Series RFII — 5.6 K-factor
“Royal Flush II” Concealed Pendent Sprinklers
Quick Response, Extended Coverage
Page 1 of 4 JULY 2009 TFP260
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
General
Description
The Tyco®Series RFII, 5.6 K-factor,
Extended Coverage, Light Hazard
(ECLH) “Royal Flush” Concealed Pen-
dent Sprinklers are decorative, 3 mm
bulb-type sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. These sprinklers are opti-
mal for architecturally sensitive areas
such as hotel lobbies, office buildings,
churches, and restaurants.
The Series RFII sprinklers are intended
for use in automatic sprinkler systems
designed in accordance with standard
installation rules (for example, NFPA
13). The fast-response thermal sensi-
tivity rating of the Series RFII (TY3532)
provides for a quick response, extend-
ed coverage (QREC) rating up to a
20 ft. x 20 ft. coverage area.
Each sprinkler includes a Cover Plate/
Retainer Assembly and a Sprinkler/
Support Cup Assembly. The separable,
two-piece assembly design provides
the following benefits:
Allows installation of the sprinklers•
and pressure testing of the fire pro-
tection system prior to installation
of a suspended ceiling or applica-
tion of the finish coating to a fixed
ceiling.
Permits the removal of suspended•
ceiling panels for access to building
service equipment without having
to first shut down the fire protection
system and remove sprinklers.
Provides for 1/2 inch (12,7 mm) of•
vertical adjustment to allow a mea-
sure of flexibility in determining the
length of fixed piping to cut for the
sprinkler drops.
The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling in-
stallation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently push-
ing the ceiling product against the Pro-
tective Cap. When ceiling installation
is complete, the Protective Cap is re-
moved and the Cover Plate/Retainer
Assembly is installed.
NOTIce
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document and with the
applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authori-
ties having jurisdiction. Failure to do
so may impair the performance of
these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condi-
tion. The installing contractor or sprin-
kler manufacturer should be contact-
ed with any questions.
Sprinkler
Identification
Number (SIN)
TY3532
Technical
Data
Approvals
UL and C-UL Listed
NYC Approved under MEA 353-01-E
(The listings apply only to the service
conditions indicated in the Design Cri-
teria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K= 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
Temperature Rating
155°F/ 68°C Sprinkler with
139°F / 59°C Plate
200°F/ 93°C Sprinkler with
165°F/ 74°C Plate
Adjustment
1/2 inch (12,7 mm)
Finishes
See the Ordering Procedure section.
Physical Characteristics
Frame ................... Bronze
Support Cup... Chrome Plated Steel
Guide Pins .........Stainless Steel
Deflector................. Bronze
Compression Screw......... Brass
Blub ......................Glass
Cap.............Bronze or Copper
Sealing Assembly................
. . . . . . . . .Beryllium Nickel w/ Teflon†
Cover Plate ................ Brass
Retainer .................. Brass
Ejection Spring ......Stainless Steel
†DuPont Registered Trademark
TFP260
Page 2 of 4
Design
Criteria
The Tyco®Series RFII Concealed
Pendent Sprinklers (TY3532) are
UL and C-UL Listed for use in light
hazard occupancies, using the design
criteria in Table A, in addition to the
requirements specified in the current
NFPA 13 for extended coverage
pendent sprinklers.
The Series RFII Concealed Pendent
Sprinklers are only listed and approved
with the Series RFII Concealed Cover
Plates with a factory-applied finish.
NOTIce
Do not use the Series RFII in
applications where the air pressure
above the ceiling is greater than
that below. Down drafts through the
Sprinkler/Support Cup Assembly
can delay sprinkler operation in a fire
situation.
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away to
expose the Sprinkler/Support Cup
Assembly.
The Deflector—supported by the
Guide Pins—then drops down to its
operational position.
The glass Bulb contains a fluid that ex-
pands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.
Installation
The Tyco®Series RFII must be installed
in accordance with the following
instructions.
NOTIce
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 155°F/68°C and
3/32 inch (2,4 mm) for the 200°F/93°C
temperature ratings.
Obtain a 1/2 inch NPT sprinkler joint
by applying a minimum to maximum
torque of 7 to 14 ft.lbs. (9,5 to 19,0
Nm). Higher levels of torque can dis-
tort the sprinkler Inlet with consequent
leakage or impairment of the sprinkler.
FIGURe 1
seRIes RFII cONceAled sPRINKleR
RESPONSE
RATING SPACING MINIMUM
FLOW/PRESSURE
QUICK 16’ x 16’
(4,9 m x 4,9 m)
26.0 GPM / 21.6 PSI
(98,4 LPM / 1,49 BAR)
QUICK 18’ x 18’
(5,5 m x 5,5 m)
33.0 GPM / 34.7 PSI
(124,9 LPM / 2,39 BAR)
QUICK 20’ x 20’
(6,1 m x 6,1 m)
40.0 GPM / 51 PSI
(151,4 LPM / 3,52 BAR)
TABle A
seRIes RFII (TY3532)
155°F/68°c ANd 200°F/93°c cONceAled sPRINKleR
HYdRAUlIc desIGN cRITeRIA
Do not attempt to compensate for in-
sufficient adjustment in the Sprin-
kler by under- or over-tightening
the Sprinkler/Support Cup Assembly.
Re-adjust the position of the sprinkler
fitting to suit.
Step 1. Install the sprinkler only in the
pendent position with the centerline
of the sprinkler perpendicular to the
mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand-tighten
the sprinkler into the sprinkler fitting.
SPRINKLER/SUPPORT CUP
ASSEMBLY
COVER PLATE/RETAINER
ASSEMBLY
GUIDE
DEFLECTOR
RETAINER
WITH THREAD
DIMPLES
(DROPPED
POSITION)
PINS (2)
SPRING
EJECTION
TABS (3)
SOLDER
DEFLECTOR
ROLL FORMED
THREADS
CUP WITH
SUPPORT
FRAME
1/2" NPT
COVER
PLATE
THREAD INTO
UNTIL MOUNTING
SUPPORT CUP
SURFACE IS
FLUSH WITH
CEILING
SCREW
COMPRESSION
CAP
BULB
SEALING
ASSEMBLY
TFP260
Page 3 of 4
COVER PLATE
PROFILE DEPTH
DIMENSION B
1/2" (12,7 mm)
THREADED
ADJUSTMENT
D
SPRINKLER
FACE OF
FITTING
RETAINER
ASSEMBLY
MANUFACTURER
3/32" (2,4 mm)
PRESET GAP
FACE OF CEILING,
RETAINING RING
MOUNTING
SURFACE
SUPPORT CUP
SPRINKLER
ASSEMBLY
DIAMETER
CLEARANCE HOLE
DEFLECTOR
IN DROPPED
POSITION
(4,8 to 17,5 mm)
3/16" to 11/16"
REFERENCE
COVER PLATE
COVER PLATE
DIAMETER
DIMENSION A
DIMENSION C
A: 3-1/4 inches (82,6 mm) C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm)
B: 3/16 inches (4,8 mm) D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm)
FRAME
ARM
SUPPORT
CUP
7/8" (23 mm)
SQUARE
1/2" SOCKET
ACCEPTS
DRIVE
ARROWS WITH
ALIGN
FRAME ARMS
CLEARANCE
HOLE
FIGURe 2
seRIes RFII cONceAled sPRINKleR INsTAllATION dIMeNsIONs
Step 4. Wrench-tighten the sprinkler
using only the RFII Sprinkler Wrench
shown in Figure 3. Apply the RFII
Sprinkler Wrench to the Sprinkler as
shown in the figure.
Step 5. Replace the Protective Cap
by pushing it upwards until it bottoms
out against the Support Cup. (Refer to
Figure 4.)
The Protective Cap helps prevent dam-
age to the Deflector and Frame Arms
when installing or finishing the ceiling.
You can also use it to locate the center
of the clearance hole by gently push-
ing the ceiling material up against the
center point of the Protective Cap.
NOTIce
As long as the Protective Cap remains
in place, the system is considered
“Out of Service”.
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate/Re-
tainer Assembly, remove and discard
the Protective Cap.
Verify that the Deflector moves up and
down freely. If the Sprinkler is dam-
aged and the Deflector does not move
up and down freely, replace the entire
Sprinkler. Do not attempt to modify or
repair a damaged sprinkler.
Step 7. Screw on the Cover Plate/Re-
tainer Assembly until its flange makes
contact with the ceiling. Do not con-
tinue to screw on the Cover Plate/Re-
tainer Assembly so that it lifts a ceiling
panel out of its normal position. If you
cannot engage the Cover Plate/Re-
tainer Assembly with the Support Cup
or you cannot engage the Cover Plate/
Retainer Assembly sufficiently to con-
tact the ceiling, you must reposition
the Sprinkler Fitting.
FIGURe 3
RFII sPRINKleR wReNcH
FIGURe 4
dIsPOsABle PROTecTIve cAP
© 2008-2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS
, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
TFP260
Page 4 of 4
Care and
Maintenance
The Tyco®Series RFII must be
maintained and serviced in accordance
with the following instructions.
NOTIce
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tem from the proper authorities and
notify all personnel who may be affect-
ed by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap be-
tween the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper oper-
ation of the sprinkler. If the ceiling re-
quires repainting after sprinkler instal-
lation, ensure that the new paint does
not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Replace sprinklers that are leaking or
exhibiting visible signs of corrosion.
Never repaint, plate, coat, or otherwise
alter automatic sprinklers after they
leave the factory. Never repaint fac-Never repaint fac-
tory-painted Cover Plates. If neces-
sary, replace them with factory-paint-
ed units. Non-factory applied paint can
adversely delay or prevent sprinkler
operation in the event of a fire.
Replace modified or over-heated
sprinklers.
Exercise care to avoid damage to
the sprinklers before, during, and
after installation. Replace sprinklers
damaged by dropping, striking, wrench
twisting, wrench slipping, or the like.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb. Refer to the Installation
Section.
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace it immediately.
Responsibility lies with the owner for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection
Association (for example, NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems should
be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national code.
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP’s sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of prod-
ucts or parts of products. TFSBP shall
not be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyer’s representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: TY3532, (temperature rating,
listed below) Series RFII Concealed
Pendent Sprinkler, P/N (specify).
155°F/68°C 200°F/93°C
TY3532 51-794-1-155 51-794-1-200
Separately Ordered Cover Plate/
Retainer Assembly
Specify: (temperature rating, listed
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify).
139°F/59°C(a) 165°F/74°C(b)
Brass.......... 56-792-1-135 56-792-1-165
Chrome ........ 56 -792-9-135 56-792-9-165
Signal White
(RAL 9003).... 56 -792-4-135 56-792- 4-165
Grey White
(RAL 9002).... 56 -792-0 -135 56 -792-0 -165
Pure White (c)
(RAL 9010).... 56 -792-3-135 56-792-3-165
Custom ........ 56 -792-X-135 56-792-X-165
(a) For use with 155°F/68°C sprinklers.
(b) For use with 200°F/93°C sprinklers.
(c) Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.

This manual suits for next models

2

Other Tyco Irrigation System manuals

Tyco EC-11 Series User manual

Tyco

Tyco EC-11 Series User manual

Tyco TY-QRF-EU User manual

Tyco

Tyco TY-QRF-EU User manual

Tyco RAPID RESPONSE Series User manual

Tyco

Tyco RAPID RESPONSE Series User manual

Tyco Issue D Quartzoid TY3191 User manual

Tyco

Tyco Issue D Quartzoid TY3191 User manual

Tyco CC3 User manual

Tyco

Tyco CC3 User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco rapid response LFII Series User manual

Tyco

Tyco rapid response LFII Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco rapid response LFII Series Operating and maintenance instructions

Tyco

Tyco rapid response LFII Series Operating and maintenance instructions

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco ESFR-25 Operating and maintenance instructions

Tyco

Tyco ESFR-25 Operating and maintenance instructions

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco DSB-1 User manual

Tyco

Tyco DSB-1 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco TY-QRF-5.6 User manual

Tyco

Tyco TY-QRF-5.6 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco G5 Sprinkler Guard User manual

Tyco

Tyco G5 Sprinkler Guard User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Popular Irrigation System manuals by other brands

Tyco Fire Product CENTRAL TY-B Series instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B Series instruction manual

Toro 340 Series brochure

Toro

Toro 340 Series brochure

Reliable RFC Series Bulletin

Reliable

Reliable RFC Series Bulletin

Marani GTS80B Instruction manual for use and maintenance

Marani

Marani GTS80B Instruction manual for use and maintenance

Toro GreenKeeper 212 user guide

Toro

Toro GreenKeeper 212 user guide

Reliable G5 Series manual

Reliable

Reliable G5 Series manual

Reliable XL Series manual

Reliable

Reliable XL Series manual

Cellfast EXPERT TT IDEAL 52-067 user manual

Cellfast

Cellfast EXPERT TT IDEAL 52-067 user manual

Tyco Fire Product CENTRAL Omega HEC-12EC PRO instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega HEC-12EC PRO instruction manual

Reliable MBEC-14 Bulletin

Reliable

Reliable MBEC-14 Bulletin

Cepex CSP-050 instructions

Cepex

Cepex CSP-050 instructions

Reliable F1FR56 manual

Reliable

Reliable F1FR56 manual

Viking MICROFAST VK328 Technical data

Viking

Viking MICROFAST VK328 Technical data

Reliable DH56 HSW-PL Bulletin

Reliable

Reliable DH56 HSW-PL Bulletin

Viking VK595 Technical data

Viking

Viking VK595 Technical data

Galcon 9001D Operation and installation instructions

Galcon

Galcon 9001D Operation and installation instructions

Rain Bird SST-1200s Operation manual

Rain Bird

Rain Bird SST-1200s Operation manual

Viking VK449 Technical data sheet

Viking

Viking VK449 Technical data sheet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.