© 2008-2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS
, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
TFP260
Page 4 of 4
Care and
Maintenance
The Tyco®Series RFII must be
maintained and serviced in accordance
with the following instructions.
NOTIce
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tem from the proper authorities and
notify all personnel who may be affect-
ed by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap be-
tween the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper oper-
ation of the sprinkler. If the ceiling re-
quires repainting after sprinkler instal-
lation, ensure that the new paint does
not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Replace sprinklers that are leaking or
exhibiting visible signs of corrosion.
Never repaint, plate, coat, or otherwise
alter automatic sprinklers after they
leave the factory. Never repaint fac-Never repaint fac-
tory-painted Cover Plates. If neces-
sary, replace them with factory-paint-
ed units. Non-factory applied paint can
adversely delay or prevent sprinkler
operation in the event of a fire.
Replace modified or over-heated
sprinklers.
Exercise care to avoid damage to
the sprinklers before, during, and
after installation. Replace sprinklers
damaged by dropping, striking, wrench
twisting, wrench slipping, or the like.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb. Refer to the Installation
Section.
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace it immediately.
Responsibility lies with the owner for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection
Association (for example, NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems should
be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national code.
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP’s sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of prod-
ucts or parts of products. TFSBP shall
not be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyer’s representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: TY3532, (temperature rating,
listed below) Series RFII Concealed
Pendent Sprinkler, P/N (specify).
155°F/68°C 200°F/93°C
TY3532 51-794-1-155 51-794-1-200
Separately Ordered Cover Plate/
Retainer Assembly
Specify: (temperature rating, listed
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify).
139°F/59°C(a) 165°F/74°C(b)
Brass.......... 56-792-1-135 56-792-1-165
Chrome ........ 56 -792-9-135 56-792-9-165
Signal White
(RAL 9003).... 56 -792-4-135 56-792- 4-165
Grey White
(RAL 9002).... 56 -792-0 -135 56 -792-0 -165
Pure White (c)
(RAL 9010).... 56 -792-3-135 56-792-3-165
Custom ........ 56 -792-X-135 56-792-X-165
(a) For use with 155°F/68°C sprinklers.
(b) For use with 200°F/93°C sprinklers.
(c) Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.