I-VICFLEX.AQC-UINSTALLATION INSTRUCTIONS
Victaulic®VicFlex™Style AQC-U Sprinkler Fitting
for Cleanroom Applications
I-VICFLEX.AQC-U_1
REV_B
Maximum Working Pressure:
200 psi/14 Bar/1379 kPa (FM Approval)
Maximum Ambient Temperature Rating:
225° F/107° C
Connection to Branch Line:
1 inch/25 mm NPT/BSPT
Minimum Bend Radius:
6 inch/152 mm (FM Approval)
Maximum K-Factor of Sprinkler to be Connected to the Style AQC-U:
5.6 US/80 metric
Maximum Number of 90° Bends:
Refer to the “Style AQC-U Friction Loss Data” section below
Style AQC-U Friction Loss Data
Length
inches/mm
NPT/BSPT
Sprinkler End
inches
Maximum
Number
of 90° Bends
Equivalent Length
of 1-inch /33.7-mm
Schedule 40 Pipe
feet/meters
36 ½ 2 24.0
915 7. 3
48 ½ 3 31.5
1220 9.6
72 ½ 4 46.6
1830 14.2
* M+W Zander Facility Engineering GmbH is a company of the
M+W Group
‡ SBB Gorilla Grid is a product of SBB, Inc.
Flexible Hose Bend Characteristics:
NOTE: For out-of-plane (three-dimensional) bends, care shall be
taken to avoid imparting torque on the flexible hose.
90°
OR
OR
Minimum
Bend Radius
Minimum
Bend Radius Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
2X
Minimum
Bend
Radius
2X
Minimum
Bend
Radius
WARNING
• Read and understand all instructions before attempting to install any Victaulic®VicFlex™products.
• Wear safety glasses, hardhat, and foot protection.
• These installation instructions are intended for an experienced, trained installer.
• The user shall understand the purpose of these products, common industry standards for safety,
and the potential consequences of improper product installation.
• It is the system designer’s responsibility to verify suitability of stainless steel flexible hose for use
with the intended fluid media within the piping system and external environment.
• The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level,
and flow rate on the stainless steel flexible hose shall be evaluated by the material specifier to
confirm system life will be acceptable for the intended service.
Failure to follow these instructions could cause improper sprinkler operation and product failure,
resulting in death or serious personal injury and property damage.
Victaulic®VicFlex™Style AQC-U Sprinkler Fittings connect the branch line directly to the sprinkler and are FM Approved for use with the
M+W Zander Facility Engineering GmbH* and SBB Gorilla Grid‡cleanroom ceiling systems. Other cleanroom ceilings can be evaluated on a
case-by-case basis by contacting Victaulic.
I-VICFLEX.AQC-U_2
REV_B
I-VICFLEX.AQC-U / Victaulic®VicFlex™Style AQC-U Sprinkler Fitting for Cleanroom Applications / Installation Instructions
IMPORTANT INSTALLATION INFORMATION
• The installer shall wear proper cleanroom attire during installation
of the Victaulic®VicFlex™Style AQC-U. Contact the building owner
or their representative to confirm requirements for the specific
cleanroom application.
• Victaulic®VicFlex™products shall be installed according to
current, applicable National Fire Protection Association (NFPA
13, 13D, 13R, etc.) standards or equivalent standards. Victaulic®
VicFlex™products are intended to be installed in wet, dry, or
preaction actuated systems. Deviations from these standards or
alterations to Victaulic®VicFlex™products or sprinklers will void
any Victaulic warranty and will impact system integrity. Installations
shall meet the provisions of the local authority having jurisdiction
and local codes, as applicable.
• Victaulic® VicFlex™Style AQC-U Sprinkler Fittings shall not be
intermixed with other manufacturer’s flexible sprinkler products.
• Refer to the specific Victaulic product submittal for applications
and listing information. In addition, when installing Victaulic
FireLock®Automatic Sprinklers with Victaulic®VicFlex™
Sprinkler Fittings, refer to the I-40 Installation and Maintenance
Instructions for details on sprinkler installation requirements.
Submittals and installation instructions can be downloaded at
victaulic.com.
• Size the piping system to provide at least the minimum required
flow rate for the sprinkler system.
• Per NFPA requirements, flush the system to remove foreign
material. Continue to flush the system until water runs clear.
• DO NOT install sprinkler system piping through heating ducts.
• DO NOT connect sprinkler system piping to domestic hot water
systems.
• DO NOT install sprinklers and sprinkler fittings where they will
be exposed to temperatures that exceed the maximum ambient
temperature rating for the sprinkler and sprinkler fittings.
• The flexible hose shall not be bent or fluctuated up-and-down or
side-to-side when it is pressurized.
• Flexible hose and fittings have limited flexibility* and are
intended only to be installed with bends not less than their
respective minimum bend radii. DO NOT install flexible hose in
a straight configuration.
• Protect wet piping systems from freezing temperatures.
• If construction is altered, refer to applicable standards to determine
if additional sprinklers are required.
• The owner is responsible for maintaining the fire protection system
in proper operating condition.
• For minimum maintenance and inspection requirements, refer to
NFPA 25 and any other applicable NFPA standards that describe
the care and maintenance of sprinkler systems. In addition, the
authority having jurisdiction may have additional maintenance,
testing, and inspection requirements that shall be followed.
WARNING
• Relocation of Victaulic®VicFlex™ products SHALL be performed
by qualified personnel familiar with the system’s original design
criteria, sprinkler listings/approvals, and state and local codes
(including NFPA 13 standards).
Failure to relocate this Victaulic® VicFlex™product properly could
affect its performance during a fire, resulting in serious personal
injury and property damage.
* Reference UL 2443: Section 25.1
CONNECTION TO THE SPRINKLER PIPING
USING AN ADAPTER NIPPLE AND A
STYLE AQC-U SPRINKLER FITTING
WARNING
• The flexible hose shall not be bent or fluctuated up-and-down or
side-to-side when it is pressurized for test.
Failure to follow this instruction could cause improper sprinkler
operation, serious personal injury, and/or property damage.
1. Apply pipe joint compound or PTFE thread sealant tape to the
tapered threads of the adapter nipple, in accordance with the pipe
joint compound or tape manufacturer’s instructions. Using a pipe
wrench, tighten the adapter nipple into the sprinkler piping.
2. Confirm that the seal inside the nut of the Style AQC-U is in place
and is free from damage prior to installation. Connect the nut to
the adapter nipple, as shown above.
• DO NOT use pipe joint compound or PTFE thread sealant tape on
the threads of the adapter nipple. The seal inside the nut of the
Style AQC-U provides the leak-proof connection.
• Tighten the connection nut to a torque of 40ft-lbs/54 N•m
(approximately ½ to ¾ of a turn past hand-tight). NOTE: To prevent
damage to the seal, tighten the assembly by applying torque only
to the connection nut and DO NOT exceed the specified torque.
I-VICFLEX.AQC-U_3
REV_B
I-VICFLEX.AQC-U / Victaulic®VicFlex™Style AQC-U Sprinkler Fitting for Cleanroom Applications / Installation Instructions
ATTACHING THE STYLE AQC-U TO THE CLEANROOM CEILING GRID
* Components provided by ceiling grid manufacturer
or others.
Exploded View of
Installation Components
Ceiling Grid*
Cross Block*
Sprinkler with Bulb Protector*
T-Bolt*
Gasket
Nut*
Swivel Bracket
Nut*
T-Bolt*
Lock Washer*
Flat Washer*
Lock Washer*
Flat Washer*
Gasket
Completed
Installation
Flexible Hose
NOTICE
• If the sprinkler deflector or bulb protector appears too large to pass through the cross block location, it may be necessary to install the
sprinkler after the Style AQC-U is tightened to the ceiling grid.
1. Slide a T-Bolt (supplied with the ceiling grid) into the slot of the two opposing ceiling grid sections, as shown in the drawing above.
2. Insert the Victaulic®VicFlex™Style AQC-U assembly into the cross block location.
3. Align the holes in the swivel bracket of the Victaulic®VicFlex™Style AQC-U with the T-Bolts. Secure the swivel bracket to the ceiling grid by
installing a flat washer, lock washer, and nut (supplied with the ceiling grid) onto the end of each T-Bolt. To ensure a rigid connection, tighten
each nut until the lock washer is flattened completely.
4. Position the two gaskets, indicated in the drawing above, to seal the ceiling penetration.
5. Install any ceiling grid face plates, sprinkler escutcheons, elastic decorative rings or covers, etc. Use caution to prevent damage to the sprinkler
during installation of any accessories.
6. After installation is complete, test the system for leaks in accordance with NFPA guidelines.
I-VICFLEX.AQC-UINSTALLATION INSTRUCTIONS
Victaulic®VicFlex™Style AQC-U Sprinkler Fitting
for Cleanroom Applications
For complete contact information, visit victaulic.com
I-VICFLEX.AQC-U 9353 REV B UPDATED 06/2018 Z000AQCU00
VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES
IN THE UNITED STATES AND/OR OTHER COUNTRIES. © 2018 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

This manual suits for next models

1

Other Victaulic Irrigation System manuals

Victaulic VicFlex VS1 User manual

Victaulic

Victaulic VicFlex VS1 User manual

Victaulic V9 FireLock IGS User manual

Victaulic

Victaulic V9 FireLock IGS User manual

Victaulic VicFlex V32 User manual

Victaulic

Victaulic VicFlex V32 User manual

Victaulic FireLock I-800 User manual

Victaulic

Victaulic FireLock I-800 User manual

Victaulic VS1 Series User manual

Victaulic

Victaulic VS1 Series User manual

Victaulic FireLock Series User manual

Victaulic

Victaulic FireLock Series User manual

Victaulic VicFlex AH1 User manual

Victaulic

Victaulic VicFlex AH1 User manual

Victaulic FireLock Series User manual

Victaulic

Victaulic FireLock Series User manual

Victaulic FireLock I-800 User manual

Victaulic

Victaulic FireLock I-800 User manual

Victaulic VicFlex Style AB6 User manual

Victaulic

Victaulic VicFlex Style AB6 User manual

Popular Irrigation System manuals by other brands

Hunter Institutional I-20 manual

Hunter

Hunter Institutional I-20 manual

IrriGreen 2 Quick install guide

IrriGreen

IrriGreen 2 Quick install guide

Toro T5 Series quick start guide

Toro

Toro T5 Series quick start guide

Tyco LFII Series Technical data sheet

Tyco

Tyco LFII Series Technical data sheet

Tyco Fire Product Star Mizar S210 instruction manual

Tyco Fire Product

Tyco Fire Product Star Mizar S210 instruction manual

Reliable XL Bulletin

Reliable

Reliable XL Bulletin

Reliable F156-300 Series Bulletin

Reliable

Reliable F156-300 Series Bulletin

Tyco TY-FRB Series Installation and operation manual

Tyco

Tyco TY-FRB Series Installation and operation manual

Tyco Fire Product EC-17 instruction manual

Tyco Fire Product

Tyco Fire Product EC-17 instruction manual

Tyco Fire Product CENTRAL ESFR-17 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 instruction manual

NaanDanJain NDJ DripKit installation guide

NaanDanJain

NaanDanJain NDJ DripKit installation guide

Tyco Fire Product SIN S3230 manual

Tyco Fire Product

Tyco Fire Product SIN S3230 manual

Brandson 304260 user manual

Brandson

Brandson 304260 user manual

Viking MICROMATIC VK134 manual

Viking

Viking MICROMATIC VK134 manual

Reliable DDX Type D Instructions for installation, operation care and maintenance

Reliable

Reliable DDX Type D Instructions for installation, operation care and maintenance

Cepex CMC-08-24 Installation and operating manual

Cepex

Cepex CMC-08-24 Installation and operating manual

Senju Sprinkler FR-RES quick start guide

Senju Sprinkler

Senju Sprinkler FR-RES quick start guide

Orbit WaterMaster Voyager Installation instruction

Orbit

Orbit WaterMaster Voyager Installation instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.