Watts TekmarNet 4 User manual

Introduction
The tekmarNet®4 Gateway 482 provides RS 232 serial communication between tekmarNet®Thermostats and third party
automation systems. The third party automation system is able to monitor and adjust the thermostat’s heating, cooling, and
ventilation fan settings. Through the use of third party device drivers written for this product, tekmarNet®systems are fully
integrated into home automation systems.
Features
Installation, Operation and Maintenance Manual
tekmarNet®4 Gateway 482
IOM-T-482
• tekmarNet®4 and tekmarNet®2 Compatible
• CSA C US approved for US and Canada
• Drivers available for these third party automation systems*:
AMX, Clare Controls, Control4, Crestron®, Elan, RTI, Savant,
URC and Vantage home automation systems
*Trademarks are the property of their respective third party.
WARNING
!
Please read carefully before proceeding with
installation. Your failure to follow any attached
instructions or operating parameters may lead to the
product’s failure.
Keep this Manual for future reference.

2IOM-T-482 2125 © 2021 Watts
Wiring ...........................................2
Wiring Symbols ..................................2
Choosing a Location ..............................2
Mounting .......................................3
Electrical Drawings .............................3-7
Wiring the tN4 Gateway ............................8
Cleaning .......................................8
Troubleshooting the Wiring..........................9
Testing the Control ................................9
Sequence of Operation .............................10
Before You Start.................................10
Compatible Equipment ...........................10
Compatible Home Automation Systems...............10
Reporting Enable DIP Switch.........................10
LED Status Indicators ............................10
tekmarNet®Home Automation Protocol...............10
Home Automation Commands......................11
Thermostat Addressing .............................11
Technical Data ....................................12
Limited Warranty ..................................12
Do not apply power to these terminals.
Serious control damage will result. Earth ground
The location of the tN4 Gateway is important. To ensure proper wiring during rough in, select an appropriate location for
the control early in the construction process. Consider the following:
• Do not expose the tN4 Gateway to temperatures beyond
32 to 122°F (0 to 50°C).
• Keep dry. Avoid potential leakage onto the control.
• Relative humidity ≤ 92% to 104°F (40°C), down to 50%
above 104°F (40°C).
• Provide adequate ventilation.
• Keep away from equipment, appliances or other sources
of electrical interference.
• Mount the enclosure to a solid backing.
• Provide easy access for wiring and viewing.
• Mount approximately 5 feet (1.5 m) off the finished floor.
• Mount near the zone managers, reset modules, tN4
thermostats, tN4 setpoint controls, and mixing expan-
sion modules. The total wire length of each tN4 bus
cannot exceed 5000 feet.
• Each tN4 bus consists of a pair of wires (tN4 and C).
• The tN4 Gateway can accept up to 5 tN4 buses.
• Use a Category 5 cable up to or less than 150 feet
(45 m) in length to connect the tN4 Gateway to the
home automation equipment.
To avoid serious personal injury and damage to the equipment:
• Improper installation and operation of this control could
result in damage to the equipment and possibly even
personal injury or death.
• This electronic control is not intended for use as a
primary limit control. Other controls that are intended
and certified as safety limits must be placed into the
control circuit.
• Do not attempt to service the control. Apart from any
field replaceable fuse(s) there are no user serviceable
parts. Attempting to do so voids warranty.
It is your responsibility to ensure that this control is safely installed according to all applicable codes and
standards. tekmar is not responsible for damages resulting from improper installation and/or maintenance.
• Read Manual and all product labels BEFORE
using the equipment. Do not use unless you
know the safe and proper operation of this
equipment.
• Keep this Manual available for easy access
by all users.
• Replacement Manuals are available at
tekmarControls.com
• Disconnect all power before opening the control.
• It is the installers responsibility to ensure that
this control is safely installed according to all
applicable codes and standards.
Table of Contents
Important Safety Information
Wiring Symbols
Wiring
Choosing a Location

3
IOM-T-482 2125 © 2021 Watts
The electrical drawing examples on the following
pages show the 482 in common applications. These
drawings have a brief explanation of what is being operat-
ed in each system. Choose the components in your sys-
tem and use the drawings as a guide to aid in wiring your
system. These are only concept drawings, not engineered
drawings. They are not intended to describe a complete
system nor any particular system. It is up to the system
designer to determine the necessary components for
and configuration of the particular system being designed
including additional equipment, isolation relays (for loads
greater than the controls specified output ratings) and any
safety devices, which in the judgment of the designer are
appropriate in order to properly size, configure and design
that system and to ensure compliance with building and
safety code requirements.
The control can be mounted on a
standard DIN rail. First remove the
control from its base and then,
using the hooks and spring clip
on the back of the control, mount
it onto the DIN rail. This will be a
popular option for those who pre-
fer to mount the control inside a
larger electrical panel.
The wiring can enter the bottom
or the back of the enclosure.
Knock-outs provided in the base
allow the wiring to be run in
conduit up to the enclosure. The
base also has holes that line up
with the mounting holes of most
common electrical boxes.
Press down at the fingertip grips
on top of the front cover and pull
out and down.
Lift the front cover up and away
from the control.
Loosen the screws at the front
of the wiring cover.
The wiring cover pulls straight out
from the wiring chamber.
The base is ready for mounting.The control lifts up and away
from the base.
Press the control release clip
on the base inside the wiring
chamber and slide the control
upwards.
Remove the safety dividers
from the wiring chamber by
pulling them straight out of
their grooves.
There are 10 conduit knock-outs at the
back and bottom of the wiring chamber.
13 Mounting holes
Control
release
clip
Control release clip
• One tN4 Gateway 482
• One RJ45 to DB9 Adapter
• One Installation and Operation Manual IOM-T-482
• One Job Record 482_J
• One Plastic Bag for Brochures
• One Screwdriver
Mounting
Electrical Drawings
Included Parts

4IOM-T-482 2125 © 2021 Watts
tN2
CR
tN2
tN4
Rh WS1S2Com
No Power
tN2
CR
tN2
tN4
Rh WS1S2Com
No Power
L
G
N
Category 5 Cable (< 150 feet, 45 m)
2
tN4 Gateway 482
RS 232
Test
Power: 115 V ±10% 60 Hz 45 mA
Designed and assembled in Canada by
tekmar Control Systems Ltd.
tektra 1017-02
tN4 Bus 0
tN4 Bus 1
tN4 Bus 2
tN4 Bus 3
tN4 Bus 4
Power
Date Code
not testing
testing
testing paused
off
red
red
Caution: Signal wiring must be rated at least 300 V.
H2051A
Power
L
1
N
5
C1
1
6
tN4
3
C0
0
4
tN4
7
C2
2
8
tN4
9
C3
3
10
tN4
11
C4
4
12
tN4
Do not apply power RS 232
Tx
Rx
To RS 232 Serial Port
Adapter
1
Reporting Enable
Power-On State
Off
On
Description: tN4 network of tekmarNet®thermostats are connected to a tN4 Gateway 482.
Refer to Thermostat wiring brochures for complete wiring schematic.
There is a limit of 24 devices per tN4 bus. Additional thermostats can be wired to the next available bus up to a
maximum of 96 devices per system.
Electrical Application 482 E1

5
IOM-T-482 2125 © 2021 Watts
Description: A Universal Reset Module 422 and Duel Zone Manager 337 are connected to a tN4 Gateway 482.
Refer to W 422 and W 337 wiring brochures for complete wiring schematic.
Electrical Application 482 E2

6IOM-T-482 2125 © 2021 Watts
Electrical Application 482 E3
Description: A Universal Reset Module 423 and Power Manager 345 are connected to a tN4 Gateway 482.
Refer to W423 and W345 wiring brochures for complete wiring schematics.

7
IOM-T-482 2125 © 2021 Watts
Description: A tN2 House Control 402 is connected to a tN4 Gateway 482.
Refer to the 402 Installation & Operation Manual for a complete wiring schematic.
Electrical Application 482 E4

8IOM-T-482 2125 © 2021 Watts
This section explains how to wire individual devices to the
tN4 Gateway. For step-by-step wiring, refer to the terminal
number on the right of the page.
• Before wiring ensure all power is turned off and take all
necessary precautions.
• Install the supplied wiring compartment barriers by sliding
them into the grooves provided to isolate the low and
high voltage wiring.
• Refer to the current and voltage ratings at the back of
this brochure before connecting devices to this control.
• All wires must be rated at least 300 V.
• High voltage wires should be 14 AWG conductors.
• Low voltage wires should be 18 AWG conductors.
• Strip all wiring to a length of 3⁄8in. or 10 mm for
all terminals.
• Only qualified personnel should attempt installation of
the tN4 Gateway.
• Provide a 15 A circuit for the power.
• An approved circuit breaker or power disconnect that
de-energizes the high voltage wiring should be located
near the tN4 Gateway, and marked as the 115 V (ac)
power disconnect for this device.
• 115 V (ac) high voltage power supply circuits must be
protected by 15 A maximum overcurrent protection.
• Connect 115 V (ac) hot (L) to terminal 2.
• Connect 115 V (ac) neutral (N) to terminal 1.
• Connect the ground wire to one of the ground screws
provided in the wiring chamber.
The tN4 Gateway includes five tN4 buses:
• tN4 Bus 0 (terminals 3 and 4)
• tN4 Bus 1 (terminals 5 and 6)
• tN4 Bus 2 (terminals 7 and 8)
• tN4 Bus 3 (terminals 9 and 10)
• tN4 Bus 4 (terminals 11 and 12)
Each tN4 bus consists of a tN4 terminal as well as a
C terminal.
Polarity is important.
Connect each tN4 bus on the system to a tN4 bus input
on the 482. The tN4 bus order on the 482 is not critical;
however, it is recommended to connect them to the
482 in the same order in order to avoid confusion during
troubleshooting.
3 4
0
C0 tN4
C tN4
The 482 exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping the
device. Do not use solvents or cleaning solutions.
12
Power
N L
115 V (ac)
Ground screw
Use a Category 5 cable with an RJ45 connector and plug
it into the 482 RS 232 serial port. Connect the opposing
end RJ45 connector into the RJ45 to DB9 adapter.
The adapter uses the following pin connections:
• Pin 3 - Data Terminal Ready (firmware programming only)
• Pin 4 - Signal Ground
• Pin 5 - Receive Data
• Pin 6 - Transmit Data
Top
View
1 8
Front
View
8 1
tN4 Bus Inputs Terminals 3 - 12
Power Requirements Terminals 1-2
Wiring the tN4 Gateway Terminals 1-12
RS 232 Serial Port
Cleaning

9
IOM-T-482 2125 © 2021 Watts
The following tests are to be performed using standard
testing practices and procedures and should only be car-
ried out by properly trained and experienced persons.
A good quality electrical test meter, capable of reading
from at least 0-300 V (ac), 0-30 V (dc), 0-2,000,000
Ohms, and testing for continuity is essential to properly
test the wiring and sensors.
Test Meter
Control Terminals
Testing the Power
1. Remove the front and wiring covers from the control.
2. Use an electrical test meter to measure (ac) voltage
between the Power N and L terminals (1 and 2). The
reading should be 115 V (ac) + / – 10%. The Power
LED should be on.
3. If power is not present the Power LED will be off.
Check the circuit(s) that supply power to the Power
N and L terminals (1 and 2).
Testing the tN4 Buses
1. Remove the front and wiring covers from the control.
2. There are a total of five tN4 buses (tN4 and C).
The corresponding tN4 LED will be on if there is
communication on the tN4 bus.
3. If there is no communication on a tN4 bus that is
supposed to have communication, there may an
open or short circuit. An open or short circuit will be
indicated as a bus error on any tN4 thermostats, tN4
setpoint controls, and tN4 system controls.
4. To test for short circuits:
• Disconnect the tN4 bus wires on both ends.
• Install wire nuts on each wire on one end to ensure
the wire ends are not touching.
• Measure for continuity using an electrical meter.
• If continuity is present, there is a short circuit fault
along the wires. It is recommended to replace the
tN4 bus wires.
5. To test for open circuits:
• Disconnect the tN4 bus wires on one end and
connect them together.
• Disconnect the tN4 bus wires on the other end.
• Use an electrical meter to measure for continuity.
• If there is no continuity, there is an open circuit fault
along the wires. It is recommended to replace the
tN4 bus wires.
Testing the RS 232 Serial Port
A terminal shell called Termite can be used to test the RS
232 serial port hexadecimal data.
Step 1: Download the Termite (complete setup) terminal
program for Windows.
http://www.compuphase.com/software_termite.htm
Step 2: Settings
Baud rate = 9600, Data bits = 8, Stop bits = 1,
Parity = none, Flow control = none, Forward = none
Hex View = check marked
Step 3: Enter commands
Hexadecimal values can be entered in the command line
at the bottom. The hexadecimal numbers must be entered
in the format 0x00 followed by a space.
The 482 includes a built-in test routine that transmits a
message via the RS232 port. The result of this is that the
Tx indicator will flash as the message is sent.
Start the test routine by pressing the Test button for
1 second. The Test LED turns red.
The RS232 message includes the following:
1. FirmwareRevision
0xca 0x07 0x06 0x02 0x87 0x01 0x00 0x00 0x91 0x00
0x28 0x35
This means that the 482 firmware version is 6c hexadecimal
or 145 in decimal.
2. ProtocolVersion
0xca 0x07 0x06 0x02 0x8f 0x01 0x00 0x00 0x02 0x00
0xa1 0x35
The means that the 482 protocol version is 02.
The 482 then exits the test routine and resumes normal
operation.
Troubleshooting the Wiring
General
Testing the Control

10 IOM-T-482 2125 © 2021 Watts
Before connecting the tN4 Gateway to a tekmarNet®
system, it is recommended that the system be fully com-
pleted, with no tekmarNet®thermostats being added or
removed at a later date. Also, each tekmarNet® thermostat
is automatically assigned a tekmarNet®address when con-
nected to the system. When using a Gateway, each device
requires a manual address. This address should be written
down together with the room location for future reference
using the Job Record J 482 and will be required in order to
name the room on the home automation equipment.
The tN4 Gateway 482 can communicate and control the
following tekmar products:
• tekmarNet®Setpoint Control 161, 162
• tekmarNet®Thermostat 532, 552, 553, 554, 557
• Snow Melting Control 654, 670, 671
The 482 is compatible with the following boiler controls but
does not communicate with them:
• Boiler Control 274, 274, 284
• House Control 400, 401, 402, 403, 406
• Reset Module 420, 421, 422, 423
The 482 is compatible with the following discontinued
products:
• tekmarNet®2 Thermostat 527, 528, 529, 530
•
tekmarNet®4 Thermostat 537, 538, 540, 541, 542,
543*, 544, 545, 546
*543 software versions J1126A to J1126I are not fully
compatible with the 482. Please contact your tekmar sales
representative for assistance with affected 543 products.
The tN4 Gateway 482 is not compatible with the tN4
Gateway 485 or 486. Two tN4 Gateway products cannot
be installed on the same heating system.
LEDS ON OFF
Power Power is on. Power is off.
Tx Flashes when RS232 message is sent. No RS232 message.
Rx Flashes when RS232 message is received. No RS232 message.
tN4 Bus 0 tN4 communication on bus 0 (b) is present. No tN4 communication on bus 0.
tN4 Bus 1 tN4 communication on bus 1 is present. No tN4 communication on bus 1.
tN4 Bus 2 tN4 communication on bus 2 is present. No tN4 communication on bus 2.
tN4 Bus 3 tN4 communication on bus 3 is present. No tN4 communication on bus 3.
tN4 Bus 4 tN4 communication on bus 4 is present. No tN4 communication on bus 4.
The 482 supports an option to automatically report thermostat
information once every minute. The Reporting Enable Power
On State DIP switch selects if Reporting Enable is normally
on or normally off when powered on. Most home automation
systems require the reporting enable to be set to on. Older
home automation equipment may require this to be set to off.
The following home automation systems* have software
drivers for the 482:
AMX Control4 Savant
Clare Controls Elan URC
Crestron RTI Vantage
The software drivers are available through the home
automation company.
Refer to the 482 product page on tekmar’s website
http://tekmarcontrols.com/accessories/482.html for an up
to date list of compatible home automation systems.
*Trademarks are the property of their respective automation company.
The tekmarNet®Home Automation protocol documentation is available on the tekmar website at:
https://www.watts.com/our-story/brands/tekmar/tha
Before You Start
Sequence of Operation
Compatible Equipment
tekmarNet®Home Automation Protocol
Compatible Home Automation Systems
Reporting Enable DIP Switch
LED Status Indicators

11
IOM-T-482 2125 © 2021 Watts
Each thermostat and setpoint control uses the following
format for addressing: Port:Bus:Thermostat Device.
The snow melting control does not reports its address to
the 482. The Bus and Thermostat Device are visible on
the thermostat and setpoint control’s LCD display. This is
documented as the ‘tekmarNet Address’ in the thermostat
data brochure.
Port Number
The leading digit is the Port number. This determined by
the wiring connection that the thermostat is wired to on
the 482.
482 tN4 Bus 0 or b = 0 482 tN4 Bus 3 = 3
482 tN4 Bus 1 = 1 482 tN4 Bus 4 = 4
482 tN4 Bus 2 = 2
Bus Number
The second digit is the thermostat bus number. The bus
number is pre-determined by the wiring of the thermostat
to a boiler or mixing reset control water temperature bus.
In the event that no reset control is installed, the bus
number is 0.
The 406 tN4 bus numbering is dependent on the
WaterTemp and the Zone settings when configuring
the control.
WATERTEMP ZONES TANK BUS MIX BUS BOILER BUS
T — 1 —
T + M — 1 2 —
T + B — 1 — 2
T + MB Mix 1 * 3
T + MB Boil 1 2 *
*When the 406 is configured in this manner, thermostats on
this bus are unable to communicate to the Gateway 482.
Thermostat Device Number
The third and fourth digits indicate the thermostat device
number. The thermostat device number is a two digit
number that ranges from 01 to 24 and can be determined
from the thermostat address. To determine the thermostat
address, please consult the data brochure for the
appropriate thermostat.
Example 1
A thermostat with bus and thermostat device number of
b:01 is wired to a model 400 controller boiler bus and in
turn is wired to the 482 on port 0. This address is 0101.
Example 2
A thermostat with bus and thermostat device number of
b:24 is wired to a model 423 controller boiler bus and in
turn is wired to the 482 on port 0. This address is 0424.
Example 3
A group of thermostats are wired together to create a
stand-alone network. A thermostat with thermostat device
number 15 is wired to the 482 on port 0. This address
is 0015.
CONTROL BUS BUS #
274 Boiler 1
275 Boiler 1
284 b 1
284 1 2
284 2 3
284 3 4
400 Boiler 1
401 Boiler 1
402 Mix 1
402 Boiler 2
403 Mix 1
CONTROL BUS BUS #
403 Boiler 2
420 Boiler 1
421 Mix 1
422 Mix1 1
422 Boiler 2
422 Mix2 2
423 Bus1 1
423 Bus2 2
423 Bus3 3
423 Boiler 4
THERMOSTAT (HEAT ONLY) THERMOSTAT (HEAT-COOL) SETPOINT CONTROLS SNOW MELT
COMMAND 532 552 553 554 557 161 162 654 670 671
Room temperature •••••••
Floor temperature*** •••••
Mode •••••
Heat setpoint •••••
Cool setpoint •••
Slab setpoint* •••••
Setpoint control setpoint • •
Fan •••
Relative humidity% • •
Maximum humidity setpoint • •
Minimum humidity setpoint • •
Outdoor temperature** ••••• •••
Melt/storm/setpoint enable •••••
* Not supported by some home automation drivers
** Requires an outdoor sensor to be connected to a thermostat, snow melt or boiler control
*** Floor temperature available when a floor sensor is installed to an auxiliary sensor input
Home Automation Commands
Thermostat Addressing

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
The installer must ensure that this control and its wiring are isolated and / or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies
with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio
or television reception, which is determined by turning the control off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna,
relocating the receiver with respect to this control, and / or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
tN4 Gateway 482; RS 232
Literature Submittal, Installation and Operating Manual, Job Record
Control Microprocessor PID control; This is not a safety (limit) control
Packaged weight 3.6 lb. (1600 g)
Dimensions 65⁄8" H x 7 9⁄16" W x 2 13⁄16" D (170 x 193 x 72 mm)
Enclosure Enclosure A, blue PVC plastic, NEMA type 1
Approvals CSA C US, meets ICES & FCC regulations for EMI / RFI
Ambient conditions Indoor use only, 32 to 122°F (0 to 50°C), RH ≤ 92% to 104°F (40°C), down to 50% above 104°F (40°C), 9842 feet (3000 m) maximum altitude
Power Supply 115 V ± 10%, 60 Hz, 45 mA
Limited Warranty The liability of tekmar under this warranty is
limited. The Purchaser, by taking receipt of any tekmar product
(“Product”), acknowledges the terms of the Limited Warranty in
effect at the time of such Product sale and acknowledges that it
has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products
sold hereunder is a manufacturer’s pass-through warranty which
the Purchaser is authorized to pass through to its customers.
Under the Limited Warranty, each tekmar Product is warranted
against defects in workmanship and materials if the Product is
installed and used in compliance with tekmar’s instructions, ordi-
nary wear and tear excepted. The pass-through warranty period
is for a period of twenty-four (24) months from the production
date if the Product is not installed during that period, or twelve
(12) months from the documented date of installation if installed
within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at
tekmar’s sole discretion: the cost of parts and labor provided by tekmar
to repair defects in materials and/ or workmanship of the defective prod-
uct; or to the exchange of the defective product for a warranty replace-
ment product; or to the granting of credit limited to the original cost of
the defective product, and such repair, exchange or credit shall be the
sole remedy available from tekmar, and, without limiting the foregoing
in any way, tekmar is not responsible, in contract, tort or strict product
liability, for any other losses, costs, expenses, inconveniences, or dam-
ages, whether direct, indirect, special, secondary, incidental or conse-
quential, arising from ownership or use of the product, or from defects in
workmanship or materials, including any liability for fundamental breach
of contract.
The pass-through Limited Warranty applies only to those defective
Products returned to tekmar during the warranty period. This Limited
Warranty does not cover the cost of the parts or labor to remove or
transport the defective Product, or to reinstall the repaired or replace-
ment Product, all such costs and expenses being subject to Purchaser’s
agreement and warranty with its customers.
Any representations or warranties about the Products made by
Purchaser to its customers which are different from or in excess of the
tekmar Limited Warranty are the Purchaser’s sole responsibility and obli-
gation. Purchaser shall indemnify and hold tekmar harmless from and
against any and all claims, liabilities and damages of any kind or nature
which arise out of or are related to any such representations or warran-
ties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned
Product has been damaged by negligence by persons other than
tekmar, accident, fire, Act of God, abuse or misuse; or has been dam-
aged by modifications, alterations or attachments made subsequent to
purchase which have not been authorized by tekmar; or if the Product
was not installed in compliance with tekmar’s instructions and /or the
local codes and ordinances; or if due to defective installation of the
Product; or if the Product was not used in compliance with tekmar’s
instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS
OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO
CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE
PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS
OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION
OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY
LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL
NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE
PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS
ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed
to have defects in workmanship or materials must be returned, together
with a written description of the defect, to the tekmar Representative
assigned to the territory in which such Product is located. If tekmar
receives an inquiry from someone other than a tekmar Representative,
including an inquiry from Purchaser (if not a tekmar Representative) or
Purchaser’s customers, regarding a potential warranty claim, tekmar’s
sole obligation shall be to provide the address and other contact infor-
mation regarding the appropriate Representative.
All specifications are subject to change without notice
Tel: 1-800-438-3903 • Fax: (250) 984-0815
tekmarControls.com
IOM-T-482 2125 © 2021 Watts
Technical Data
Limited Warranty and Product Return Procedure
Table of contents
Other Watts Gateway manuals