I-VICFLEX.VS1_2 REV_C
I-VICFLEX.VS1 / Victaulic®VicFlex™Style VS1 Dry Sprinkler/ Installation Instructions
IMPORTANT INSTALLATION INFORMATION
• Victaulic®VicFlex™Style VS1 Dry Sprinklers must be installed
according to current, applicable National Fire Protection
Association (NFPA 13, 13D, 13R, etc.) standards or equivalent
standards. Victaulic®VicFlex™Style VS1 Dry Sprinklers are
intended to be installed in wet, dry, or preaction actuated systems.
Deviations from these standards or alterations to Victaulic®
VicFlex™Style VS1 Dry Sprinklers will void any Victaulic warranty.
In addition, installations must meet provisions of the local authority
having jurisdiction and local codes, as applicable.
• Transport and store Victaulic®VicFlex™Style VS1 Dry Sprinklers in
a cool, dry environment in their original packaging.
• Refer to the specific product submittal for applications and
listing information. These submittals are located in Sections
10 and 40 of the Victaulic G-100 Catalog or on the Victaulic
website at victaulic.com.
• Size the piping system to provide the minimum operating pressure
of 7 psi/0.5 Bar/48 kPa.
• Per NFPA requirements, flush the system to remove foreign
material. Continue to flush the system until water runs clear.
• DO NOT install sprinkler system piping through heating ducts.
• DO NOT connect sprinkler system piping to domestic hot water
systems.
• DO NOT install Victaulic®VicFlex™Style VS1 Dry Sprinklers where
they will be exposed to temperatures that exceed the maximum
ambient temperature rating for the product.
• Victaulic®VicFlex™Style VS1 Dry Sprinklers have limited
flexibility and are intended only to be installed with bends not
less than their respective minimum bend radii.
• Protect wet piping systems from freezing temperatures.
• If construction is altered, refer to applicable standards to determine
if additional Victaulic®VicFlex™Style VS1 Dry Sprinklers are
required.
• DO NOT install Victaulic®VicFlex™Style VS1 Dry Sprinklers that
have been dropped or struck by another object, even if they do
not appear damaged. Never install glass bulb sprinklers if the bulb
is cracked or if there is a loss of liquid from the bulb. Discard and
replace any Victaulic®VicFlex™Style VS1 Dry Sprinklers that are
damaged or show signs of corrosion.
• Before installation, verify that the Victaulic®VicFlex™Style VS1 Dry
Sprinkler is the proper style, orifice size, and temperature rating for
the intended service.
• VICTAULIC®VICFLEX™STYLE VB2 BRACKET ASSEMBLIES
SHALL BE USED ONLY WITH STYLE VS1 RECESSED PENDENT
SPRINKLERS.
• VICTAULIC®VICFLEX™STYLE VB3 BRACKET ASSEMBLIES
SHALL BE USED ONLY WITH STYLE VS1 CONCEALED
PENDENT SPRINKLERS.
• DO NOT paint, coat, plate, or alter Victaulic®VicFlex™Style
VS1 Dry Sprinklers. Victaulic®VicFlex™Style VS1 Dry Sprinklers
that have been altered from their manufactured condition may
not function properly and will void any agency listings and/or
approvals.
• DO NOT test Victaulic®VicFlex™Style VS1 Dry Sprinklers with a
heat source. The glass bulb can weaken or shatter if exposed to a
heat source during testing.
• Victaulic®VicFlex™Style VS1 Dry Sprinklers that have operated
cannot be reassembled or reused, per NFPA requirements. When
replacing sprinklers, use new sprinklers of the same type, orifice,
temperature, and response.
• DO NOT clean Victaulic®VicFlex™Style VS1 Dry Sprinklers
with soapy water, detergents, ammonia, cleaning fluids, or other
chemicals. Remove any dust, lint, etc. with a soft, dry cloth.
• Inspect Victaulic®VicFlex™Style VS1 Dry Sprinklers on a regular
basis for corrosion, mechanical damage, obstructions, etc. The
frequency of inspections may vary due to corrosive atmospheres/
water supplies and activities around the sprinklers.
• DO NOT hang anything from or attach anything to Victaulic®
VicFlex™Style VS1 Dry Sprinklers. Obstructing the discharge
pattern will prevent the sprinkler from operating properly.
• The owner is responsible for maintaining the fire protection system
in proper operating condition.
• For minimum maintenance and inspection requirements, refer to
NFPA 25 and any other applicable NFPA standards that describe
the care and maintenance of sprinkler systems. In addition, the
authority having jurisdiction may have additional maintenance,
testing, and inspection requirements that must be followed.
WARNING
• Replacement/relocation of this Victaulic®VicFlex™Style VS1
Dry Sprinkler MUST be performed by qualified personnel
familiar with the system’s original design criteria, sprinkler
listings/approvals, and state and local codes (including NFPA 13
standards).
Failure to replace/relocate Victaulic®VicFlex™Style VS1 Dry
Sprinklers properly could affect their performance during a fire,
resulting in serious personal injury and property damage.
STYLE VS1 SPRINKLER ASSEMBLY DRAWING
3
2
1
Recessed Pendent Shown Above
Item Description
1Swivel Hex Nut
2Weld Fitting
3Inlet