Victaulic UM Series User manual

I-UM
I-UMINSTALLATION, MAINTENANCE, INSPECTION, AND TESTING INSTRUCTIONS
REV_A
Series UM Universal Manifold Assembly
(With or Without Control Valve)
WARNING
• Read and understand all instructions before attempting to install any Victaulic products.
• Always verify that the piping system has been completely depressurized and drained
immediately prior to installation, removal, adjustment, or maintenance of any Victaulic
products.
• Confirm that any equipment, branch lines, or sections of piping that may have been isolated
for/during testing or due to valve closures/positioning are identified, depressurized, and
drained immediately prior to installation, removal, adjustment, or maintenance of any
Victaulic products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property
damage.
• The Series UM Universal Manifold Assembly shall be used only in fire protection systems that are designed and installed in accordance
with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in
accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of
systems from freezing temperatures, corrosion, mechanical damage, etc.
• These installation instructions are intended for an experienced, trained installer. The installer shall understand the use of this product and
why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper product installation.
Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system
failure, resulting in death or serious personal injury and property damage.

I-UM_2 REV_A
I-UM / Series UM Universal Manifold Assembly / Installation, Maintenance, Inspection, and Testing Instructions
INTRODUCTION
The Series UM Universal Manifold Assembly is a complete manifold assembly that includes a flow switch, Universal Test and Drain (UTD) assembly,
system pressure gauge, and a pressure relief valve.
FLOOR CONTROL VALVE ASSEMBLY – The UM meets NFPA 13 requirements for “Floor Control Valve Assemblies” where check valves are not
required (i.e. pressure-reducing control valves that are recognized as checking devices) in multi-story buildings requiring zoning by floor, or whenever
separate control and floor zoning is specified. Typically, larger sizes are utilized on vertical risers where check valves are not required. Per NFPA 13
requirements, all UM assemblies contain a listed pressure relief valve, which is pre-piped to drain.
NOTICE
• NFPA 13 requires a test connection capable of providing a flow rate equal to or less than one sprinkler of the smallest orifice in the system.
• Drawings and/or pictures in this manual may be exaggerated for clarity.
• This product and this installation, maintenance, and testing manual contain trademarks, copyrights, and/or patented features that are the
exclusive property of Victaulic.
ASSEMBLY DRAWINGS
5
6
1
2
3
7
4
5
6
7
4
2
1
3
1 ¼ – 3-INCH/42.4 – 88.9-MM SIZES
(3-INCH/88.9-MM ASSEMBLY SHOWN ABOVE)
4 – 8-INCH/114.3 – 219.1-MM SIZES
(8-INCH/219.1-MM ASSEMBLY SHOWN ABOVE)
Item Description
1Body*
2Flow Switch
3Rigid Coupling
4Control Valve with Internal Supervisory Switch (Optional)†
5Adjustable Pressure Relief Valve (ARV)**
6Universal Test and Drain Assembly (UTD)‡
7Stainless Steel Braided Flexible Drain Hose Assembly (Grooved x Grooved Connections)
* UL Listed under File EX27312 Riser Manifold with Flow Detection
† The control valve for 1 ¼ – 1 ½-inch/42.4 – 48.3-mm sizes is the Victaulic Series 728 FireLock™ Ball Valve.
The control valve for 2 – 8-inch/60.3 – 219.1-mm sizes is the Victaulic Series 705 FireLock™ Butterfly Valve
** NFPA 13 requirement that relief valve is UL Listed – Pre-piped to drain, preset for 175 psi/12 Bar, and adjustable to 310 psi/21 Bar for high-pressure
system conditions and hydrostatic tests. NOTE: It is not necessary to remove the Adjustable Pressure Relief Valve (ARV) to perform a hydrostatic test.
The ARV may be adjusted temporarily to a pressure above the test pressure.
‡ For flow testing, the 1-inch/33.7-mm Universal Test and Drain Assembly (UTD) utilizes a K2.8 test orifice; the 1 ¼-inch/42.4-mm UTD utilizes a K4.2 test
orifice; and the 2-inch/60.3-mm UTD utilizes a K5.6 test orifice. Operating positions for the UTD are: Off (normal operating condition), Drain (full drain),
and Test (flow through K-factor orifice).

I-UM_3
REV_A
I-UM / Series UM Universal Manifold Assembly / Installation, Maintenance, Inspection, and Testing Instructions
INSTALLATION
• The UM is shipped preassembled in a single box. Confirm that adequate space is available for the assembly.
• Flush water supply piping. Before installing the UM, flush the water supply piping thoroughly to remove all foreign material.
• The UM shall be installed in accordance with all applicable installation standards (i.e. NFPA 13 or other).
• Protect system from freezing temperatures. The UM and supply piping SHALL NOT be located in an area where exposure to freezing
temperatures or mechanical damage may occur. Install the UM in an accessible and visible location that is maintained at or above a minimum
temperature of 40ºF/4ºC.
• Confirm material compatibility. It is the system designer’s responsibility to confirm material compatibility of the UM and associated accessories
when a corrosive environment or contaminated water is present.
• The UM may be installed in the horizontal or vertical (flow upward) orientation.
• All electrical connections shall be made per the applicable installation standard and/or the National Electric Code (i.e. NFPA 70, NFPA 72 or
other).
• Verify that the braided flexible drain hose does not become kinked or permanently deformed when routing it to the drain connection. The flexible
braided drain hose is intended for use only downstream of a drain valve and shall not be used anywhere else within the system.
• All coupling connections shall be made by referencing the current version of the installation instructions, which can be downloaded by scanning
the QR codes below. All coupling connections shall be checked to verify proper installation, in accordance with the following instructions.
I-009N Installation Instructions
For connections to the control valve on certain UM sizes
For connections to the drain hoses on 2 ½ inch/73.0 mm
and larger UM sizes
I-108 Installation Instructions
For connections to the drain hose on certain
UM sizes
I-109 Installation Instructions
For connection to the control valve on certain UM sizes
For connections to the drain hose on certain UM sizes
• Per NFPA 13, proper hydrostatic test procedures shall be followed. NOTE: It is not necessary to remove the ARV to perform a hydrostatic
test. The ARV may be adjusted temporarily to a pressure above the test pressure. Verify that the ARV is returned to its normal setting after
completing the hydrostatic test.
FLOW SWITCH WIRING
The flow switch includes two sets of switches. One set can be used to activate the central fire alarm system, while the other set can be used to
activate a local alarm, if necessary. Refer to the schematic below for the wiring diagram.
BLACK
(LINE/HOT)
NEUTRAL
WHITE
CIRCUIT
BREAKER
COM
COM
NO
NO
WHITE
WIRE NUT WIRE NUT
LOCAL
AUDIBLE/VISUAL
ANNUNCIATOR
LOAD OUT TO
AUDIBLE/VISUAL
ANNUNCIATOR
FIRE PANEL OR
ADDRESSABLE
MODULE
BLACK

I-UM_4 REV_A
I-UM / Series UM Universal Manifold Assembly / Installation, Maintenance, Inspection, and Testing Instructions
CONTROL VALVE WIRING
The following wiring instructions apply to both the Victaulic Series 728 FireLock™Ball Valve and Victaulic Series 705 FireLock™Butterfly Valve.
Scan QR code for access to the Series 728
Installation and Wiring Instructions
Scan QR code for access to the Series 705
Installation and Wiring Instructions
1. The supervisory switch contains two single-pole, double-throw, prewired switches.
2. Switches are rated:
10 amps @ 125 or 250 VAC/60 Hz
0.50 amps @ 125 VDC
0.25 amps @ 250 VDC
3. Switches supervise the control valve in the “fully opened” position. Switches will not supervise the valve in the “closed” position.
4. One switch contains two #18 insulated wires per terminal, which permit complete supervision of leads (refer to diagrams and notes below). The
second switch contains one #18 insulated wire per terminal. This double circuit provides flexibility to operate two electrical devices at separate
locations, such as an indicating light and an audible alarm, in the area that the control valve is installed.
5. A #14 insulated ground lead (green) is provided.
Switch #1 = S1 For connection to the supervisory circuit of a UL Listed alarm control panel
Switch #2 = S2 Auxiliary switch that may be connected to auxiliary devices, per the authority having jurisdiction
S1 {Normally Closed Contact: (2) Blue
Switch is Open When Valve is in “Fully Opened” Position
Common Contact: (2) Yellow
S2{Normally Closed Contact: Blue with Orange Stripe
Normally Open Contact: Brown with Orange Stripe
Common Contact: Yellow with Orange Stripe
Only S1 (two leads per terminal) may be connected to the fire alarm control panel.
Connection of alarm switch wiring shall be in accordance with NFPA 72, and the auxiliary switch per NFPA 70 (NEC).
FIRE ALARM
CONTROL PANEL
SUPERVISORY
CIRCUIT
COMMON (YELLOW)
BLUE
CONTACT RATINGS:
16A 125V/250 VAC
VOLTAGE
SOURCE
COMMON
(YELLOW/ORANGE)
GEAR OPERATOR
S–1 COMMON (YELLOW)
BLUE
GREEN
BROWN/ORANGE
BLUE/ORANGE
VALVE WIRING SHOWN WITH VALVE IN OPEN POSITION
S–2
END-OF-LINE
RESISTOR
OPERATOR CASE
GROUND
AUX. DEVICE
(BELL/HORN)
ARV SETTING PROCEDURE
Hex Cap
Turn clockwise for
higher pressure setting
or counterclockwise for
lower pressure setting
DO NOT Adjust
Calibration Screw
Inside Hex Cap
• The 300-psi/21-Bar ARV is factory set to relieve at approximately 175 psi/12 Bar.
• The ARV may be reset to a higher pressure; however, it shall be reset to relieve at a pressure that is in
accordance with requirements of the local authority having jurisdiction (typically nominal 10 psi/0.7 Bar above
the expected normal system pressure).
• To reset the ARV, use an adjustable crescent wrench to turn the hex cap clockwise for a higher pressure setting
or counter-clockwise for a lower pressure setting. Use the calibrated lines on the stem for an approximate relief
pressure setting. One full turn of the hex cap will result in approximately 25 psi/1.7 Bar increase or decrease.
• DO NOT adjust the calibration screw inside the hex cap, as indicated in the drawing to the left.
• To verify the new setting, isolate the ARV and use a small hydrostatic pump attached to the supply. Increase
the pressure to 10 psi/0.7 Bar above the expected normal system pressure. Readjust the ARV, as needed, to
maintain a 10 psi/0.7 Bar higher relief setting.
NOTE: An ARV replacement kit is available for order. This kit includes the ARV, a hose, and two worm gear hose
clamps.

I-UM_5
REV_A
I-UM / Series UM Universal Manifold Assembly / Installation, Maintenance, Inspection, and Testing Instructions
TESTING
Refer to NFPA 25, FM Datasheets, or any applicable local requirements to perform testing. The authority having jurisdiction in the area may require
these tests on a more frequent basis. Verify these requirements by contacting the authority having jurisdiction in the affected area.
Before proceeding with any tests involving water flow, the following precautions shall be taken.
NOTE: It is not necessary to remove the ARV to perform a hydrostatic test. The ARV may be adjusted temporarily to a pressure above the test
pressure. Verify that the ARV is returned to its normal setting after completing the hydrostatic test.
1. Check for alarm connections to a central station or fire department. If such connections are found, notify the authority having jurisdiction,
remote station alarm monitors, and those in the affected area before proceeding with testing. NOTE: A main drain test may also operate local
fire alarms, unless they are temporarily disabled.
2. Check the location where the test connection discharges to verify that all is clear and that there is no possibility of water flow causing property
damage or personal injury.
3. Check the end of the test connection to verify that it is unobstructed. To achieve a satisfactory test, there shall be an unrestricted flow of water
when the handle on the UTD is in the “DRAIN” (full drain) position.
4. Move the handle on the UTD to the “TEST” (flow through K-factor orifice) position. Verify that an alarm condition results within the timeframe
specified by the local authority having jurisdiction.
5. Move the handle on the UTD to the “OFF” (normal operating) position. NOTE: The ARV is located on the upstream side of the UTD and will
continue to vent excess system pressure with the handle on the UTD in the “OFF” (normal operating) position.
REQUIRED INSPECTIONS AND/OR MAINTENANCE
WARNING
• Depressurize and drain the piping system before attempting to perform any maintenance.
• The building owner or their representative is responsible for maintaining the fire protection system in proper
operating condition.
• To ensure proper system operation, refer to NFPA 25, FM Datasheets, or any applicable local requirements for
valve inspection requirements. The authority having jurisdiction in the area may require these inspections on a
more frequent basis. Verify these requirements by contacting the authority having jurisdiction in the affected
area, and always refer to the instructions in this manual for additional inspection and testing requirements.
• The frequency of inspections shall be increased in the presence of contaminated water supplies, corrosive/scaling
water supplies, and corrosive atmospheres.
• Any activities that require taking the valve out of service may eliminate the fire protection provided. A fire patrol
is strongly recommended for the affected areas.
• Before servicing or testing the system, notify the authority having jurisdiction.
Failure to follow these instructions could cause system failure, resulting in death or serious personal injury and
property damage.
Refer to NFPA 25, FM Datasheets, or any applicable local requirements to perform inspections and/or maintenance. The authority having jurisdiction
in the area may require inspections and/or maintenance on a more frequent basis. Verify these requirements by contacting the authority having
jurisdiction in the affected area.
1. Notify the authority having jurisdiction, remote station alarm monitors, and those in the affected area before performing any inspections, testing,
or maintenance that requires closing the control valve.
2. Verify that the system is completely depressurized and drained immediately prior to performing maintenance. NOTE: Keep the handle on the
UTD in the “DRAIN” (full drain) position during any maintenance.
3. The water supply shall be free from sediment or other debris. During an inspection of a water control valve, if sediment or other debris is noted,
a further examination of internal valve parts is required. Remove all deposits from all operating components and ports.
Flow Switch (All Sizes):
Periodic testing and inspection is required for the flow switch. Scan the QR code provided for complete flow switch
and paddle replacement instructions.
Scan QR code for flow switch
used on all UM sizes
ARV (All Sizes): The ARV is not field serviceable. If leakage is observed, test the pressure setting by referring to the “ARV Setting Procedure.” The
ARV shall be replaced if it does not respond to field adjustments. NOTE: Visual calibration lines on the ARV are used for approximate adjustment.
Verify the pressure setting with a calibrated pressure gauge.
UTD (All Sizes): The UTD does not require any regularly scheduled maintenance and is not field serviceable.

I-UMINSTALLATION, MAINTENANCE, INSPECTION, AND TESTING INSTRUCTIONS
Series UM Universal Manifold Assembly
(With or Without Control Valve)
For complete contact information, visit victaulic.com
I-UM 15847 REV A UPDATED 03/2021 Z0000UM000
VICTAULIC AND FIRELOCK ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES
IN THE UNITED STATES AND/OR OTHER COUNTRIES. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
Table of contents
Other Victaulic Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Siemens
Siemens SIMATIC ET 200SP HA Equipment manual

Festo
Festo 571816 operating instructions

KTR
KTR KTR-STOP RL Operating & assembly instructions

Bosch
Bosch Rexroth ABZSS operating instructions

Emerson
Emerson CASH VALVES Installation, operation and maintenance instructions

PPI
PPI SMART ROLL operation & maintenance