Viconics VTR8300 Series User guide

Fan Coil Unit Application Guide
VTR8300/VT8300 Series Room Controllers
For firmware Release 2.1

TABLE OF CONTENTS
VTR83 - 3-SPEED FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
VTR83 - ECM FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
VT83 - 3-SPEED FAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
VT83 ECM FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
VT83 - 3-SPEED MIXED VOLTAGE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
APPENDIX A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
APPENDIX B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
APPENDIX X. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
DEPLOYMENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

3
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Commercial interface (local override)
Power Part Number Description Humidity PIR ZigBee Communication
VTR8350A5000B
BACnet
®
fan coil Room Controller
Yes No No BACnet®
VTR8350A5500B
BACnet
®
fan coil Room Controller
Yes Yes No BACnet®
VTR8350A5500BP
BACnet
®
fan coil Room Controller
Yes Yes Yes BACnet®
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components; the VTR8300 Room
Controller and the VC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil unit and temperature
controller to be re-used, thereby reducing overall costs and installation time.
The VC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional
horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The Relay Pack is
not required for the VT8300 Series models.
VTR8300 AND VC3000 | LINE-VOLTAGE FAN COIL ROOM CONTROLLERS AND RELAY PACKS
Transformer Relay Packs for VTR8300 Series
Power Part Number Description
VC3500E5000 Transformer relay pack five relay fan outputs
VC3504E5000 Transformer relay pack five relay fan outputs, and four inputs
VC3514E5000 Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs
VC3400E5000 Transformer relay pack four relay outputs and smart VDC output
VC3404E5000 Transformer relay pack four relay outputs, smart VDC output, and four inputs
VC3300E5000 Transformer relay pack three relay fan outputs
ZigBee Pro Module for VT(R)8300 Series
Power
Part Number Description
VCM8000V5000P
Release 20 Optional ZigBee Pro module for VT(R)8300 Series room controllers.

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
4
To other
VC3xxxE
Relay
Pack
Terminal Controller
Relay Pack
VTR83xxA VC3504E
4 - Tx / Rx
5 - 7 Vdc Power Hot
6 - Power Common
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
Relay Pack
VC3300E
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
Terminal Controller
Terminal Controller
To others
To others
13 - COM +
14 - COM -
VTR83xxA VTR83xxA
13 - COM +
14 - COM -
Only ONE VC3xxxE Relay Pack with remote
monitoring inputs can be used under a single
VTR83xxA Controller. All other slave units must be
VC3xxxE Relay Pack(s) WITHOUT remote inputs. A
maximum of 10 VC3xxxE Relay Packs can be used
for a single VTR83xxA Room Controller.
From VTR83xxA to first VC3xxxE Relay Pack
• Uses existing or new field wires
• A minimum of 3 wires are required 14-18 Ga,
• Solid or Stranded, shield not necessary
From first VC3xxxE to all other slave
VC3xxxE Relay Pack(s)
• Uses existing or new field wires
• A minimum of 2 wires are required 14-18 Ga,
Solid or Stranded, shield not necessary
• Connect only two wires: Tx/Rx (1) and Power
Common (3).
Daisy Chained Topology
Star Topology Mixed Daisy Chained & Star Topology
COMMUNICATION WIRING TO VC3XXXE RELAY PACK
Network Wiring Topology
BACnet®Communication Shielded Wiring (if required)
• NOTE: See VTR8300 BACnet®integration manual for more details
• Installation Note:
The maximum distance between the SER8300
Room Controller and the SC3000 relay pack is
recommended at 50ft (15m) or less.
Terminal Identification All VTR83xx
Terminal Equipment Controller
Terminal 4 Tx – Rx Communication
Terminal 5 Power Hot 7.0 VDC
Terminal 6 Power Common
Terminal 12 ECM 0-10 VDC output
Terminal 13 BACnet +
Terminal 14 BACnet -
Terminal 16 BI 1 ( Configurable )
Terminal 17 BI 2 ( Configurable )
Terminal 18 Scom
VTR8300 | TERMINAL IDENTIFICATION AND FUNCTION

5
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the VT8300 Room Controller.
The VT8300 Room Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage solutions, when control
of both line-voltage and low-voltage end devices is required.
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power Part Number Description Humidity PIR ZigBee Communication
VT8350U5000B
BACnet
®
fan coil Room Controller
Yes No No BACnet®
VT8350U5500B
BACnet
®
fan coil Room Controller
Yes Yes No BACnet®
VT8350U5500BP
BACnet
®
fan coil Room Controller
Yes Yes Ye s BACnet®
VT8300 LOW-VOLTAGE 24 VAC FAN COIL ROOM CONTROLLERS
Mixed-voltage Relay Packs for VT8300 Series
Part Number Description
VC1300E5000
3 on/off outputs, 110/130V 3 speed
VC2300E5000
3 on/off outputs, 220/240V 3 speed
Wireless Accessories for VT(R)8300 Series
Part Number Description
SED-DOR-P-5045 Wireless door switch
SED-WIN-P-5045 Wireless window switch
SED-WDS-P-5045 Wireless window and door switch
SED-WDC-G-5045 Wireless window/door sensor
SED-CMS-P-5045 Wireless ceiling mounted motion sensor
SED-WMS-P-5045 Wireless wall mounted motion sensor
SED-MTH-G-5045 Wireless motion/temperature/humidity sensor
SED-WLS-G-5045 Wireless water leakage sensor

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
6
Fan Type - ECM
Control Type On/Off Floating Analog
1- BO1 Normally Close Heat Valve Close Heat valve Not used
2- BO2 Not used Not used Not used
3- BO3 Not used Not used Not used
4- BO4 ECM Fan Start ECM Fan Start ECM Fan Start
5- RC / 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 V~ Hot
6- C / 24 V~ Com 24 V~ Com 24 V~ Com 24 V~ Com
7- RH Aux Heat Aux Heat Aux Heat
8- BO8 Aux Heat Aux Heat Aux Heat
9- UO9 Normally Close Cool Valve Close Cool Valve Not used
10- UO10 ECM Fan Analog Output ECM Fan Analog Output ECM Fan Analog Output
11- UO11 Normally Open Cool Valve Open Cool Valve Analog Heat valve
12- UO12 Normally Open Heat Valve Open Heat Valve Analog Cool Valve
13- RS485 + RS485 +
14- RS485 - RS485 -
15- RS485 Ref RS485 Ref
16- UI16 UI16 Function
17- UI17 UI17 Function
18-Scom Common
19- UI19 UI19 Function
20- UI20 Remote Room Sensor
21-Scom Common
22- UI22 Remote Supply Sensor
23- UI23 Not used
24- UI24 Not used
VT8300 | TERMINAL IDENTIFICATION AND FUNCTION FOR 3-SPEED FAN

7
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
VT8300 | TERMINAL IDENTIFICATION FOR ECM FAN SYSTEM
Fan Type - ECM
Control Type On/Off Floating Analog
1- BO1 Normally Close Heat Valve Close Heat valve Not used
2- BO2 Not used Not used Not used
3- BO3 Not used Not used Not used
4- BO4 ECM Fan Start ECM Fan Start ECM Fan Start
5- RC / 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 V~ Hot
6- C / 24 V~ Com 24 V~ Com 24 V~ Com 24 V~ Com
7- RH Aux Heat Aux Heat Aux Heat
8- BO8 Aux Heat Aux Heat Aux Heat
9- UO9 Normally Close Cool Valve Close Cool Valve Not used
10- UO10 Analog ECM Fan Analog ECM Fan Analog ECM Fan
11- UO11 Normally Open Cool Valve Open Cool Valve Analog Heat valve
12- UO12 Normally Open Heat Valve Open Heat Valve Analog Cool Valve
13- RS485 + RS485 +
14- RS485 - RS485 -
15- RS485 Ref RS485 Ref
16- UI16 UI16 Function
17- UI17 UI17 Function
18-Scom Common
19- UI19 UI19 Function
20- UI20 Remote Room Sensor
21-Scom Common
22- UI22 Remote Supply Sensor
23- UI23 Not used
24- UI24 Not used

VTR83 3-Speed

9
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
System Fan Cooling Heating Other
4 pipes 3 Speed 2 positions valve 2 positions valve Door and motion detect
4 pipes 3 Speed 2 positions valve 2 positions valve Motion detect
4 pipes Twice 3 speed 2 positions valve 2 positions valve Two VC3500 relays
2 pipes 3 Speed 2 positions valve Changeover sensor Window sensor
2 pipes 3 Speed 2 positions valve Heating SSR Dehumidification
2 pipes 3 Speed 2 positions valve Changeover sensor Motion detect
2 pipes 3 Speed 2 positions valve Changeover sensor Fresh air damper
VTR83
1, 2 OR 3-SPEED FAN APPLICATIONS
See Appendix B for relay pack wiring.

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
10
Configuration
Parameter Name Configuration Settings
Fan control 3 speed
Fan Menu L-M-H-A
Fan cont. heat. On
BI1 Motion NO or Motion NC (remote PIR sensor only)
BI2 Door Dry
Pulsed heating Off
Pipe no. 4
Seq. operation Ht - Cl
VTR83X0A5X00B WITH VC3500E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/
COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
VC3500E5000
2 POSITION
COOLING VALVE
Cooling Coil
2 POSITION
HEATING VALVE
Heating Coil
Airow Direction
3 Speed Fan
VTR83X0
Onboard
PIR Sensor
AND / OR
OR*
Wired Remote
PIR Sensor
Wireless Remote
PIR Sensor

11
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Tx/Rx
7 Vdc
Com
1
2
3
VC3500E5000
VTR83X0
WHT
BLK
RED
BLU
GRN
YEL
ORG
NOTE: See Appendix B for VC3500
wiring to fan coil
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
Tx / Rx
7 VDC
Com
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closed.
Wireless Door Switch and Motion
Wireless door switch automatically toggles occupancy to standby.
Motion will switch to occupied as long as the door stays closed
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Can be configured for 2-pipe systems (without changeover).
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, or remote
night setback.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires
are not energized. On demand, system will automatically
switch “on” low (red), medium (blue) or high (brown) speed.

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
12
VTR8350A5X00B WITH VC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH
3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
Configuration
parameter name Configuration settings
Fan control 3 speed
Fan menu L-M-H-A
Fan cont. heat On
Pulsed heating On
Pipe no. 2
Seq. operation Cool - Rht
Cooling Coil Electric Heating
SSR
SOLID STATE RELAY
(GENERIC)
VC3404E5000
2 POSITION
COOLING VALVE
VTR8350
Airow Direction
3 Speed Fan

13
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
1
2
3
4
5
6
7
8
9
10
SOLIDSTATE
RELAY
(4-32Vdc)
(-)
(+)
VC3404E5000
VTR8350
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
Tx / Rx
7 VDC
Com
WHT
BLK
RED
BLU
GRN
YEL
ORG
NOTE: See Appendix B for VC3400
wiring to fan coil
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
14
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on”
low (red), medium (blue) or high (brown) speed.
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or
provide alarms for service or filter monitoring.
• Universal input can be configured for changeover sensor.

15
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
VTR83X0A5X00B WITH VC3504E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/
COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN
Configuration
Parameter Name Configuration Settings
Fan control 3 speed
Fan Menu L-M-H-A
Fan cont On
BI1 Window
RUI1 COS
Pipe No 2
Seq. operation Cool
VC3504E5000
2 POSITION
Cooling / Heating Coil Supply Sensor
Airow Direction
3 Speed Fan
VTR83X0
COOLING VALVE / HEATING VALVE
SENSOR
C/O
SENSOR
Onboard
PIR Sensor

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
16
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
1
2
3
4
5
6
7
8
VC3504E5000
VTR83X0
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
Tx / Rx
7 VDC
Com
WHT
BLK
RED
BLU
GRN
YEL
ORG
10K type 2
10K type 2
NOTE: See Appendix B for VC3500
wiring to fan coil
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens
to maintain room temperature, else valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve
opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Wireless Window Switch
Wireless window switch automatically locks out heating/cooling
when window is opened.

17
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or
provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on”
low (red), medium (blue) or high (brown) speed.

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
18
VTR83X0A5X00B WITH VC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED
FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
Configuration
Parameter Name Configuration Settings
Fan control 3 speed
Fan menu L-M-H-A
Fan cont. heat On
RUI1 COS
Pulsed Heating Occ Out
Pipe no. 2
Seq. operation Cool
VC3514E5000
2 POSITION
Airow Direction Cooling / Heating Coil Supply Sensor
3 Speed Fan
VTR83X0
COOLING VALVE / HEATING VALVE
Fresh Air
DAMPER
Return Air
SUPPLY SENSOR
C/O
SENSOR
10K OHM TYPE 2
10K OHM TYPE 2

19
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
1
2
3
4
5
6
7
8
9OCC -
VC3514E5000
VTR83X0
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
Tx / Rx
7 VDC
Com
NOTE: See Appendix B for VC3500
wiring to fan coil
For 7 Vdc SSR
Fresh Air Damper
WHT
BLK
RED
BLU
GRN
YEL
ORG
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating. The occupancy output opens fresh air damper to
minimum position.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve
opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating
valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires
are not energized. On demand, system will automatically
switch “on” low (red), medium (blue) or high (brown) speed.

Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
20
Configuration
Parameter Name Configuration Settings
Fan control 3 speed
Fan menu L-M-H-A
Fan cont. heat On
Pipe No 4
Seq. operation Ht-Cl
VTR83X0A5X00B WITH VC3500E5000 AND VC3300E5000 RELAYS: HEATING/COOLING 4-PIPE FAN COIL
UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK
VC3300E5000
2 POSITION
COOLING VALVE
Cooling Coil
2 POSITION
HEATING VALVE
Heating Coil
Airow Direction
3 Speed Fan
VC3500E5000
VTR83X0
Other manuals for VTR8300 Series
5
This manual suits for next models
4
Table of contents
Other Viconics Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Delta Electronics
Delta Electronics DTE Accessory DTE-2DS instruction sheet

Stulz
Stulz CyberLab Original instructions

Temptronic
Temptronic ThermoStream TP04100A Interface & Applications manual

Supco
Supco VG64 installation guide

KMC Controls
KMC Controls STE-6010 installation guide

MAXTHERMO
MAXTHERMO MC-2438 Operation manual