Weltem AmeriCool WPC-23000 User manual

1
Owner’s Manual
WPC-15000
Please read and save these instructions. Read carefully before attempting to assemble, install, oper-
ate or maintain the product described.
Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and / or property damage! Retain instructions for future reference.
AmeriCool by Weltem Portable Air Condioners feature spot cool-
ing for large areas where cooling of the enre area is not praccal.
A dedicated spot cooling thermostat controls the unit in this ap-
plicaon. These air condioners can also be used in smaller areas
for room cooling.
A control panel provides ease of use and contains a self-diagnosc
funcon and display, showing operang modes, room and set
temperatures, and faults. If an abnormal operaon occurs, a visual
display of the fault is shown. Caster wheels are included for easy
portability. Suitable applicaons include: a factory or work place,
industrial kitchen, computer room, emergency cooling, etc.
Aer unpacking the unit, carefully inspect unit for any damage that may have occurred during
transit. Check for any loose, missing, or damaged parts.
Descripon
Unpacking
WPC-23000
Figure 1
Owner’s Manual
Specicaons
WPC-23000
Portable Air Conditioners
by
Model No. Power Supply Ph-V-Hz Cooling
Capacity Btu/h
Power Consump-
on Was
EER Btu/
Wh
Rated Cur-
rent Amps
WPC-23000 3 phases, 460V, 60Hz 92,000 10,500 8.8 16.5
Model No. Nema Plug Power Cord
Gauge AWG
Power Cord
Length
Dimensions
W x D x H - in. (mm)
WPC-23000 Terminal type 10 10 28.9 x 51.6 x 59.8
(735 x 1,310 x 1,520)
Model No. Weight (Net / Gross) Lbs(kg) No. of Cool Air
Outlets Pcs
Condensate tank
Gallons(Liters)
Ambient temperature
range °F( °C)
WPC-23000 761/793 (345/360) 3Auto Pump
Included 64~113(18~45)

2 3
Owner’s Manual
WPC-23000
Specicaons (Connued)
General Safety Informaon
Please read this manual carefully for instrucons on correct installaon and usage. Please read
all safeguards.
1. Transport and store the unit in an upright posion only. Leave unit in an upright posion for at
least 3 hours before rst use.
2. Always place the unit on an even, level surface.
3. Ensure the unit is connected to a grounded power supply of the correct rang / capacity.
4. The unit will cool when the room temperature is between 18°C (64.4°F) ~ 45°C(113°F) depend-
ing on the thermostat seng.
5. DO NOT use this unit for funcons other than those described in this instrucon manual.
6. DO NOT lt the unit.
7. DO NOT cover or obstruct the unit’s inlet and outlet grilles.
8. DO NOT use the unit in areas where it will be exposed to rain or water.
9. NEVER unplug the unit while it is operang.
Model No. Seng temperature
(Room cool mode) °F( °C)
Seng temperature
(Spot cool mode) °F( °C)
WPC-23000 64~86 (18~30) 32~86 (0~30)
Model No. Applicaon Area
(Room cool mode) ²(m²)
Refrigerant
Type / oz(g)
Design Pressure - Hi/
Low Psig
WPC-23000 2,637 (245) R-410A
/ 141 (4,000) 450 / 250
Model No. Indoor Air Flow
CFM(CMM)
Wheels
pcs / diameter
Hot Air Duct Di-
ameter In.(mm)
Maximum Exhaust
Duct Lenght (m)
WPC-23000 2,890 (48) 4 / 127mm 20 (500) 100 (30)
Safety Devices
Compressor overload protector, An-freezing thermister,
Full drain tank switch, Automac restart (Power inter-
rupon), Compressor me delay program, High pressure
switch
Features Temperature control, Self-diagnosc funcon, Drain
pump included, Washable lters, °F( °C) display, O-mer

3
Owner’s Manual
WPC-23000
10. DO NOT place any foreign objects on the unit.
11. DO NOT operate the unit with wet or damp hands.
12. DO NOT allow chemical substances to come into contact with the unit.
13. DO NOT operate the unit in the presence of ammable substances or vapors such as alcohols,
pescides, gasoline, etc.
14. DO NOT use the plug to start and to stop the unit. Always use the control panel to start and
to stop the unit.
15. Always turn o the unit when it is not in use and unplug the power plug from the electrical
outlet.
16. Always turn the unit o and unplug the main power plug from the electrical outlet before
cleaning, moving or performing maintenance.
17. AVOID the use of adapter plugs or extension cords. If it is necessary to use an extension cord
or an adapter plug to operate the unit, ensure that they are correctly rated for the applica-
on. Consult a local qualied lectrician and all local electrical codes to ensure proper setup.
Any extension cord used with this device must be rated for a minimum of 22A.
18. DO NOT unplug the unit by pulling on the electrical cord. Keep electrical cord away from heat
sources and always completely unroll the cord to avoid overheang. If the power cord be-
comes damaged, a qualied service agent, qualied electrician, or similarly qualied person
must replace it, in order to avoid a hazard or shock.
19. The lters must be used with the product at all mes. When the lters are removed for clean-
ing, always ensure that the unit has been turned o and unplugged from the electrical outlet.
20. Regularly clean the lters to maintain eciency. If the lters are not cleaned regularly, the
units output performance and eciency will decline and energy consumpon will increase.
21. DO NOT operate the unit with a damaged power cord or plug, aer it malfuncons, has been
dropped or damaged.
22. Only use in the upright posion on an even, at surface. Unit must be posioned at least 24
inches (60 cm) from the nearest object in any direcon.
23. Stop operaon immediately if abnormal noise or odor is noced. Contact a local service
center.
24. Appliance is not to used by children or persons with reduced physical, sensory or mental
capabilies, or lack of experience and knowledge, unless they have been given supervision or
instrucon.
25. Children being supervised not to play with appliance.
26. That the appliance shall be installed in accordance with naonal wiring regulaons.
27. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualied persons in order to avoid a hazard.
SAVE THESE INSTRUCTIONS
DO NOT use the unit in wet environments, such as a laundry room, to avoid
the risk of electrical shock.
DO NOT operate the unit in explosive or ammable environments.
DO NOT operate a unit with a damaged power cord.

4 5
Owner’s Manual
WPC-23000
Assembly
COMPONENT PARTS
Front and Right Side View
Condenser / filter
Figure 3
Figure 2
Back and Le Side View
Caster
Electrical access panel
Drain pump hose connector
Handle
Cool air outlet
Display / Control board
Top fan exhaust flange
Evaporator / filter
Condenser / filter
Drain pump included
Figure 8
Figure 7
Figure 4 Figure 5
Figure 6
1. Remove cool air outlet hose(s) from
carton.
2. Place the cool air outlet hose(s) on
the front top of air condioner.
3. Use screws (enclosed inside of box
with cool air outlet hose(s) to install
the cool air outlet hose(s)
on the air condioner as shown in
Figure 5.
1. Take out the cord holder
from the accessory box.
2. Place the cord holder on
the back side of air condioner.
3. Use screws (enclosed inside of
accessory box ith cord
holder)to install the cord
holder on the air condioner
as shown in Figure 4.
TOP FAN EXHAUST FLANGE
1. Remove the top fan exhaust flange from carton.
2. Place the top fan exhaust flange on the top of air
condioner.
3. Use screws (enclosed inside of box with the top fan
exhaust flange) to install the top fan exhaust flange on air
condioner as shown in Figure 6.
HANPLE
1. Remove a handle from carton.
2. Place the handle on upper side of rear panel.
3. Use screws (enclosed inside of box with a handle)
to install the handle as shown in Figure 7.
POWER CORD HOLDER
DISCHARGE DUCTS
/SUPPLY AIR DUCT
A condenser plenum can be purchased separately. condenser plenum
fits over the condenser to duct condenser air to the unit to improve
cooling efficiency.
1. Remove the Filter("A")
2. Check the Filter("C") is inserted properly in condenser plenum("B")
3. Install "B" which contains "C" by using driver with enclosed
bolts(6EA) as Figure 8.
CONDENSER PLENUM
(Oponal)
A
B
C

5
Owner’s Manual
WPC-23000
Installaon
MOVING THE UNIT
PLUGGING IN THE UNIT
Unlock the casters and push the unit using the side handles to a at, level surface and set the
caster brakes to the locked posion.
Check the prongs and surface of the power cord plug for dust/dirt. If dust and/or dirt are pres-
ent, wipe o with a clean, dry cloth.
Check the power cord, plug and prongs for damage or excess play.
If any damage or excess play is found, contact a qualied repair technician or a qualied electri-
cian to perform replacement or repair of the power cord, plug or prongs.
NOTE: Make sure the AC outlet is free of dirt, dust, oil, water, or any other foreign material.
WARNINGS REGARDING PROPER LOCATION FOR INSTALLATION
Do not use the unit in explosive environments or in areas where ammable
gas leakage may occur.
Do not use the unit in areas where it will be exposed to rain or water.
Do not use the unit in a corrosive atmosphere.
Do not use the unit above 18°C(64°F) ~ 45°C(113°F).
Do not install the unit on uneven or sloping surface. The unit may roll or
topple over even if the casters are set to the locked posion.
If the power cord or plug is damaged, repair should only be performed by
qualied electrical personnel.
Do not connect / disconnect the power cord or aempt to operate buons
with wet hands. This could result in electrical shock.
Only operate in the upright posion on a at level surface, at least 60cm(24inches)
from any objects. (See Figure 8)
Figure 8

6 7
Owner’s Manual
WPC-23000
Operaon
CONTROL PANEL
1. POWER BUTTON: Acvates unit when POWER BUTTON is pressed. (Fan starts on low speed). If
power buon is pressed during operaon, unit stops.
2. BLOWER BUTTON: Changes fan speed from (Low) to (High) when pressed.
3. SPOT/COOL BUTTON: Acvates compressor and begins producing cool air 5 seconds aer but-
ton is pressed. Regulates temperature based on outlet cool air temperature.
4. ROOM/COOL BUTTON: Acvates compressor and produces cool air 5 seconds aer buon is
pressed. Regulates temperature based on inlet ambient air temperature.
5. SET TEMP BUTTONS: Change target temperature/data value by +/- 1. Change data value by +/-
10 by pressing connually. Press the SET TEMP BUTTONS to set temperature. Upper buon is
to heighten temperature and Lower buon is to lower temperture.
6. ALARM: Alarm indicator lights (blinks) and indicates abnormal system operaon. If Alarm oc-
curs, compressor stops. System operaon stops when ALARM light is acvated (blinks) longer
than 3 minutes.
7. CURRENT TEMP: Displays current room temperature in display in Fahrenheit. (In Room Cool
Mode only). SPOT/COOL Mode – Displays outlet (cool air) temperature during normal opera-
ons. In order to change °F to °C, press SPOT/COOL and ROOM/COOL buons together for 2
seconds. C will blink 2 mes and Figure will change to °C. ALARM codes blink and are displayed
when abnormal operaon occurs.
8. TARGET TEMP: displays the unit set temperature for ROOM/COOL mode only.
OFF-TIMER: Enter to Timer Seng Mode if you press BLOWER Buon and SPOT/COOL Buon
together for 1 seconds. Press UP/DOWN Buon to set the mer unl it shows the gure you
want to set. Aer 5 seconds, the gure will be memorized and the compressor will stop aer the
me set.
AUTO RESTART: If the unit goes o due to an electrical interrupon, the unit will automacally
restart when the power resumes.
1 2
5
3 4
6
87
Figure 9

7
Owner’s Manual
WPC-23000
Maintenance
FILTER CLEANING (See Figures 10 and 11)
There are three lters in the unit. The evaporator lter is located at the front of the unit. The
condenser lters are located at the side of the unit.
1. loosen up 2 bolts on the front lter guard.
2. Slide lter up and use a vacuum cleaner to remove the dust from the lter.
3. If the lter is heavily covered with dust and dirt, warm water and mild soap or neutral deter-
gent may be used to wash the lter. Do not use any other chemicals to clean lter, as they will
likely damage the lter.
4. Dry the lter in a shaded area before replacing it. Do not operate the unit without the lter
installed and the lter guard in the closed posion.
5. Replace the clean lter and close the lter guard.
6. To clean the condenser lters, li up on the side lters from the middle bar slightly and then
angle the lters outwards from the boom and remove.
7.Use the same cleaning procedure as above (3 – 5).
8. To replace the condenser lter, place the top of the lter in the guide and slide the lter up
unl the boom of the lter clears the frame. Then push the boom of lter into the guide
and let lter gently fall inside the guide.
NOTE: For eecve cooling clean the lter at least every 2 weeks.
– For your convenience, record the complete model number and product name (located on the
Product Idencaon Plate), the purchase date, purchase locaon, serial number, and warranty
period in the table below.
– Also, aach your purchase receipt as proof of purchase to this instrucon manual for future
reference.
– To ensure your product is covered by warranty, the complete faulty product along with your
original purchase receipt must be provided at the place of purchase.
Do not operate without the lter ed.
Do not operate the unit with a damaged cord or plug, aer the unit malfunc-
ons, or if the unit has been dropped or damaged.
– Loosen up 2 bolts on
the front filter guard.
– Slide filter up and use
a vacuum cleaner to remove
the dust from the filter.
– Remove dust from the filt
er
using a vacuum cleaner
hose aachment.
– If required wash the filter i
n
luk
ewarm water with a mild
detergent. Leave to dry in
a shaded area before
reinstalling.
Figure 10 – Removing Filters Figure 11 – Removal of Dust

8 9
Owner’s Manual
WPC-23000
Maintenance (Connued)
– To ensure your product is covered by warranty, the complete faulty product along with your
original purchase receipt must be provided at the place of purchase.
Product Portable Air Condioner
Model No.
Date of Purchase
Place of Purchase
Serial No.
Period of Warranty
Customer: Please read and keep this
manual for future reference and keep
sales receipt as proof of purchase.
SELF-DIAGNOSTIC CODES (See Table 1)
The alarm light is acvated if abnormal operaon occurs, and a code is displayed on the control
panel. The compressor and condenser fan motor will stop operang. The evaporator fan will con-
nue to run for 3 minutes. If the fault is reced within 3 minutes, the unit will resume opera-
on. If the fault persists for more than 3 minutes, the evaporator fan also stops. The fault must
be reced before the unit can resume normal operaon.

9
Owner’s Manual
WPC-23000
Frost prevenon
sensor and
Abnormal
temperature
sensor value
Refrigerant high
pressure switch
Abnormal
temperature
sensor value
Abnormal
temperature
sensor value
Evaporator motor
overload
(for wpc-23000)
Drain pump
alarm
Indoor heat exchanger
temperature too low
TH3 temperature sensor
has a loose or broken
connecon
Blocked air filter
Blocked / kinked exhaust
duct
Ambient temperature
is too high
TH1(Outlet) temperature
sensor has a loose or
broken connecon
TH2(Inlet) temperature
sensor has a loose or
broken connecon
Drain pump defecve or
improper hose connecon
(including kink or blockage)
Ambient temperature is
too high
Unstable voltage supply
Defecve compressor
Abnormal operaon of
evaporator motor
(for wpc-23000)
Abnormal operaon of
condenser motor
(for wpc-23000)
Do not use the air
condioner if ambient
temperature is lower than
18°C (64°F)
Contact a qualified service
agent
Clean air filter
Ensure exhaust duct is not
blocked / kinked
Do not use the air
condioner if ambient
temperature is higher than
45°C (113°F)
Contact a qualified service
agent
Contact a qualified service
agent
Do not use the air condioner
if ambient temperature is
higher than 45°C (113°F)
Contact a qualified service
agent
Replace compressor
Contact a qualified service
agent
Check the hose connecon
and hose
Replace drain pump
SELF-DIAGNOSTIC ALARM CODES
Alarm
Display ProblemCause Correcve Acon
Compressor
overload
Condenser motor
overload
(for wpc-23000)
愚決檺律
;ΠΕΖΝ ͽͲ΅ͶʹͲΆ΅ͺͿ
Ͳ΅Ϳ
͵Ͳ;ͶͺʹͽΈʹ
惾剳
岂憮斲決溎 Ω
惾剳殯Έʹ
洇殯微塾
沗昷 円皦 筛汾
朞洛斲穳
沲滎汆怺塶姷嵷滆惾畲嵦
汾曊愯憛樮廇汾曊
汾曊族旇籗族壊
祢彺熞庲岂惾嘪決砋瑚砋
汾曊匶渆壊彺愕昪凊洢击穊床
歾刃汞獞朞昦抏汆昦汆汾曊篊洎埮昦沊
ʹ怾割犚儆
Table 1- Alarm Codes

10 11
Owner’s Manual
WPC-23000
Wiring Diagram
Figure 12 - Circuit Wiring Diagram (WPC-23000)
愚決檺律
;ΠΕΖΝ ΈͺͺͿ͵ͺͲͲ;
Ͳ΅Ϳ ͵Έ͵Ͳ
箒嵢壊
毶癢
岂憮斲決溎 Ω
(TH1)
(TH2)
(TH3)
POWER
3P AC 460V / 60HZ
DRAIN
PUMP
460V
220V
TR
MB
MC1OCR1
R
S
T
R
E
S
T
R
S
T
R
S
T
R
S
T
MC2
COM
Comp’ Over Load
H
L
OCR2
洇殯微塾
ΈʹΫ冾殯
ΈʹΫ冾殯
旇柦勢
Ͳ΄Ͷ΅Ͷʹ΅抆把
ͲͿ櫖昢ͳͿʹ嵢櫶冶懆凃
娚枪稒崎決微檗懆凃
Ͳ΄Ͷ΅Ͷʹ΅抆把
Ϳʹ櫖昢Ϳ嵢懆凃
砒毒欌΅洢其洗滆Ͷ犚儆
;ʹʹ犚儆懆凃
·怾割犚儆
Ϋ·怾割斳洢
沗昷 円皦 筛汾
朞洛斲穳
沲滎汆怺塶姢嵷惾畲嵦
汾曊愯憛樮廇汾曊
汾曊族旇籗族壊
祢彺熞庲岂惾嘪決砋瑚砋
汾曊匶渆壊彺愕昪凊洢击穊床
歾刃汞獞朞昦抏汆昦汆汾曊篊洎埮昦沊
W-15 3P
MC3 OCR3
(TH1)
(TH2)
(TH3)
POWER
3P AC 460V / 60HZ
DRAIN
PUMP
R(L1)
S(L2)
T(L3)
C(CM)
PHASE
PROTECTOR
380/460V
220V
TR
MB
MC1OCR1
R
S
T
R
E
S
T
R
S
T
R
S
T
R
S
T
MC2
COM
Comp’ Over Load
H
L
OCR2
B(NC)
A(NO)
W-15 3P
MC3 OCR3
(TH1)
(TH2)
(TH3)
POWER
3P AC 460V / 60HZ
3P AC 380V / 50HZ
DRAIN
PUMP
380/460V
220V
TR
MB
MC1OCR1
R
S
T
R
E
S
T
R
S
T
R
S
T
R
S
T
MC2
COM
Comp’ Over Load
H
L
OCR2
W-15 3P
MC3 OCR3
[]W}G㜄㉐⏈GwohzlGwyv{lj{vyO㜡ㇵⵝ㫴PG⿃Ḕ
Z_W}G㜄㉐⏈G㻈ᴴ

11
Owner’s Manual
WPC-23000
Troubleshoong chart
Symptom Possible Cause(s) Correcve Acon
Water leakage High water level in
condensate tank
1. Remove blockage from drain
hose
2. Remove any object stuck under-
neath of the black panel under
the water tank
The unit doesn’t work
1. Check the power supply
to verify that power is
available to the unit
1. Reset the circuit breaker and
restart the unit
2. Verify that the power
cord is connected
2. Connect power cord
No cold air ows from the
cold air outlet
1. Ambient air cannot be
properly cooled if the
lter is dirty and not
regularly cleaned
1. Clean the lter
2. Compressor will not
work if the unit is
turned o and on
quickly.
2. Wait 2 minutes aer unit is
turned o before turning the
unit back on.
3. The ambient air tem-
perature may be too
high
3. The temperature of the com-
pressor can be higher when
the ambient temperature is
too high. The compressor will
not work unless the ambient
air temperature is within the
acceptable operang range of
the unit
Water ow can be heard
aer compressor shuts o No cause Common to hear coolant owing
aer unit shuts o

12 13
Owner’s Manual
WPC-23000
Obtaining service
If the AmeriCool by Weltem Portable Air Condioner requires Service:
1.
Use the TROUBLESHOOTING secon in this manual to eliminate obvious causes.
2. Verify there are no circuit breakers tripped.
3.
Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve
the problem, call AmeriCool by Weltem Portable Air Condioner Technical Support at
562.231.7175. Please have the following informaon available BEFORE calling the Technical
Support Department:
a. Your name and address.
b. The serial number of the unit.
c. Where and when the unit was purchased.
d.
All of the model informaon about your AmeriCool by Weltem Portable Air Condi-
oner.
e. Any informaon on the failure, including LED’s that may or may not be illuminated.
f.
A descripon of the protected equipment, including model numbers if possible.
Shipping list
• (1) PORTABLE AIR CONDIRIONER
• (1) Owner’s Manual
• (1) POWER CORD HOLDER
• (3) DISCHARGE / SUPPLY AIR DUCTS
• (1) EXHAUST FLANGE
• (1) Handle

13
PB
WPC-23000
Owner’s Manual
LIMITED WARRANTY
AmeriCool warrants all AmeriCool products to be free from defects in materials or workmanship,
under normal use and service, for a period of 12 months from the date of purchase to the end user
(original invoice must be provided). AmeriCool warrants that the compressor will be free from
defects in materials and workmanship for 12 months from the date of purchase to the end user.
AmeriCool’s obligaon under this warranty is limited to the repair or replacement at its opon,
of any part or parts, which, upon Ameriool’s examinaon are shown to be defecve, or at Ameri-
Cool’s opon, the return of the purchase price to the purchaser.
Correcon of such defects by repair or replacement, or at AmeriCool’s opon, the return of the
purchase price shall constute fulllment of warranty obligaons to the purchaser. This warranty
does not cover defects or malfuncons which result from causes beyond AmeriCool’s control,
including, without limitaon,(i) unusal physical or electrical stress:(ii) accident, neglect, abuse,
misuse or other abnormal use; (iii) failure to perform roune maintenance in accordance with
AmeriCool’s recommended procedures; (iv)normal wear and tear; (v) repairs or aempted repairs
by an unauthorized person; (vi) modicaons or alteraons to the Products; (vii) use with parts or
devices not supplied or approved by AmeriCool (viii) improper installaon or service; (ix) shipping
damage to any units or spare parts during shipping. This includes and is not limited to compres-
sors, evaporators and condenser coils. This warranty shall extend only to the original end-user and
shall be void if any labels or other idenfying marks permanently axed to Products when shipped
by AmeriCool are removed, altered, defaced or obliterated.
TO THE EXTENT PERMITTED BY LAW, THIS WARRANTY, AS LIMITED HEREIN, SHALL BE IN LIEU OF
AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, ON THE PART OF
AMERICOOL INC., OR WELTEM CO.,LTD. WHETHER ARISING FROM LAW, COURSE OF DEALING, US-
AGE OF TRADE, OR OTHERWISE, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF
MERCHANT-ABILITY OR FITNESS OF A PARTICULAR PURP OSE OR ANY LIABILITY FOR COMMERCIAL
LOSSES BASED UPON NEGLIGENCE OR MANUFACTURER’S STRICT LIABILITY. EXCEPT AS EXPRESSLY
PROVIDED HEREIN,NEITHER AMERICOOL, INC., NOR WELTEM CO., LTD. WILL, IN ANY EVENT, BE
LIABLE FOR LOST PROFITS, COSTS OF PROCESSING,INJURY, GOODWILL, OR ANY OTHER CONSE-
QUENTIAL DAMAGES OF ANY KIND ARISING FROM BREACH OF THIS WARRANTY.
Printed in January, 2021
Manufactured in Weltem Co., Ltd.,
154, Jayumuyeok 3-gil, Masanhoewon-gu, Changwon-City, Gyeongsangnam-do,
Republic of KOREA 51340 www.weltem.com
Distributed by Americool,Inc. In the USA (Tel.888-726-6158)
WWW.AMERICOOLLLC.COM
Table of contents
Other Weltem Air Conditioner manuals

Weltem
Weltem Americool HPC-3000 User manual

Weltem
Weltem Icen WPC-9000 User manual

Weltem
Weltem AMERICOOL User manual

Weltem
Weltem WPC-5000 User manual

Weltem
Weltem WPC-6000 User manual

Weltem
Weltem AMERICOOL WPC-36003 User manual

Weltem
Weltem WPW-4000 User manual

Weltem
Weltem WSC-4000 User manual

Weltem
Weltem WPC-4000 User manual

Weltem
Weltem AmeriCool WMC-2500 User manual
Popular Air Conditioner manuals by other brands

Daikin
Daikin FAQ71CVEB installation manual

GE
GE AEZ10AVL1 Owner's manual and installation instructions

Haier
Haier HBU-18CA03T3 Operation & installation manual

Bryant
Bryant 14 SEER Service manual

Hitachi
Hitachi airHome 400 DJ Series Operation manual

Mitsubishi Electric
Mitsubishi Electric MSZ-LN25VGW operating instructions