VIDICON STAR User manual

FEATURES MOUNTING
INSTALLATION INSTRUCTIONS
STAR
COMPACT
GLASS BREAK & SHOCK
DETECTOR
The STAR is the ultimate answer for all those
tired of false alarms. It listens for sounds of
breaking glass, which produce two sequential
signals of different frequencies. The unique
phased frequency detection circuitry of this
detector allows detection of both shock signal
and the strong signal of glass breakage creating
a “false alarm free” glass break detector.
The detector does not need to be attached to
the window, providing volume protection, and
allowing you to protect several windows with one
detector.
FEATURES
•Shock and/or breakage selectable
•Analyzes two frequencies
•Unique signal analysis ignores
environmental disturbances
•Memory LED
•ASIC based electronics
•Sensitivity adjustment
•New ultra compact design
•Flush mount installation (option)
•Outstanding detection range and reliability
FIG. 1
The detector offers flexible installation. It can be
either ceiling mounted or wall mounted as
shown in the figure above.
SELECT LOCATION MOUNTING THE DETECTOR THE BACK COVER
See FIG. 1
•If heavy blinds or curtains cover the glass,
you must locate the detector behind the
blinds on the window frame or above it,
otherwise the blinds might block the sound.
Make sure to test the unit thoroughly for
proper detection.
•Install the detector in a direct line of sight
with the protected glass.
•Do not mount the unit in front of air ducts, or
close to bells (measuring 0.5m (or larger) in
diameter).
•For a few protected glasses in one room,
locate the detector in optimal distance from
them to achieve the best detection.
Note: for symmetrical cover of the detection area
it is recommended to place the detector on
the ceiling.
See FIG. 2
1. Use a small screwdriver to push the prong on
top of the case and open the case.
2.
Snap out the detector PCB.
3. Insert the wires through the wiring hole (B).
4. Use the mounting holes (A) to mount the
detector.
5. Connect the wires to the terminal.(See
Terminal Connections)
6. Reinstall the detector PCB.
7. Close the case.
JUMPERS ( FIG. 4 )
•JP1 - Shock / Glass selector for detection
calibration.
•JP2 - Memory LED control.
•JP3 - Reduces the sensitivity of sound
detection by 50%.
FIG. 2
A
A
B
TERMINAL BLOCK CONNECTIONS THE CALIBRATION TOOL TESTING THE DETECTOR
FIG. 3
Terminal 1 - Marked - (GND)
Connect to ground of the control panel.
Terminal 2 - Marked + ( +12V )
Connect to the positive Voltage output of 9-16
Vdc
source (usually from the alarm control unit).
Terminals 3 & 4 - Marked TAMPER
If a Tamper function is required connect these terminals
to a 24hour normally closed protective zone in the
control unit. If the front cover of the detector is opened,
an immediate alarm signal will be sent to the control
unit.
Terminals 5 & 6 - Marked RELAY
These are the output relay contacts of the detector.
Connect to the control at zone input.
The Simulator/Tester & Calibration tool is
especially designed to check phased frequency
glass break detectors.
Since the detector will react to the high
frequency breakage sound only when it comes
sequentially after a low frequency SHOCK
sound, this device is necessary to check for
proper operation of the STAR without actually
breaking the glass.
Manual mode:
In this mode, the Simulator will emit the high
frequency sound of breaking glass for "Glass"
adjustment.
Automatic mode:
In order to simulate breaking glass, place the
Simulator on the surface of the protected glass,
and gently hit it with your hand. The Simulator
will then emit the sound of breaking glass. Be
careful not to break the glass while testing the
detector.
First use the Simulator in manual mode to
simulate the noise of glass breaking. Check that
the yellow LED is ON. If it does not light, the
sensitivity calibration is necessary (See Sound
Calibration).
Now use your hand or a padded object to
carefully strike the glass. If the green LED does
not light, adjust as necessary (See Shock
Calibration).
Now use the Simulator in automatic mode and
check that the red LED lights. If the red LED is
ON, your detector is working properly. Otherwise
try adjusting the sound and shock setting until
the red LED lights.

GLASS BREAK ADJUSTMENT SHOCK ADJUSTMENT THE MEMORY FUNCTION
To adjust the glass break setting
(increase/decrease sensitivity) place the jumper
JP1 according the GLASS marking (connecting
the middle pin with the upper pin) - (See Fig. 4)
Green LED is constantly ON.
Now you can adjust the sensitivity by rotating
the upper potentiometer (marked as GLASS
CAL. - see Fig. 4).
Operate the Sound Break Simulator and rotate
the potentiometer clock-wise to increase
sensitivity, and counter-clock-wise to decrease
sensitivity until the Yellow and Red LED’s are
illuminating for each glass break sound.
Remember that rotating the potentiometer will
have no effect upon the settings if the middle pin
of JP1 is not connected to the upper pin.
Note
When the jumper is set for GLASS adjustment,
only the high frequency sound of breaking glass
is detected.
To adjust the shock setting (increase/decrease
sensitivity) place the jumper JP1 according the
SHOCK marking (connecting the middle pin with
the lower pin) - (See Fig. 4) Yellow LED is
constantly ON.
Now you can adjust the sensitivity by rotating
the lower potentiometer (marked as SHOCK
CAL. - see Fig. 4).
Hit gently on the protected glass and rotate the
potentiometer clock-wise to increase sensitivity,
and counter-clock-wise to decrease sensitivity
until the Green and Red LED’s are illuminating
for each hit.
Remember that rotating the potentiometer will
have no effect upon the settings if the middle pin
of JP1 is not connected to the lower pin.
Note
When the jumper is set for SHOCK adjustment,
only the low frequency of the shock signal prior
to glass breakage is detected.
The alarm memory function allows the
identification of an alerting detector out of
multiple detectors connected to one (or the
same) zone of the control panel.
To enable this function, Set ON jumper JP2
(MEM) (connected on both pins - See Fig. 4)
In case of an alarm, the Red LED will stay ON
until memory function is reset.
To reset the memory function, switch OFF
(disconnect) the voltage wire (+12V) from the
TERMINAL BLOCK for minimum 15 seconds
then switch on (reconnect) voltage wire (+12V).
(The control panel key ON/OFF can be used for
this application if it control the voltage (+12V).
SENSITIVITY SETTING
For some installations you may find that VIG is
too sensitive. Use JUMPER JP3 to decrease
sensitivity to 50%.
JP3 OPEN - 100% sensitivity
JP3 CONNECTED - 50% sensitivity
FINAL TESTING PCB LAYOUT WIRE SIZE REQUIREMENTS
•Make sure to disconnect the jumper at JP1.
When the jumper is disconnected, the
detector will detect both shock and sound
frequencies.
To ensure maximum protection against false
alarms, activate any device in the area, which
might automatically cycle pumps, generators,
heating/air conditioning units, etc. If the cycling
devices trigger an alarm, mount the unit in a
different location.
FIG. 4
Use #22 AWG (0.5mm) or wires with a larger
diameter. Use the following table to determine
required wire gauge (diameter) and length of
wire between the detector and the control panel.
Wire Length m 200 300 400 800
Wire Diameter mm .5 .75 1.0 1.5
Wire Length ft 800 1200 2000 3400
Wire Gauge # 22 20 18 16
TECHNICAL SPECIFICATIONS WARRANTY CONTACT US:
Power Input
9 - 16 Vdc
Current Consumption
Standby: 22mA at 12Vdc
Active: 25mA at 12Vdc
Detection Range
10m (33ft), Adjustable
Dimensions
78mm x 51mm x 21mm
(3.07 `` x 2.01`` x 0.83)
Mounting
Ceiling or Wall
Alarm Output Relay
N.C 50mA/24Vdc with
27 Ohm in line resistor
Tamper Switch
N.C 50mA 24Vdc with
10 Ohm in line resistor
Operating Temperature -20°C to 50°C
Range (-4°F to 122°F)
Operating Humidity 95% max relative humidity
Range non condensing
Storage Temperature -30°C to 70°C
Range (-22°F to 158°F)
Microphone Electro Condenser
RFI Protection 30V/m 10 -1000MHz
EMI Protection 50,000V electrical
Interference from lightning
VIDICON reserves the rights to change specifications
without prior notice
VIDICON LIMITED WARRANTY
(VIDICON) warrants this product to be free from defects in materials and
workmanship under normal use and servicefor a period of ONE YEAR from the
last day of the week and year whose numbers are printed on the printed circuit
board inside this product.
VIDICON’s obligation is limitedto repairing or replacing this product, atits option,
free of charge for materials or labor,if it is proved to be defective in materials or
workmanship under normal use and service. VIDICON shall have no obligation
under this Limited Warranty or otherwise if the product is altered or improperly
repaired or serviced by anyone other then VIDICON.
There are no warranties, expressed or implied,of merchantability or fitness for a
particular purpose orotherwise, which extend beyond the descriptionon the face
hereof. In no case shall VIDICON be liable to anyone for any consequential or
incidental damages for breach of this or any other warranty, expressed or
implied, or upon any other basis of liability whatsoever, even if the loss or
damage is caused by VIDICON’s own negligence or fault.
VIDICON does not represent that this product can not be compromised or
circumvented; that this product will prevent any person injury or property loss or
damage by burglary, robbery, fire or otherwise; or that this product will in all
cases provide adequate warning or protection. Purchaser understands that a
properly installed and maintained product can only reduce the risk of burglary,
robbery or other events occurring without providing an alarm, but it is not
insurance or a guarantee that such will notoccur or that there will be no personal
injury or property loss or damage as a result.Consequently,VIDICONshallhave
no liability for any personal injury; property damage or any other loss based on
claim that this product failed to give any warning. However, if VIDICON is held
liable, whether directly or indirectly, for any loss or damage arising under this
limited warranty or otherwise, regardless of cause or origin, VIDICON’s
maximum liability shall not in any case exceed the purchase price of this product,
which shall be the complete and exclusive remedy against VIDICON.
VIDICON LTD.
Israel: 14 Shenkar St
Hertzelya Pituah 46733
PO BOX 12575 Israel
Tel: +972 9 9511211
Fax: +972 9 9511222
Poland: 15 Powazkowska St
01-797 Warsaw Poland
Tel: +48 22 562 3000
Fax: +48 22 562 3030
P/N 7121352 Ver. A A.Y.
Other VIDICON Security Sensor manuals
Popular Security Sensor manuals by other brands

Blaupunkt
Blaupunkt DC-S3 manual

Sperian
Sperian ToxiPro Reference manual

Raptor
Raptor 47HLB 80 installation guide

ADEMCO
ADEMCO 4192SDM Installation and maintenance instructions

Hochiki
Hochiki RHD-E-AS instruction manual

PBA Safety
PBA Safety Speakman SE 607 Installation maintenance and operating instructions