
To conform to EMC Standards, use shielded cabling. Technical information is available from the
factory on request or on our website (www.veris.com/ce)
†Minimum input voltage for 4-20mA operation:
250 Ω loop (1-5V) = 12 VDC
500 Ω loop (2-10V) = 15 VDC
Minimum input voltage for volt operation:
0-5VDC output = 12 VDC
0-10VDC output = 15 VDC
* Accuracy combines linearity, hysteresis, and repeatability.
** F.S. is defined as full span of selected range in bidirectional mode.
PW SerieS PW SerieS
Dimensions
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
ProDuct iDentification
quick install
The PW Series sensor is designed to accept high differential pressure. Install the
sensor on a duct or pipe across a pump, filter, heat exchanger, compressor, or other
non-corrosive wet media. The dual sensor design eliminates the need for a bypass
valve, and the bi-directional capability reduces installation errors. A pushbutton
allows easy zero adjustment.
Mount sensor on a duct or pipe, across a pump, filter, or other pressure differential.1.
Wire as shown (see page 2).2.
Configure the jumpers (see page 2).3.
available
2.2"
(57 mm)
4"
(102 mm)
5.8"
(147 mm)
LOW HIGH
WET DIFFERENTIAL PRESSURE
Local Display
L = LCD Display
X = No Display
NIST
N = NIST
X = None
US or EU
S = Standard3
C = CE
Operational Range 1
03 = 0-50 psig
04 = 0-100 psig
05 = 0-250 psig
06 = 0-3.5 barg2
07 = 0-7.0 barg2
08 = 0-17 barg2
PW
1Select operational range according to maximum gauge pressure, NOT differential pressure.
Example: High gauge pressure=90 psig, Select 100 psig model (04).
2barg models use BSPT threads on sensor fittings.
3 Not available with barg units.
VERIS INDUSTRIES ™
inStallation GUiDe
PW SerieS
Z202882-0T PAGE 2 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 08102
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Wiring
JP8
JP7
JP6
JP3
JP2
JP1
ZERO
Analog Reverse/Normal
Port Swap/Normal
Bidirectional/Normal
Fast/Slow Surge Damping
5V/10V Output
mA/Volts Output
POWER
REMOTE ZERO
(Dry Contact)
DIGITAL CONTROL
Analog Input
0-5V/0-10V
or 4-20mA
Optional
Digital Output
POWER SOURCE
12 to 30 VDC/24 VAC
SIGNAL
COM
PW SERIES /
Range
A
B
C
D
HI PORT
100 psi
100 psi
50 psi
50 psi
0 psi
LO PORT
0 psi
50 psi
50 psi
100 psi
100 psi
4-20mA 0-10V
+100 psi
+50 psi
0 psi
-50 psi
-100 psi
Bidirectional Operation
Input Conditions Result Outputs Read
DP
20mA
16mA
12mA
8mA
4mA
10V
7.5V
5V
2.5V
0V
17.0 bar
17.0 bar
8.5 bar
8.5 bar
0 bar
0 bar
8.5 bar
8.5 bar
17.0 bar
17.0 bar
+17.0 bar
+8.5 bar
0 bar
-8.5 bar
-17.0 bar
20mA
16mA
12mA
8mA
4mA
10V
7.5V
5V
2.5V
0V
Output is either
mA or V
e.g. PW-04
e.g. PW-08
Range (psi)
Model
PW-03
PW-04
PW-05
A
50
100
250
B
25
50
125
C
10
20
50
D
5
10
25
Range (bar)
A
3.5
7.0
17.0
B
1.75
3.5
8.5
C
0.7
1.4
3.4
D
0.35
0.7
1.7
e.g. PW-04
e.g. PW-08
Use the Range switch to
select F.S. differeintial
pressure.
Model
PW-06
PW-07
PW-08
oPeration
Blink Codes:
LED Color Status
Solid Green Normal operation.
Flashing Green Low > High; use port swap jumper or bidirectional mode.
Solid Red Differential pressure is too high; select a higher pressure range.
Flashing Red Gauge pressure over sensor range; reduce line pressure or replace with a
higher range device.
Auto-Zero: Press and hold the Zero button for 2 seconds or provide contact closure
on the auxiliary ‘Remote Zero’ terminal to reset the output to zero pressure. To
protect the device from accidental zeroing, this feature is only enabled when the
detected pressure is within 5% of factory calibration.
configuration
Jumper Options Notes
JP1 Voltage (V) or Current (mA)
JP2 0-10V or 0-5V output span Use only if JP1 is set toV mode.
JP3 Slow or Fast Slow mode provides 5 second averaging for
surge damping.
JP6 Normal or Bidirectional Normal: 0 to F.S. pressure
Bidirectional: -F.S. pressure to +F.S. pressure;
output reads ½ when pressure is zero.
JP7 Normal or Port Swap Reverses polarity of the pressure ports (i.e.
makes the LO port operate as the HI port and
vice versa); used when the sensor is incorrectly
plumbed.
JP8 Normal or Analog Reverse Normal: output increases as pressure increases;
Reverse: output is maximum when pressure
differential is zero and decreases as pressure
increases.
Caution: This product uses a half-wave rectifier power supply. If the installer is using
a transformer to power the device, do not use the same transformer to power other
devices utilizing non-isolated full-wave power supplies.
Optional: Connect Zero terminals to digital output (contact closure) of control
system.
Caution: Zero input is for dry-contact only. Do not apply voltage to the Zero
terminals.

This manual suits for next models

6

Other Veris Industries Transducer manuals

Veris Industries EP3 Series User manual

Veris Industries

Veris Industries EP3 Series User manual

Veris Industries Hawkeye H720 User manual

Veris Industries

Veris Industries Hawkeye H720 User manual

Veris Industries PWR Series User manual

Veris Industries

Veris Industries PWR Series User manual

Veris Industries PW Series User manual

Veris Industries

Veris Industries PW Series User manual

Veris Industries Hawkeye 922 User manual

Veris Industries

Veris Industries Hawkeye 922 User manual

Veris Industries ENERCEPT H8035 User manual

Veris Industries

Veris Industries ENERCEPT H8035 User manual

Veris Industries PW2 Series User manual

Veris Industries

Veris Industries PW2 Series User manual

Veris Industries PH Series User manual

Veris Industries

Veris Industries PH Series User manual

Veris Industries PW Series User manual

Veris Industries

Veris Industries PW Series User manual

Veris Industries H623-10 User manual

Veris Industries

Veris Industries H623-10 User manual

Veris Industries PWXN07C User manual

Veris Industries

Veris Industries PWXN07C User manual

Veris Industries H622-20 User manual

Veris Industries

Veris Industries H622-20 User manual

Popular Transducer manuals by other brands

APPA 39T instruction manual

APPA

APPA 39T instruction manual

KEPO DAP9050-F5 specification

KEPO

KEPO DAP9050-F5 specification

Setra Systems 540 Series installation guide

Setra Systems

Setra Systems 540 Series installation guide

Analogic bk ultrasound 8811 user guide

Analogic

Analogic bk ultrasound 8811 user guide

Humminbird Trolling Motor Transducer installation guide

Humminbird

Humminbird Trolling Motor Transducer installation guide

Airmar Shorty P8 Owner's guide & installation instructions

Airmar

Airmar Shorty P8 Owner's guide & installation instructions

Veris EP2 Series manual

Veris

Veris EP2 Series manual

Siedle Novotechnik T Series manual

Siedle

Siedle Novotechnik T Series manual

turck IM12-FI01-1SF-1R Safety manual

turck

turck IM12-FI01-1SF-1R Safety manual

HBM T12 Mounting instructions

HBM

HBM T12 Mounting instructions

Gemco 958 Series installation manual

Gemco

Gemco 958 Series installation manual

SIAP+MICROS t002 TTT User manual and maintenance

SIAP+MICROS

SIAP+MICROS t002 TTT User manual and maintenance

OJ Electronics PTH-3202-DF instructions

OJ Electronics

OJ Electronics PTH-3202-DF instructions

EarthQuake Q10B installation manual

EarthQuake

EarthQuake Q10B installation manual

HBM S2M Series Mounting instructions

HBM

HBM S2M Series Mounting instructions

Theta Digital 30P operating manual

Theta Digital

Theta Digital 30P operating manual

aci WPR2 Series Installation and operation instructions