TFP682
Page 9 of 10
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies
Specify: (specify SIN), (specify Stan-
dard Response or Quick Response),
(specify K-factor), (specify) tempera-
ture rating, (specify Upright, Pendent
or HSW), P/N (specify from Table D)
Recessed Escutcheon
Specify: Style (specify 10 or 40)
Recessed Escutcheon, Grey Aluminum
(RAL9007) nish, P/N (specify*)
*Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler
Wrench, P/N 56-850-4-001
Care and
Maintenance
The TYCO Series TY-B and TY-FRB
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected re protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notied.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a re or inadvertent oper-
ation may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a re situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For more informa-
tion, see the Installation section.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant sprinklers, after
the installation has been completed,
to verify the integrity of the corrosion
resistant material of construction.
Thereafter, annual inspections accord-
ing to NFPA 25 should sufce; however,
instead of inspecting from the oor
level, a random sampling of close-up
visual inspections should be made, so
as to better determine the exact sprin-
kler condition and the long term integ-
rity of the corrosion resistant material
of construction, as it may be affected
by the corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualied Inspection Service in accor-
dance with local requirements and/or
national codes.
P/N 57 — XXX — X — XXX
Standard Response (SR) SIN
570 TY-B 5.6K Upright SR TY3151
590 TY-B 8.0K Upright SR TY4151
571 TY-B 5.6K Pendent SR TY3251
591 TY-B 8.0K Pendent SR T Y4251
578 TY-B 5.6K HSW SR TY3351
Quick Response (QR) SIN
370 TY-FRB 5.6K Upright QR TY3131
390 TY-FRB 8.0K Upright QR T Y4131
371 TY-FRB 5.6K Pendent QR TY3231
391 TY-FRB 8.0K Pendent QR TY4231
378 TY-FRB 5.6K HSW QR TY3331
Sprinkler Finish
2Grey Aluminium (RAL9007)
Temperature Rating
135 135°F (57°C)
155 155°F (68°C)
175 175°F (79°C)
200 200°F (93°C)
286 286°F (141°C)
360 360°F (182°C)*
* TY-B - Only
TABLE D
POLY-STAINLESS SERIES TY-B AND TY-FRB
UPRIGHT, PENDENT AND HORIZONTAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION