manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Visonic
  6. •
  7. Security Sensor
  8. •
  9. Visonic K-980D User manual

Visonic K-980D User manual

DE1842 1
K
KK
K-980
-980-980
-980D
DD
D
Dual-Technology Pet-Immune Intrusion Detector Installation Instructions
1
11
1. FEATURES
. FEATURES. FEATURES
. FEATURES
• Uses TSI™ - Target Specific Imaging technology for distinction
between humans and pets (patent pending)
• Immune to pets weighing up to 36 kg (80 lb)
• True Motion Recognition™ (TMR) algorithm distinguishes
between the true motion of a human body and other disturban-
ces which invariably cause false alarms (patented)
• DRO-stabilized MW microstrip technology (patented)
• MW Motion Simulator simulates the effect created by a human
body moving in the MW field (patent pending)
• Range control for adjusting the MW coverage
• Integral swivel bracket for wall or ceiling installation
• Sealed chamber protects the pyroelectric element from insects.
• Programmable motion event counter (1 or 2 events)
• Simple-to-use three position vertical adjustment
• TEST input to remotely enable/disable the walk test LED (per
new European standards)
• Open collector TROUBLE output
• White light protection
Figure 1. The K-980D Detector
2. SPECIFICATIONS
Input Voltage: 9 to 16 VDC
Current Drain: About 28 mA @ 12 VDC
OPTICAL
Max. Coverage Range: 12 x 12 m (40 x 40 ft) / 90°
Pet Immunity: Immune to pets weighing up to 36 kg (80 lb)
Vertical Adjustment: 3-position adjustment scale: 1.8 m (6 ft),
2.1 m (7 ft) and 2.4 m (8 ft).
PIR SECTION
Detector: Low noise dual-element pyroelectric sensor
Tripping Indication: LED flashes green for up to 5 seconds
True Motion Event Verification Counter: Selectable, 1 or 2
motion events
MW SECTION
Oscillator: Microstrip DRO-stabilized Doppler module
Frequency: 10.525 or 2.45 GHz
Detection Range: Adjustable from 25% to 100% (3 m to 12 m)
Trip Indication: LED glows green for up to 5 seconds
ALARM, TAMPER & TROUBLE DATA
Alarm Indication: LED glows red for 1.3 to 5 seconds if both
detectors trip
Relay Contacts: N.C., rated at 0.1 A resistive / 30 VDC; 18 Ω
resistor in series with contacts
Alarm Duration: 1.3 to 5 seconds (LED glows red and output
relay contacts open)
Tamper Switch: N.C., rated at 50 mA resistive / 30 VDC
Trouble Output: Open collector, 100 mA max., with 18Ωresistor
in series and 47 kΩpull-up (see Figure 11)
MOUNTING
Height: Up to 2.4 m (8 ft)
Installation Options: Surface or corner (without bracket);
surface or ceiling (with bracket).
Bracket Adjustment: 20°downward (only in non-pet immune
applications), 20°left and right.
ENVIRONMENTAL
RFI Protection: >30 V/m up to 1000 MHz.
Operating Temperatures: -10°C to 50°C (14°F to 122°F).
Storage Temperatures: -20°C to 60°C (-4°F to 140°F).
Compliance with Standards: Designed to meet FCC part 15;
complies with the European Council Directive EMC 89/336/EEC
& 92/31/EEC, and bears the CE mark and certification.
PHYSICAL
Dimensions (H x W x D): 117 x 65 x 47 mm
(4-5/8 x 2-9/16 x 1-7/8 in.).
Weight: 109 g (3.85 oz) without bracket, 124 g (4.4 oz) with
bracket.
PATENTS
U.S. Patents 5,237,330 and 5,693,943 (other patents pending)
3
33
3. INSTALLATION
. INSTALLATION. INSTALLATION
. INSTALLATION
3.1 Installation Hints
Important! The detector is immune to 36 kg
(80 lb) animals moving on the floor or
climbing on furniture as long as the activity
takes place below 1 m (3 ft). Above the 1 m
(3 ft) height limit, the detector is immune to
18 kg (40 lb) pets, but the pet immunity will
decrease as the pet gets closer to the detector. It is therefore
recommended to select a mounting location that minimizes
potential close proximity of animals.
To minimize false alarms:
Do not aim at heat sources Mount on solid, stable surfaces
2DE1842
Do not expose to air draughts Do not install outdoors
Prevent direct sunlight from
reaching the detector
Keep wiring away from
electrical power cables
Do not install behind partitions
In addition, a few important rules must be observed while
selecting a mounting location:
A. Microwave radiation passes through glass and non-metallic
walls. Be sure to adjust the MW range so that it does not
exceed the room limits, or else motion in the next room or
moving traffic along the outer side of the wall will cause the
MW detector to trip.
B. Large reflecting objects (especially metals) within the
coverage area can distort the microwave detector's coverage
pattern.
C. If two K-980D units are installed in the same room or on
opposite sides of a shared wall, they should not face each
other and must be mounted at least 2 meters apart.
D. Do not install the K-980D in places where one of the two
detector circuits alarms constantly or intermittently, due to
environmental interference.
3.2 Mounting without Swivel Bracket
A. Remove the front cover as shown in Figure 3.
Figure 3. Cover Removal
B. Loosen the vertical
adjustment screw,
slide the PCB
down and remove
it via the “keyhole”
(see Figure 4).
C. Pull the PCB
straight out and
put it aside until
required again. Figure 4. PCB Removal
D. Refer to Figure 5 and punch out the mounting knockouts at
the rear wall of the base (for surface mounting) or at the
angled sides of the base (for corner mounting).
Figure 5. Inside View
E. Punch out any one of the wiring knockouts shown in Figure 5.
F. Hold the base against the wall at the selected installation
location, mark the points for drilling and drill the holes (insert
the plastic dowels supplied if necessary).
G. Pass the wires through the wiring inlets into the base and
attach the base to the wall using the screws supplied.
H. Return the PCB to its place within the base.
I. Proceed to wire the terminal block as instructed in Para. 3.5.
3.3 Mounting with Swivel Bracket
A. Remove the front cover as shown in Figure 3.
B. Remove the PCB (see Figure 4) and put it temporarily aside.
C. Punch out the large knockout in the round bulge at the top
part of the base (see Figure 6)
Figure 6. Attaching the Bracket
D. Assemble the bracket as shown in Figure 6.
E. Rotate the bracket to the desired position (see Figure 7) but
do not yet tighten the screw fully.
Figure 7. Wall and Ceiling Positions of Bracket
F. Punch out the selected
wiring knockouts in the
bracket (see Figure 8).
G. Press the bracket
against the mounting
surface and mark the
points for drilling. Drill
out the holes and
insert plastic dowels. Figure 8. Bracket Base, Rear View
DE1842 3
H. Route the cable
through the bracket
and into the detector
as shown in Figure 9.
I. Attach the bracket to
the mounting surface
using the two screws
supplied.
J. Swivel the detector
horizontally to face
the desired direction,
but do not tilt it if
this is a pet immune Figure 9. Routing the Cable
application (see Figure 10). However, if pets are not present it
is advisable to tilt the detector as much as 20°down.
Figure 10. Tilt/Swivel Limits
K. Having pointed the detector as desired, tighten the bracket
screw strongly, to prevent any further change of position.
3.4 Wiring
Refer to Figure 11
and connect wires
to the terminal
block in the order
given below:
Terminal: TAMP
(tamper switch)
Connect to: A
normally closed 24-
hour tamper zone
of the control panel.
Details: Upon re-
moval of the cover,
the tamper contacts
open. Figure 11. Terminal Block Wiring
Terminal: NC (alarm relay)
Connect to: Normally closed burglar protection zone.
Details: Upon alarm or power failure, the output relay's normally
closed contacts open.
Terminal: TRB (trouble output)
Connect to: 24-hour trouble zone
Details: The TRB open collector output will be grounded upon
detector malfunction, thus triggering the trouble zone.
Alternative: A buzzer or an interface relay may be connected
across the TRB output and the 12 VDC (+) terminals.
Terminal: TST (TEST input)
Connect to: +12 VDC or ground potential (depending on the
setting of DIP switch SW-3) via a test switch.
Details: Applying the trigger voltage to the TST input will enable
the dual color LED for walk testing.
Terminals: 12 V (+) and (–)
Connect to: A power source within the range of 9 to 16 VDC.
Details: It is advisable to connect the power source only after all
other connections have been completed and rechecked. Dis-
connect the AC mains from the alarm control panel and verify that
the voltage supplied to the detector is above 9 Volts with the
backup battery as the only power source.
Note: Use RTV to seal the base opening(s) to prevent insects
from entering the detector.
3.5 The Power-up Process
After connecting the (+) and (–) terminals to the power source,
the LOGICA starts a 30-second warm-up period, indicated by
alternate flashing of the green and red lights.
Caution! If the alternate flashing of the red and green lights
does not stop within 30 seconds, a failure has been detected by
the self-test circuitry.
3.6 Visual Indications
The dual color LED is used to signal various alarm and trouble
messages as shown in Table 1 below:
Table 1. Interpreting the Visual Indications
Visual Indication Significance
None No detection
Steady green (5 s) MW walk-test detection
Flashing green PIR walk-test detection
Steady red (5 s) Alarm: MW + PIR detection
Flashing red and - Trouble is being detected by the self
green (alternately) test circuitry, or
- Initial warm-up routine (stops 30
seconds after power up).
Notes: 1. During walk testing, the green light lights steadily (MW detection) or
flashes (PIR detection), depending on which one of the two detectors discovered
the movement first. Upon subsequent discovery of the movement by the other
detector, the green light goes off and the red light comes on (alarm).
2. If the LED maintains alternate red and green flashing beyond the warm-up
period, a malfunction has been diagnosed. Replace the unit without delay.
3.7 Mode Selector
The DIP switch mode
selector is mounted on
the unit’s PC board (see
Figure 5). It controls four
functions as demonst-
rated in Figure 12 and
as detailed in Table 2. Figure 12. DIP Switch Mode Selector
Table 2. Mode Selector Switch functions
Switch State Function
SW-1 OFF One motion event trips the PIR
ON Two motion events trip the PIR
SW-2 OFF The walk-test LED is disabled*
ON The walk-test LED is enabled permanently
SW-3 OFF LED enabled remotely by ground potential (–)
applied to TST input; LED disabled by floating
TST input (or by +12 VDC applied to the TST
input).
ON LED enabled remotely by floating TST input (or by
+12 VDC applied to the TST input); LED disabled
by ground potential applied to the TST input.
SW-4 OFF Output relay opens upon alarm
ON Output relay opens upon alarm and also when
trouble is detected.
*
The LED may be enabled remotely with a test switch connected to
the TST input as shown in Figure 11.
3.8 Vertical Adjustment
A. Pet-Immune Applications
To maintain maximum coverage range and
pet immunity, the vertical adjustment scale
must be adjusted in accordance with the
actual mounting height (refer to Figure 13).
Loosen the vertical adjustment screw and
slide the printed circuit board up or down until
the pointer shows the actual mounting height on the scale.
When done, re-tighten the screw well.
4DE1842
Figure 13. Vertical Adjustment
B. Pet-Free Locations
To obtain the best coverage possible where no pets are present,
mount the detector with the integral bracket at any desired height
between 1.8 and 2.4 m (6 to 8 ft). Then set the vertical adjustment
scale to the 2.4 m (8 ft) position and tilt the detector 20°down.
3.9 Setting the Motion Event Counter
If you wish to set the PIR detector for maximum false alarm
immunity, shift DIP switch No. 1 (SW-1) to ON. In this position, two
consecutive motion events are required to trip the PIR detector. For
faster catch performance, shift SW-1 to OFF. In this position, only
one motion event is required to trip the PIR detector.
3.10 PIR Walk Test
A. Rotate the MW RANGE control fully counterclockwise to MIN.
B. Verify that DIP switch SW-2 is set to ON (the LED is enabled).
C. Mount the front cover in place.
D. Walk into the detector's field of view at the expected far edge
of the coverage area. The green light should flash for up to 5
seconds each time your motion is detected.
Note: If the green light glows steadily for up to 5 seconds,
your motion has been detected by the MW detector.
E. If PIR detection is not obtained at the far end of the coverage
area, remove the front cover and re-adjust the vertical
position. Replace the cover and retest.
3.11 MW Walk Test
A. Remove the front cover.
B. Verify that the MW RANGE control is set fully counterclockwise
to MIN and that DIP switch SW-2 is set to ON (LED is enabled).
C. Start by moving into the coverage area at the far edge. The
LED should light green for up to 5 seconds each time your
motion is detected.
D. If your motion was not detected at the far edge, advance the
MW RANGE control slightly clockwise toward MAX and try
again until your motion is detected reliably at the far edge.
Caution! The MW detection range must not exceed the far
edge of the desired coverage area.
E. Walk across the coverage area at various ranges and verify
that your motion is consistently detected.
Note: If PIR trips interfere with your test, disable the PIR by
inserting a small piece of cardboard in front of the sensor.
3.12 Alarm Walk Test
A. Set DIP switch SW-2 to ON (the LED is enabled).
B. Install the front cover in place.
C. Walk across the detector’s field of view in different directions,
at various distances from the detector, and verify proper
alarming throughout the detector's coverage area (the red
light glows for 1.3 to 5 seconds).
D. When done, remove the cover and set DIP switch SW-2 to
OFF to prevent unauthorized tracing of the coverage pattern.
E. Remount the cover and fasten it to the base using the small
screw at the bottom.
Attention! To assure proper function of the detector, the range
and coverage area should be checked at least twice a year.
Furthermore, it is recommended that users perform a walk test
at the far end of the coverage pattern to assure an alarm signal
prior to each time the alarm system is armed.
4
44
4. MISCELLANEOUS COMMENTS
. MISCELLANEOUS COMMENTS. MISCELLANEOUS COMMENTS
. MISCELLANEOUS COMMENTS
This device has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in residential installations. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful
interference to radio and television reception. However, there is no
guarantee that interference will not occur in a particular installation. If
this device does cause such interference, which can be verified by
turning the device off and on, the user is encouraged to eliminate the
interference by one or more of the following measures:
– Re-orient or re-locate the receiving antenna.
– Increase the distance between the device and the receiver.
– Connect the device to an outlet on a circuit different from the one
which supplies power to the receiver.
– Consult the dealer or an experienced radio/TV technician.
WARRANTY
WARRANTYWARRANTY
WARRANTY
Visonic Ltd. and/or its subsidiaries and its affiliates ("the Manufacturer") warrants its
products hereinafter referred to as "the Product" or "Products" to be in conformance with
its own plans and specifications and to be free of defects in materials and workmanship
under normal use and service for a period of twelve months from the date of shipment by
the Manufacturer. The Manufacturer's obligations shall be limited within the warranty
period, at its option, to repair or replace the product or any part thereof. The Manufacturer
shall not be responsible for dismantling and/or reinstallation charges. To exercise the
warranty the product must be returned to the Manufacturer freight prepaid and insured.
This warranty does not apply in the following cases: improper installation, misuse,
failure to follow installation and operating instructions, alteration, abuse, accident or
tampering, and repair by anyone other than the Manufacturer.
This warranty is exclusive and expressly in lieu of all other warranties, obligations or
liabilities, whether written, oral, express or implied, including any warranty of
merchantability or fitness for a particular purpose, or otherwise. In no case shall the
Manufacturer be liable to anyone for any consequential or incidental damages for breach
of this warranty or any other warranties whatsoever, as aforesaid.
This warranty shall not be modified, varied or extended, and the Manufacturer does not
authorize any person to act on its behalf in the modification, variation or extension of this
warranty. This warranty shall apply to the Product only. All products, accessories or
attachments of others used in conjunction with the Product, including batteries, shall be
covered solely by their own warranty, if any. The Manufacturer shall not be liable for any
damage or loss whatsoever, whether directly, indirectly, incidentally, consequentially or
otherwise, caused by the malfunction of the Product due to products, accessories, or
attachments of others, including batteries, used in conjunction with the Products.
The Manufacturer does not represent that its Product may not be compromised and/or
circumvented, or that the Product will prevent any death, personal and/or bodily injury
and/or damage to property resulting from burglary, robbery, fire or otherwise, or that the
Product will in all cases provide adequate warning or protection. User understands that a
properly installed and maintained alarm may only reduce the risk of events such as
burglary, robbery, and fire without warning, but it is not insurance or a guarantee that such
will not occur or that there will be no death, personal damage and/or damage to property
as a result.
The Manufacturer shall have no liability for any death, personal and/or bodily injury
and/or damage to property or other loss whether direct, indirect, incidental,
consequential or otherwise, based on a claim that the Product failed to function.
However, if the Manufacturer is held liable, whether directly or indirectly, for any loss or
damage arising under this limited warranty or otherwise, regardless of cause or origin, the
Manufacturer's maximum liability shall not in any case exceed the purchase price of the
Product, which shall be fixed as liquidated damages and not as a penalty, and shall be the
complete and exclusive remedy against the Manufacturer.
Warning: The user should follow the installation and operation instructions and among
other things test the Product and the whole system at least once a week. For various
reasons, including, but not limited to, changes in environmental conditions, electric or
electronic disruptions and tampering, the Product may not perform as expected. The user
is advised to take all necessary precautions for his/her safety and the protection of his/her
property.
6/91
VISONIC LTD. (ISRAEL): P.O.B 22020 TEL-AVIV 61220 ISRAEL. PHONE: (972-3) 645-6789, FAX: (972-3) 645-6788
VISONIC INC. (U.S.A.): 10 NORTHWOOD DRIVE, BLOOMFIELD CT. 06002-1911. PHONE: (860) 243-0833, (800) 223-0020 FAX: (860) 242-8094
VISONIC LTD. (UK): UNIT 1, STRATTON PARK, DUNTON LANE, BIGGLESWADE, BEDS. SG18 8QS. PHONE: (01767) 600857 FAX: (01767) 601098
INTERNET: www.visonic.com
VISONIC LTD. 2000 K-980D DE1842- (REV. 1, 3/00)

Other Visonic Security Sensor manuals

Visonic DISC MCW User manual

Visonic

Visonic DISC MCW User manual

Visonic GB-502 PG2 User manual

Visonic

Visonic GB-502 PG2 User manual

Visonic MCT-550 User manual

Visonic

Visonic MCT-550 User manual

Visonic DUET-AM C/O User manual

Visonic

Visonic DUET-AM C/O User manual

Visonic DISCOVERY PIR MCW User manual

Visonic

Visonic DISCOVERY PIR MCW User manual

Visonic CLIP Series User manual

Visonic

Visonic CLIP Series User manual

Visonic MCPIR-3000 User manual

Visonic

Visonic MCPIR-3000 User manual

Visonic TOWER-32AMPG2 User manual

Visonic

Visonic TOWER-32AMPG2 User manual

Visonic NEXT PLUS PIR / K9-85 User manual

Visonic

Visonic NEXT PLUS PIR / K9-85 User manual

Visonic TOWER 20 AM - INSTALLER GUIDE User manual

Visonic

Visonic TOWER 20 AM - INSTALLER GUIDE User manual

Visonic TOWER CAM PG2 User manual

Visonic

Visonic TOWER CAM PG2 User manual

Visonic TOWER 20 AM - INSTALLER GUIDE User manual

Visonic

Visonic TOWER 20 AM - INSTALLER GUIDE User manual

Visonic DISCOVERY K9-80 User manual

Visonic

Visonic DISCOVERY K9-80 User manual

Visonic MCT-302 User manual

Visonic

Visonic MCT-302 User manual

Visonic DUO 240 - INSTALLER GUIDE User manual

Visonic

Visonic DUO 240 - INSTALLER GUIDE User manual

Visonic MP-840 User manual

Visonic

Visonic MP-840 User manual

Visonic GSD-441 PG2 User manual

Visonic

Visonic GSD-441 PG2 User manual

Visonic Quatro+ User manual

Visonic

Visonic Quatro+ User manual

Visonic DUO 220 User manual

Visonic

Visonic DUO 220 User manual

Visonic POWERMAX - User manual

Visonic

Visonic POWERMAX - User manual

Visonic MCT-350 User manual

Visonic

Visonic MCT-350 User manual

Visonic MCT-560 User manual

Visonic

Visonic MCT-560 User manual

Visonic NEXT PLUS Series User manual

Visonic

Visonic NEXT PLUS Series User manual

Visonic NEXT PG2 - User manual

Visonic

Visonic NEXT PG2 - User manual

Popular Security Sensor manuals by other brands

schmersal AZM 160 Mounting and wiring instructions

schmersal

schmersal AZM 160 Mounting and wiring instructions

Hanwei GE-201 operating manual

Hanwei

Hanwei GE-201 operating manual

Alula RE129 install guide

Alula

Alula RE129 install guide

DSC LC-102PIGBSS installation instructions

DSC

DSC LC-102PIGBSS installation instructions

Velleman PIR451 user manual

Velleman

Velleman PIR451 user manual

NA-DE 10970 quick start guide

NA-DE

NA-DE 10970 quick start guide

RKI Instruments 35-3001-05 Series Operator's manual

RKI Instruments

RKI Instruments 35-3001-05 Series Operator's manual

Vaisala MD30 reference guide

Vaisala

Vaisala MD30 reference guide

Tarmo 603129 instructions

Tarmo

Tarmo 603129 instructions

Cavius 6005-001 quick start guide

Cavius

Cavius 6005-001 quick start guide

ZUCCHETTI AXESS 907 AX BIO user manual

ZUCCHETTI AXESS

ZUCCHETTI AXESS 907 AX BIO user manual

THORLABS SIR5-FC manual

THORLABS

THORLABS SIR5-FC manual

CT BE UP manual

CT

CT BE UP manual

Panasonic HL-G1 Series user manual

Panasonic

Panasonic HL-G1 Series user manual

Siemens QNA2 D Series Commissioning

Siemens

Siemens QNA2 D Series Commissioning

Dilon Navigator 2.0 User and service manual

Dilon

Dilon Navigator 2.0 User and service manual

Ecolink WST-601 Installation manual & users guide

Ecolink

Ecolink WST-601 Installation manual & users guide

Vimar NEVE UP 09462 manual

Vimar

Vimar NEVE UP 09462 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.