
028-5008-04 LIT-R851B -E04-EN Sep-19 5
LINEAR / PROGRESSIVE
The R851B series features 2 different staging sequences:
•LINEAR LAST IN FIRST OUT ( CONTROL SWITCH #1 OFF, FACTORY DEFAULT )
This is the regular mode, Stage #1 will always be the first to energize and the last stage to de-energize
•PROGRESSIVE FIRST IN FIRST OUT ( CONTROL SWITCH #1 ON )
In this mode, the stages are rotated to ensure a more uniform wear of the contactors and elements. For example, on an increase in
demand, stage 1 will be energized following by stage 2, etc. On a decrease in demand, stage 1 will de-energized first followed by
stage 2, etc.
Please verify that if this mode is enabled, the manufactured product still complies with active codes and regulations.
VERNIER STAGE SELECTION AND WIRING
The Viconics R851B series step controller has an integrated vernier control output. This output will give a precise and full modulation
of the load from 0 to 100% of the total capacity of the unit. If a master slave application is used, always connect the vernier output of
the master unit.
RATIO SETTING ( See also slave application section at the end )
First adjust the vernier stage ratio potentiometer. This will insure a smooth capacity rise of the total load.
Example 1:
The total unit has 100 kW divided in 10 equal stage of 10 kW.
If only 10 kW is used as the modulating stage, then the heater would have 9 on/off mechanical stage plus
one modulating stage. This modulating stage has the same value as all the other stage. Adjust the vernier stage ratio
potentiometer to 100%.
Example 2:
The total unit still has 100 kW divided in 10 equal stage of 10 kW.
If 20 kW are used as the modulating stage, then the heater would have 8 on/off mechanical stage plus one modulating stage.
The modulating stage has twice the value as all the other stage. Adjust the vernier stage ratio potentiometer to 200%.
ADJUSTMENTS
Functions of the units can be configured with six dip switch and 2 potentiometers.
0 to 9 min.
Step up interstage delay potentiometers setting
2 potentiometers are used to adjust the interstage delay from 0 seconds up to10 minutes.
The value selected by both potentiometers will add up for the total step up interstage delay.
This delay is the minimum time delay between each step activation when the control signal rises
Control
switch S2
ON
1 2 3 4 5 6
Step down & minimum ON time setting ( Control switch S2 )
Control switch S2 Off = 2 seconds On = 5 seconds
This delay acts as a minimum ON time when each step is activated
The delay is also the step down interstage delay when the control signal drops