Waterco MultiCyclone Plus User manual

Waterco Limited ABN 62 002 070 733
www.waterco.com
WARNING
(W99279) 11/2010
OFFICES - AUSTRALIA
NSW - Sydney
(HEAD OFFICE)
Tel : +61 2 9898 8686
VIC/ TAS - Melbourne
Tel : +61 3 9764 1211
WA - Perth
Tel : +61 8 9273 1900
QLD - Brisbane
Tel : +61 7 3299 9900
SA/ NT - Adelaide
Tel : +61 8 8244 6000
ACT Distributor
Tel : +61 2 6280 6476
OFFICES - OVERSEAS
Waterco USA
Augusta, USA
Tel : +1 706 793 7291
Waterco Canada
St-Hyacinthe, QC, Canada
Tel : +1 450 796 1421
Waterco (Europe) Limited
Sittingbourne, Kent. UK
Tel : +44(0) 1795 521 733
Waterco (NZ) Limited
Auckland, New Zealand
Tel : +64 9 525 7570
Waterco (C) Limited
Guangzhou, China
Tel : +8620 3222 2180
Waterco (Far East) Sdn. Bhd.
Selangor, Malaysia
Tel : +60 3 6145 6000
PT Waterco Indonesia
Jakarta, Indonesia
Tel : +62 21 4585 1481
Waterco International Pte Ltd
Singapore
Tel : +65 6344 2378
Installation and
Operation Manual
This equipment must be installed and serviced by a qualified technician.
Improper installation may result in property damage, serious injury or death.
Improper installation and/or operation will void the warranty.
Notice to Installer
This manual contains important information about the installation, operation
& safe use of this product. Once the product has been installe this manual
must be given to the owner / operator of this equipment.
Rainbow Pool Products
PO Box 2388, Mansfield Qld 4122
Telephone STD 61-7-3849 5385
Facsimile STD 61-7-3849 5384
Email: [email protected]
Web: www.rainbowpoolproducts.com.au

SAFETY INFORMATION
1. The Waterco MultiCyclone lters are designed to work with water at a temperature > than
0ºC and < than 45ºC. The lter should never be operated outside of these temperatures or
damage may occur.
2. The installation should be carried out in accordance to local safety standards and bylaws.
3. Any modication of the lter requires the prior consent from Waterco. Original replacement
parts and accessories authorised by the manufacturer ensure a high level of safety. Waterco
assumes no liability for the damage and injuries caused by unauthorised replacement parts
and accessories.
4. The user should make sure that the installation is carried out by qualied authorised persons
and that these persons have rst carefully read the following instructions.
5. The operating safety of the lter is only guaranteed if the installation and operation
instructions are correctly followed.
6. In the event of defective operation or fault, contact Waterco or its nearest authorised service
agent.
7. To reduce the risk of injury, do not permit children to use this product.
8. Incorrectly installed equipment may fail, causing severe injury or property damage.
9. Chemical spills and fumes can weaken Swimming Pool / Spa equipment. Corrosion can
cause lters and other equipment to fail, resulting in severe injury or property damage. Do
not store pool chemicals near your equipment.
I pg 02
MultiCyclone Plus
MULTICYCLONE PLUS
MultiCyclone Plus combines centrifugal and cartridge ltration into one streamlined housing,
creating an ultra compact ltration system.
r%VBMTUBHFàMUSBUJPO
r.JOJNBMNBJOUFOBODF
r4BWFXBUFSBOEFOFSHZ
rIZESPDZDMPOFT
rGU2pleated lter cartridge.
Dual stage filtration
Incoming water tangentially enters its multiple
hydrocyclones, generating a strong centrifugal effect.
Approximately 80% of the incoming dirt load is spiralled
down to its clear sediment chamber. The outgoing water
is nally polished via its inbuilt cartridge lter, producing
crystal clear water.
Simple maintenance
MultiCyclone Plus’s sediment chamber is easily cleaned
by opening its purge valve. Only 15 litres of water is
discharged.
Ultra compact filtration
MultiCyclone Plus’s streamlined design means the entire
ltration system can be installed vertically, reducing the
footprint of the equipment pad. Additionally, minimal
pipework reduces ltration system’s overall head loss.
Extended filter capacity
The MultiCyclone Plus’s centrifugal section lter pre-lters
up to 80% of the incoming dirt load before it reaches
the lter cartridge, magnifying the capacity of its 40 ft2
lter cartridge by up to 5 times. MultiCyclone Plus has a
ltration capacity equivalent to a 200 ft2cartridge lter.
SAFTEY INFORMATION ------------------------------------------ 01
MULTICYCLONE PLUS ------------------------------------------- 02
MULTICYCLONE TOTAL HEAD LOSS CURVE ------------------ 04
INSTALLATION ---------------------------------------------------- 04
START UP PROCEEDURES -------------------------------------- 06
MULTICYCLONE PLUS FILTER MAINTENANCE ---------------- 07
INSUFFICIENT WATER PRESSURE ------------------------------ 07
FILTER CARTRIDGE MAINTENANCE ---------------------------- 08
GENERAL MAINTENANCE GUIDE ------------------------------ 09
WINTERISING ----------------------------------------------------- 09
TROUBLESHOOTING GUIDE ------------------------------------ 10
WARRANTY ------------------------------------------------------- 10

SAFETY INFORMATION
1. The Waterco MultiCyclone lters are designed to work with water at a temperature > than
0ºC and < than 45ºC. The lter should never be operated outside of these temperatures or
damage may occur.
2. The installation should be carried out in accordance to local safety standards and bylaws.
3. Any modication of the lter requires the prior consent from Waterco. Original replacement
parts and accessories authorised by the manufacturer ensure a high level of safety. Waterco
assumes no liability for the damage and injuries caused by unauthorised replacement parts
and accessories.
4. The user should make sure that the installation is carried out by qualied authorised persons
and that these persons have rst carefully read the following instructions.
5. The operating safety of the lter is only guaranteed if the installation and operation
instructions are correctly followed.
6. In the event of defective operation or fault, contact Waterco or its nearest authorised service
agent.
7. To reduce the risk of injury, do not permit children to use this product.
8. Incorrectly installed equipment may fail, causing severe injury or property damage.
9. Chemical spills and fumes can weaken Swimming Pool / Spa equipment. Corrosion can
cause lters and other equipment to fail, resulting in severe injury or property damage. Do
not store pool chemicals near your equipment.
I pg 02
MultiCyclone Plus
MULTICYCLONE PLUS
MultiCyclone Plus combines centrifugal and cartridge ltration into one streamlined housing,
creating an ultra compact ltration system.
r%VBMTUBHFàMUSBUJPO
r.JOJNBMNBJOUFOBODF
r4BWFXBUFSBOEFOFSHZ
rIZESPDZDMPOFT
rGU2pleated lter cartridge.
Dual stage filtration
Incoming water tangentially enters its multiple
hydrocyclones, generating a strong centrifugal effect.
Approximately 80% of the incoming dirt load is spiralled
down to its clear sediment chamber. The outgoing water
is nally polished via its inbuilt cartridge lter, producing
crystal clear water.
Simple maintenance
MultiCyclone Plus’s sediment chamber is easily cleaned
by opening its purge valve. Only 15 litres of water is
discharged.
Ultra compact filtration
MultiCyclone Plus’s streamlined design means the entire
ltration system can be installed vertically, reducing the
footprint of the equipment pad. Additionally, minimal
pipework reduces ltration system’s overall head loss.
Extended filter capacity
The MultiCyclone Plus’s centrifugal section lter pre-lters
up to 80% of the incoming dirt load before it reaches
the lter cartridge, magnifying the capacity of its 40 ft2
lter cartridge by up to 5 times. MultiCyclone Plus has a
ltration capacity equivalent to a 200 ft2cartridge lter.
SAFTEY INFORMATION ------------------------------------------ 01
MULTICYCLONE PLUS ------------------------------------------- 02
MULTICYCLONE TOTAL HEAD LOSS CURVE ------------------ 04
INSTALLATION ---------------------------------------------------- 04
START UP PROCEEDURES -------------------------------------- 06
MULTICYCLONE PLUS FILTER MAINTENANCE ---------------- 07
INSUFFICIENT WATER PRESSURE ------------------------------ 07
FILTER CARTRIDGE MAINTENANCE ---------------------------- 08
GENERAL MAINTENANCE GUIDE ------------------------------ 09
WINTERISING ----------------------------------------------------- 09
TROUBLESHOOTING GUIDE ------------------------------------ 10
WARRANTY ------------------------------------------------------- 10

MULTICYCLONE PLUS TOTAL HEAD LOSS CURVE
I pg 04
Note: The MultiCyclone Plus centrifugal section is designed to lter sediment that is heavier
than water; oating debris cannot be ltered out by centrifugal ltration.
INSTALLATION
Be sure to comply with the local plumbing codes.
Be sure that all provisions for wastewater disposal meet local, state or national codes. Do not
discharge water where it will cause ooding or damage.
If the incoming water pressure is higher than the maximum operating pressure of 350kPa /
3.5Bar / 50psi, a Pressure Regulating Valve (PRV) must be installed upstream of the lter inlet.
The PRV should be set to 90% of the maximum operating pressure of the tank.
If the incoming water ow is less than the lter’s minimum ow requirements, the lter’s ltration
efciency will be affected, please consult Waterco.
Model Connection
Ports
Minimum
Flow
Maximum
Flow
Filter
Area
Max.
Pressure
MultiCyclone12
Plus
40mm / 50mm
(EU) / 1 1/2”
40lpm / 2.4 m3/hr
/ 11gpm
152lpm / 9.1 m3/
hr / 40gpm 3.7m2/ 40 ft2350 kPa
(50psi)
MultiCyclone16
Plus
50mm / 63mm
(EU) / 2”
50lpm / 3 m3/hr /
13gpm
152lpm / 9.1 m3/
hr / 40gpm 3.7m2/ 40 ft2350 kPa
(50psi)
Air Release Valve
Filter Cartridge Housing Lid
Filter Housing Retaining Clamp
Band Tightening Nut
Filter Cartridge Housing
Clear Poly Carbonate Sediment
Chamber
Water Flow
12 Plus: 40mm/50mm (EU)
1 ½” Quick Fit Union.
16 Plus: 50mm/63mm (EU)
2” Quick Fit Union.
Pressure Gauge
Filter Housing Retaining Clamp Band
3.7m2/ 40ft2Pleated Filter Cartridge
12 / 16 Hydrocyclones
12 Plus: 40mm/50mm (EU)
1 ½” Quick Fit Union.
16 Plus: 50mm/63mm (EU)
2” Quick Fit Union.
25mm / 32mm (EU)
1” Purge Valve
0
2
4
6
8
10
12
0 50 100 150 200 250 300 350 400
MultiCyclone Plus Total Head Loss Curve
Flow lpm
Head Loss (m)
MultiCyclone 12 Plus MultiCyclone 16 Plus
Typical Installation
1. Position the lter as close to the Swimming Pool / Spa as possible.
2. Position the lter so that it is free from ooding, away from sumps,
guttering, garden hollows, etc.
3. Position the lter so that the piping connections purge valve and air
release valve is convenient and accessible for operation, servicing and
winterising.
4. Ensure that the compliance label is facing the front to allow easy
identication.
MultiCyclone Plus

MULTICYCLONE PLUS TOTAL HEAD LOSS CURVE
I pg 04
Note: The MultiCyclone Plus centrifugal section is designed to lter sediment that is heavier
than water; oating debris cannot be ltered out by centrifugal ltration.
INSTALLATION
Be sure to comply with the local plumbing codes.
Be sure that all provisions for wastewater disposal meet local, state or national codes. Do not
discharge water where it will cause ooding or damage.
If the incoming water pressure is higher than the maximum operating pressure of 350kPa /
3.5Bar / 50psi, a Pressure Regulating Valve (PRV) must be installed upstream of the lter inlet.
The PRV should be set to 90% of the maximum operating pressure of the tank.
If the incoming water ow is less than the lter’s minimum ow requirements, the lter’s ltration
efciency will be affected, please consult Waterco.
Model Connection
Ports
Minimum
Flow
Maximum
Flow
Filter
Area
Max.
Pressure
MultiCyclone12
Plus
40mm / 50mm
(EU) / 1 1/2”
40lpm / 2.4 m3/hr
/ 11gpm
152lpm / 9.1 m3/
hr / 40gpm 3.7m2/ 40 ft2350 kPa
(50psi)
MultiCyclone16
Plus
50mm / 63mm
(EU) / 2”
50lpm / 3 m3/hr /
13gpm
152lpm / 9.1 m3/
hr / 40gpm 3.7m2/ 40 ft2350 kPa
(50psi)
Air Release Valve
Filter Cartridge Housing Lid
Filter Housing Retaining Clamp
Band Tightening Nut
Filter Cartridge Housing
Clear Poly Carbonate Sediment
Chamber
Water Flow
12 Plus: 40mm/50mm (EU)
1 ½” Quick Fit Union.
16 Plus: 50mm/63mm (EU)
2” Quick Fit Union.
Pressure Gauge
Filter Housing Retaining Clamp Band
3.7m2/ 40ft2Pleated Filter Cartridge
12 / 16 Hydrocyclones
12 Plus: 40mm/50mm (EU)
1 ½” Quick Fit Union.
16 Plus: 50mm/63mm (EU)
2” Quick Fit Union.
25mm / 32mm (EU)
1” Purge Valve
0
2
4
6
8
10
12
0 50 100 150 200 250 300 350 400
MultiCyclone Plus Total Head Loss Curve
Flow lpm
Head Loss (m)
MultiCyclone 12 Plus MultiCyclone 16 Plus
Typical Installation
1. Position the lter as close to the Swimming Pool / Spa as possible.
2. Position the lter so that it is free from ooding, away from sumps,
guttering, garden hollows, etc.
3. Position the lter so that the piping connections purge valve and air
release valve is convenient and accessible for operation, servicing and
winterising.
4. Ensure that the compliance label is facing the front to allow easy
identication.
MultiCyclone Plus

I pg 06
5. The lter should be placed on a level concrete slab, very rm ground, or equivalent. Ensure
that the ground will not subside, preventing any strain from the attached plumbing.
6. Ensure that there is no movement of the lter during operation of the purge valve.
7. Allow sufcient clearance around the lter to permit visual inspection of the entire system.
Plumbing
1. Check that the incoming water pressure is within the lter’s recommended working pressure
and ensure that a pressure limiting valve is installed if using mains water or a high pressure
pump.
2. Ensure that a foot valve / non return valve are installed if the pump is installed 500mm / 20”
above the water level.
3. If the lter is installed below the water level or connected to mains water, isolation valves
should be installed at the inlet and outlet of the lter. This will prevent water ow during any
routine maintenance.
4. Minimise the length of pipe and the number of ttings to minimise restrictions to water ow.
5. Ensure that all plumbing connections are glued and tightened securely to prevent leaking.
6. Ensure solvents are not excessively applied to ttings as this could run into “o”-rings and
create sealing problems.
7. Do not over tighten ttings or adapters.
Screw the supplied half barrel unions and tails onto the inlet and outlet before gluing the UPVC
piping onto the lter.
Use only recommended glue for connection pipe and fittings
Cut and t the pipe and ttings onto the MultiCyclone Plus and the pump. Refer to Pump
Installation Manual for correct pump plumbing procedures.
It is best practice to t all the cut pipe and ttings onto the ltration system before gluing; this
will ensure that the system has been aligned correctly.
Glue the pipe and ttings onto the pump, lter and pool return lines and allow the glue to set
for 24 hours before commissioning the system.
Plumbing Connection
1. Connect the pipe extending from the pump outlet to the inlet of the MultiCyclone Plus.
2. Connect from the pipe extending from the outlet of the MultiCyclone Plus to the next
component in line with the ltration system or water return line.
3. Glue all plumbing to barrel union ttings in accordance with glue (solvent) manufactures
specications and allow 24 hours to set. Ensure glue (solvent) is not excessively applied to
ttings as this could run onto “o”-rings and create sealing problems.
Note: Waterco recommends that a shut off valve be installed after the MultiCyclone Plus on
the pool return line to assist with ushing out the collected debris. Please refer to “Insufcient
Water Pressure”.
4. Turn on pool pump. Be sure to check that there are no leaks from the connectors. If required,
tighten by hand.
START UP PROCEEDURES
The MultiCyclone Plus is an advanced and highly efcient lter system that will provide years of
trouble free service if the following maintenance procedures are maintained.
To start up the ltration system either from new or after cleaning is exactly the same.
1. Ensure that the MultiCyclone Plus is plumbed correctly.
2. Ensure that all valves installed before and after the MultiCyclone Plus are open.
3. Loosen the air release valve on top of the MultiCyclone Plus lter lid.
4. Prime the swimming pool pump. (Refer to the pump installation and operation manual).
5. Turn on the swimming pool pump and allow the pump to run until all the air has been expelled
from the MultiCyclone Plus. Water will run from the air release valve.
6. Re-tighten the air release valve.
7. The lter is primed and ready for operation.
Note: In some cases this may be required to be done a few times before the unit will remain
primed and be fully operational.
Do not stand over the lid of the MulitCyclone Plus whilst adjusting the air release valve
to purge the system of air.
Injury may occur if air release valve becomes loose.
MultiCyclone Plus

I pg 06
5. The lter should be placed on a level concrete slab, very rm ground, or equivalent. Ensure
that the ground will not subside, preventing any strain from the attached plumbing.
6. Ensure that there is no movement of the lter during operation of the purge valve.
7. Allow sufcient clearance around the lter to permit visual inspection of the entire system.
Plumbing
1. Check that the incoming water pressure is within the lter’s recommended working pressure
and ensure that a pressure limiting valve is installed if using mains water or a high pressure
pump.
2. Ensure that a foot valve / non return valve are installed if the pump is installed 500mm / 20”
above the water level.
3. If the lter is installed below the water level or connected to mains water, isolation valves
should be installed at the inlet and outlet of the lter. This will prevent water ow during any
routine maintenance.
4. Minimise the length of pipe and the number of ttings to minimise restrictions to water ow.
5. Ensure that all plumbing connections are glued and tightened securely to prevent leaking.
6. Ensure solvents are not excessively applied to ttings as this could run into “o”-rings and
create sealing problems.
7. Do not over tighten ttings or adapters.
Screw the supplied half barrel unions and tails onto the inlet and outlet before gluing the UPVC
piping onto the lter.
Use only recommended glue for connection pipe and fittings
Cut and t the pipe and ttings onto the MultiCyclone Plus and the pump. Refer to Pump
Installation Manual for correct pump plumbing procedures.
It is best practice to t all the cut pipe and ttings onto the ltration system before gluing; this
will ensure that the system has been aligned correctly.
Glue the pipe and ttings onto the pump, lter and pool return lines and allow the glue to set
for 24 hours before commissioning the system.
Plumbing Connection
1. Connect the pipe extending from the pump outlet to the inlet of the MultiCyclone Plus.
2. Connect from the pipe extending from the outlet of the MultiCyclone Plus to the next
component in line with the ltration system or water return line.
3. Glue all plumbing to barrel union ttings in accordance with glue (solvent) manufactures
specications and allow 24 hours to set. Ensure glue (solvent) is not excessively applied to
ttings as this could run onto “o”-rings and create sealing problems.
Note: Waterco recommends that a shut off valve be installed after the MultiCyclone Plus on
the pool return line to assist with ushing out the collected debris. Please refer to “Insufcient
Water Pressure”.
4. Turn on pool pump. Be sure to check that there are no leaks from the connectors. If required,
tighten by hand.
START UP PROCEEDURES
The MultiCyclone Plus is an advanced and highly efcient lter system that will provide years of
trouble free service if the following maintenance procedures are maintained.
To start up the ltration system either from new or after cleaning is exactly the same.
1. Ensure that the MultiCyclone Plus is plumbed correctly.
2. Ensure that all valves installed before and after the MultiCyclone Plus are open.
3. Loosen the air release valve on top of the MultiCyclone Plus lter lid.
4. Prime the swimming pool pump. (Refer to the pump installation and operation manual).
5. Turn on the swimming pool pump and allow the pump to run until all the air has been expelled
from the MultiCyclone Plus. Water will run from the air release valve.
6. Re-tighten the air release valve.
7. The lter is primed and ready for operation.
Note: In some cases this may be required to be done a few times before the unit will remain
primed and be fully operational.
Do not stand over the lid of the MulitCyclone Plus whilst adjusting the air release valve
to purge the system of air.
Injury may occur if air release valve becomes loose.
MultiCyclone Plus

I pg 08
MULTICYCLONE PLUS FILTER MAINTENANCE
The MultiCyclone Plus lter maintenance is determined by the following conditions:
1. The sediment chamber is half lled with sediment. This accumulation of sediment can be
visibly monitored through the MultiCyclone Plus’s clear sediment chamber. The MultiCyclone
Plus is cleaned by simply opening the purge valve. Only 15 litres (4 gallons) of water is
discharged to clean the MultiCyclone of sediment.
2. A pressure gauge reading of 50kPa (7.2psi) above the operating pressure may result in a
reduced ow rate that is insufcient to meet the requirements of the pool.
Example: Filter operates normally at 60kPa (8.2psi) needs to be cleaned at 110kPa (16psi).
Flush out the sediment chamber
With pump running:
Whilst the water pump is running simply open the sediment purge valve until the sediment has
been ushed out. This is visible through the clear sediment chamber. Once the sediment has
been ushed out, close the purge valve.
Without pump running:
Alternatively, switch the pump, off. Open the air release valve and then open the purge valve.
The water will drop through the MultiCyclone Plus ushing out most of the debris from the
sediment chamber. Then close the air release valve and turn on the pump and the turbulence
of the water entering the sediment chamber will ush out the rest of the sediment. Once the
sediment chamber has been cleansed, close the purge valve, start the pump and close the air
release valve once water is owing out through the air release valve.
INSUFFICIENT WATER PRESSURE
In situations where the water ow from the pump is not powerful enough purge the sediment
out of the sediment chamber. Waterco recommends tting a 2 way valve after the MultiCyclone
Plus on the pool water return line.
The 2 way valve is used to throttle the ow of water out of the MultiCyclone Plus, increasing
water turbulence through the sediment chamber and improving its purging action.
Whilst the pump is operating, open the purge valve, and then partially close the 2 way valve,
throttling the water ow sufciently to purge the sediment chamber of trapped sediment. Once
the sedimement chamber is clean, open the 2 way valve and then close the purge valve.
Do not close the 2 way valve prior to opening the purge valve and do not close the purge
valve while the 2 way valve is closed or partially closed. Both valves should never be
closed or partially closed at the same time.
FILTER CARTRIDGE MAINTENANCE
To ensure maximum life from your MultiCyclone Plus’s lter cartridge you need to maintain the
lter cartridge regularly.
When the lter is rst started and has been purged of air, note the pressure on the pressure
gauge. This is what is known as the lter operating pressure and it is important that you be
aware of this gure.
All ltration systems will operate at different pressures depending on the pool hydraulics.
You will need to clean the lter cartridge once the pressure gauge has reached 50kPa (7.2psi)
above the operating pressure.
Example: Filter operates normally at 60kPa (8.2psi) needs to be cleaned at
110kPa (16psi).
Cartridge Cleaning
Prior to removing the MultiCyclone Plus cartridge lter’s lid, you will need to release the pressure
from the lter cartridge housing. With the pump off, loosen the air release valve on top of the
MultiCyclone Plus lter lid to release pressure from the lter housing.
1. Undo and remove the clamp around the cartridge lter’s lid by unscrewing the tightening
nuts, this can be either by hand or using a 25mm (1”) open end spanner/adjustable wrench
on the moulded hexagon section and remove the lid off the lter tank.
2. Remove the lter cartridge from the lter housing.
3. Using a garden type hose clean the surface of the pleated element. Make sure to clean
between the pleats.
4. Place the lter cartridge back into the lter housing ensuring that it is seated correctly.
5. Ensure the lid “o”-ring is clean of any debris and is correctly seated into lter body “o”-ring
groove prior to lid being retted.
6. Place the lid onto the lter housing and ret retaining clamp band and tightening nuts using
a 25mm (1”) open end spanner/adjustable wrench ensuring lid is correctly tted.
7. Refer to the start up procedure to recommence operation.
MultiCyclone Plus
Do not over tighten the lid tightening nuts.

I pg 08
MULTICYCLONE PLUS FILTER MAINTENANCE
The MultiCyclone Plus lter maintenance is determined by the following conditions:
1. The sediment chamber is half lled with sediment. This accumulation of sediment can be
visibly monitored through the MultiCyclone Plus’s clear sediment chamber. The MultiCyclone
Plus is cleaned by simply opening the purge valve. Only 15 litres (4 gallons) of water is
discharged to clean the MultiCyclone of sediment.
2. A pressure gauge reading of 50kPa (7.2psi) above the operating pressure may result in a
reduced ow rate that is insufcient to meet the requirements of the pool.
Example: Filter operates normally at 60kPa (8.2psi) needs to be cleaned at 110kPa (16psi).
Flush out the sediment chamber
With pump running:
Whilst the water pump is running simply open the sediment purge valve until the sediment has
been ushed out. This is visible through the clear sediment chamber. Once the sediment has
been ushed out, close the purge valve.
Without pump running:
Alternatively, switch the pump, off. Open the air release valve and then open the purge valve.
The water will drop through the MultiCyclone Plus ushing out most of the debris from the
sediment chamber. Then close the air release valve and turn on the pump and the turbulence
of the water entering the sediment chamber will ush out the rest of the sediment. Once the
sediment chamber has been cleansed, close the purge valve, start the pump and close the air
release valve once water is owing out through the air release valve.
INSUFFICIENT WATER PRESSURE
In situations where the water ow from the pump is not powerful enough purge the sediment
out of the sediment chamber. Waterco recommends tting a 2 way valve after the MultiCyclone
Plus on the pool water return line.
The 2 way valve is used to throttle the ow of water out of the MultiCyclone Plus, increasing
water turbulence through the sediment chamber and improving its purging action.
Whilst the pump is operating, open the purge valve, and then partially close the 2 way valve,
throttling the water ow sufciently to purge the sediment chamber of trapped sediment. Once
the sedimement chamber is clean, open the 2 way valve and then close the purge valve.
Do not close the 2 way valve prior to opening the purge valve and do not close the purge
valve while the 2 way valve is closed or partially closed. Both valves should never be
closed or partially closed at the same time.
FILTER CARTRIDGE MAINTENANCE
To ensure maximum life from your MultiCyclone Plus’s lter cartridge you need to maintain the
lter cartridge regularly.
When the lter is rst started and has been purged of air, note the pressure on the pressure
gauge. This is what is known as the lter operating pressure and it is important that you be
aware of this gure.
All ltration systems will operate at different pressures depending on the pool hydraulics.
You will need to clean the lter cartridge once the pressure gauge has reached 50kPa (7.2psi)
above the operating pressure.
Example: Filter operates normally at 60kPa (8.2psi) needs to be cleaned at
110kPa (16psi).
Cartridge Cleaning
Prior to removing the MultiCyclone Plus cartridge lter’s lid, you will need to release the pressure
from the lter cartridge housing. With the pump off, loosen the air release valve on top of the
MultiCyclone Plus lter lid to release pressure from the lter housing.
1. Undo and remove the clamp around the cartridge lter’s lid by unscrewing the tightening
nuts, this can be either by hand or using a 25mm (1”) open end spanner/adjustable wrench
on the moulded hexagon section and remove the lid off the lter tank.
2. Remove the lter cartridge from the lter housing.
3. Using a garden type hose clean the surface of the pleated element. Make sure to clean
between the pleats.
4. Place the lter cartridge back into the lter housing ensuring that it is seated correctly.
5. Ensure the lid “o”-ring is clean of any debris and is correctly seated into lter body “o”-ring
groove prior to lid being retted.
6. Place the lid onto the lter housing and ret retaining clamp band and tightening nuts using
a 25mm (1”) open end spanner/adjustable wrench ensuring lid is correctly tted.
7. Refer to the start up procedure to recommence operation.
MultiCyclone Plus
Do not over tighten the lid tightening nuts.

I pg 10
It is suggested that you should periodically remove the lter cartridge and soak it over night in
a suitable cartridge cleaning compound. This will remove any debris not removed by hosing
down of the lter cartridge.
Some swimming pool stores offer a lter cartridge cleaning service using the correct solutions
otherwise you may wish to use Waterco Cartridge cleaning solution. Directions of use are on
the product.
The cleaning time depends upon the swimming pool condition and use. Intervals between
cleaning the element should not exceed a period of 12 months in any instance.
GENERAL MAINTENANCE GUIDE
To ensure the maximum life of the MultiCyclone Plus, please follow the procedures below:
1. Clean the lter cartridge regularly according to the instructions set under “MultiCyclone Filter
Cartridge”
2. Maintain a correct chemical balance of your pool / spa water. The chemical balance of water
is a relationship between its pH, total alkalinity, calcium hardness and water temperature.
The water must be maintained at all times to the following:
PH LEVEL : BETWEEN 7.2 & 7.8.
TOTAL ALKALINITY : BETWEEN 80 & 150ppm.
CALCIUM HARDNESS : BETWEEN 150 & 300ppm.
Also, within these tolerances be balanced to the Langelier Saturation Index within a range of
-0.2 to +0.2.
Note: Testing kits are available to test the water yourself or alternately bring a sample of the
water to a professional pool and spa shop.
3. Mains water and rural water supplies need to be monitored. Saturation (life) in mains water
or bore (rural) will vary depending on water quality.
4. To prevent damage to the pump and lter and for proper operation of the system, clean
pump strainer and skimmer baskets regularly.
5. Replace the pressure gauge if faulty readings are observed.
WINTERISING
Proper winterising procedures should always be taken in order to protect your lter in cold
climates (temperatures below freezing point).
1. Switch off the Pump / Close the inlet valve.
TROUBLESHOOTING GUIDE
WARRANTY
MultiCyclone Plus is covered by a 2 year warranty and 1 year warranty on labour. Commercial
installations are covered by a 1 year warranty.
Please refer to Waterco’s warranty terms and conditions.
Symptoms Possible Problems / Solutions
Water Is Not Clear
Insufcient disinfectant level.
Incorrect pool chemistry.
Heavy bathing and/ or dirt loads.
Incorrect ow.
Insufcient running times. (Increase pump run time.)
Filter is dirty. (Clean per instructions.)
Hole in lter element.
Air leak on suction line
Pump impeller vanes blocked
Other restrictions include (pool suction cleaners) resistance from other inline
equipment such as strainers.
Pump not primed.
Low Water Flow
Check strainer baskets for debris.
Check for air leaks on suction side.
Check for restrictions or blockage in either suction or return lines.
Filter needs to be cleaned or replaced.
Pool water level too low.
Pump not primed.
Pump impeller vanes blocked.
Strainer baskets not being used and/ or not being cleaned regularly.
Pump operating under speed (low voltage).
Short Filter Cycles
Presence of algae, check disinfectant content.
Check pH and total alkalinity.
Pump output exceeds design ow rate of lter, check pump performance.
Ineffective cleaning, check conditions, replace lter cartridge.
High Pressure on
Start Up
Small eyeball tting in Pool/ Spa.
Partially closed valve on return line.
Too large of pump, check selection.
Dirt Returns to Pool Hole in lter cartridge, replace lter cartridge.
Worn “o”-ring seal inside lter, replace o-ring.
2. Open the air release valve and open the purge vale to allow water to ow out of the
MultiCyclone Plus.
3. Remove any drain plugs from the pump.
4. Drain water from the pipe work.
MultiCyclone Plus

I pg 10
It is suggested that you should periodically remove the lter cartridge and soak it over night in
a suitable cartridge cleaning compound. This will remove any debris not removed by hosing
down of the lter cartridge.
Some swimming pool stores offer a lter cartridge cleaning service using the correct solutions
otherwise you may wish to use Waterco Cartridge cleaning solution. Directions of use are on
the product.
The cleaning time depends upon the swimming pool condition and use. Intervals between
cleaning the element should not exceed a period of 12 months in any instance.
GENERAL MAINTENANCE GUIDE
To ensure the maximum life of the MultiCyclone Plus, please follow the procedures below:
1. Clean the lter cartridge regularly according to the instructions set under “MultiCyclone Filter
Cartridge”
2. Maintain a correct chemical balance of your pool / spa water. The chemical balance of water
is a relationship between its pH, total alkalinity, calcium hardness and water temperature.
The water must be maintained at all times to the following:
PH LEVEL : BETWEEN 7.2 & 7.8.
TOTAL ALKALINITY : BETWEEN 80 & 150ppm.
CALCIUM HARDNESS : BETWEEN 150 & 300ppm.
Also, within these tolerances be balanced to the Langelier Saturation Index within a range of
-0.2 to +0.2.
Note: Testing kits are available to test the water yourself or alternately bring a sample of the
water to a professional pool and spa shop.
3. Mains water and rural water supplies need to be monitored. Saturation (life) in mains water
or bore (rural) will vary depending on water quality.
4. To prevent damage to the pump and lter and for proper operation of the system, clean
pump strainer and skimmer baskets regularly.
5. Replace the pressure gauge if faulty readings are observed.
WINTERISING
Proper winterising procedures should always be taken in order to protect your lter in cold
climates (temperatures below freezing point).
1. Switch off the Pump / Close the inlet valve.
TROUBLESHOOTING GUIDE
WARRANTY
MultiCyclone Plus is covered by a 2 year warranty and 1 year warranty on labour. Commercial
installations are covered by a 1 year warranty.
Please refer to Waterco’s warranty terms and conditions.
Symptoms Possible Problems / Solutions
Water Is Not Clear
Insufcient disinfectant level.
Incorrect pool chemistry.
Heavy bathing and/ or dirt loads.
Incorrect ow.
Insufcient running times. (Increase pump run time.)
Filter is dirty. (Clean per instructions.)
Hole in lter element.
Air leak on suction line
Pump impeller vanes blocked
Other restrictions include (pool suction cleaners) resistance from other inline
equipment such as strainers.
Pump not primed.
Low Water Flow
Check strainer baskets for debris.
Check for air leaks on suction side.
Check for restrictions or blockage in either suction or return lines.
Filter needs to be cleaned or replaced.
Pool water level too low.
Pump not primed.
Pump impeller vanes blocked.
Strainer baskets not being used and/ or not being cleaned regularly.
Pump operating under speed (low voltage).
Short Filter Cycles
Presence of algae, check disinfectant content.
Check pH and total alkalinity.
Pump output exceeds design ow rate of lter, check pump performance.
Ineffective cleaning, check conditions, replace lter cartridge.
High Pressure on
Start Up
Small eyeball tting in Pool/ Spa.
Partially closed valve on return line.
Too large of pump, check selection.
Dirt Returns to Pool Hole in lter cartridge, replace lter cartridge.
Worn “o”-ring seal inside lter, replace o-ring.
2. Open the air release valve and open the purge vale to allow water to ow out of the
MultiCyclone Plus.
3. Remove any drain plugs from the pump.
4. Drain water from the pipe work.
MultiCyclone Plus
Table of contents
Other Waterco Swimming Pool Filter manuals
Popular Swimming Pool Filter manuals by other brands

JNS Aquaria
JNS Aquaria ConeS CO Series quick start guide

Pentair Pool Products
Pentair Pool Products D.E. Cartridge Style Filter Quad D.E. Installation and user guide

Hayward
Hayward AquaRite S3 Series owner's manual

Zodiac
Zodiac Nature2 Express owner's manual

TIP
TIP SBS 36 Translation of original operating instructions

JNS Aquaria
JNS Aquaria VS-2 installation guide

ubbink
ubbink Pool Filter 300 manual

XtremepowerUS
XtremepowerUS 90151 Owner's manual and safety instructions

Skimz
Skimz HANGON H-SERIES Quick installation guide

Lectranator Systems
Lectranator Systems 360 Installation & operation manual

Pentair Pool Products
Pentair Pool Products Tagelus datasheet

Bestway
Bestway P6818 quick guide