Weltem Icen WPC-23000 User manual

Owner’s Manual WPC-23000
Model No. Power Supply Ph-V-Hz Cooling
Capacity Btu/h
Power Consump-
on Wa s
EER Btu/
Wh
Rated Cur-
rent Amps
WPC-23000 3 phases, 380V, 50Hz 83,000 13,800 9.2 21
Model No. Nema Plug Power Cord
Gauge AWG
Power Cord
Length (m)
Dimensions
W x D x H - in. (mm)
WPC-23000 Terminal type 10 328.9 x 51.6 x 59.8
(735 x 1,310 x 1,520)
Model No. Weight (Net / Gross) Lbs(kg) No. of Cool Air
Outlets Pcs
Condensate tank
Gallons(Liters)
Ambient temperature
range °F( °C)
WPC-23000 761/793 (345/360) 3Auto Pump
Included 69~113(21~45)

2 3
Owner’s Manual WPC-23000
Model No. Seng temperature
(Room cool mode) °F( °C)
Seng temperature
(Spot cool mode) °F( °C)
WPC-23000 64~86 (18~30) 32~86 (0~30)
Model No. Applicaon Area
(Room cool mode) ²(m²)
Refrigerant
Type / oz(g)
Design Pressure - Hi/
Low Psig
WPC-23000 2,260 (210) R-410A
/ 123(3,500) 450 / 250
Model No. Indoor Air Flow
CFM(CMM)
Wheels
pcs / diameter
Hot Air Duct Di-
ameter In.(mm)
Maximum Exhaust
Duct Lenght (m)
WPC-23000 2550 (73) 4 / 127mm 20 (500) 100 (30)
Safety Devices
Compressor overload protector, An-freezing thermister,
Full drain tank switch, Automac restart (Power inter-
rupon), Compressor me delay program, High pressure
switch
Features
Temperature control, Self-diagnosc funcon, Two speed
fan, Oponal drain pump kit, Washable lters, °F( °C)
display, O-mer

3
Owner’s Manual WPC-23000

4 5
Owner’s Manual WPC-23000
Front and Right Side View
Condenser / filter
Figure 3
Figure 2
Back and Le Side View
Caster
Electrical access panel
Drain pump hose connector
Handle
Cool air outlet
Display / Control board
Top fan exhaust flange
Evaporator / filter
Condenser / filter
Drain pump included
Figure 8
Figure 7
Figure 4 Figure 5
Figure 6
1. Remove cool air outlet hose(s) from
carton.
2. Place the cool air outlet hose(s) on
the front top of air condioner.
3. Use screws (enclosed inside of box
with cool air outlet hose(s) to install
the cool air outlet hose(s)
on the air condioner as shown in
Figure 5.
1. Take out the cord holder
from the accessory box.
2. Place the cord holder on
the back side of air condioner.
3. Use screws (enclosed inside of
accessory box ith cord
holder)to install the cord
holder on the air condioner
as shown in Figure 4.
TOP FAN EXHAUST FLANGE
1. Remove the top fan exhaust flange from carton.
2. Place the top fan exhaust flange on the top of air
condioner.
3. Use screws (enclosed inside of box with the top fan
exhaust flange) to install the top fan exhaust flange on air
condioner as shown in Figure 6.
HANDLE
1. Remove a handle from carton.
2. Place the handle on upper side of rear panel.
3. Use screws (enclosed inside of box with a handle)
to install the handle as shown in Figure 7.
POWER CORD HOLDER
DISCHARGE DUCTS
/SUPPLY AIR DUCT
A condenser plenum can be purchased separately. condenser plenum
fits over the condenser to duct condenser air to the unit to improve
cooling efficiency.
1. Remove the Filter("A")
2. Check the Filter("C") is inserted properly in condenser plenum("B")
3. Install "B" which contains "C" by using driver with enclosed
bolts(6EA) as Figure 8.
CONDENSER PLENUM
(Oponal)
A
B
C

5
Owner’s Manual WPC-23000

6 7
Owner’s Manual WPC-23000
Operaon
CONTROL PANEL
1. POWER BUTTON: Acvates unit when POWER BUTTON is pressed. If POWER BUTTON is
pressed during operaon, unit stops.
2. BLOWER BUTTON: Indicates fan speed. (Not available for 3 phase model)
3. COOL BUTTON: Acvates compressor and begins producing cool air in 5 seconds aer
buon is pressed.
4. TIMER BUTTON: Enters to Timer Seng Mode by pressing TIMER BUTTON for 1 seconds.
Two digits on CURRENT TEMP indicate hour(s) and two digits on TARGET TEMP indicate
minutes. Set desired o-me by pressing SET TEMP BUTTONS.
5. ALARM: Alarm indicator lights (blinks) and indicates abnormal system operaon.
If Alarm occurs, compressor stops. System operaon stops when Alarm light is acvated
(blinks) longer than 3 minutes.
6. SPOT/COOL: Lights (blinks) when unit is operated on SPOT/COOL mode.
7. SET TEMP BUTTONS: Change target temperature/data value by +/-1. Press the SET TEMP
BUTTONS to set temperature. Upper buon is to heighten temperature and Lower buon
is to lower temperture.
8. TARGET TEMP: Displays unit set temperature for ROOM/COOL mode only.
Set TARGET TEMP 0 ℃ or 32℉ on SPOT/COOL mode.
108&3 #-08&3 $00- 5*.&3
4105$00-
"-"3.
$633&/5
5&.1)6.*%
5" 3(&5
5&.1)6.*%
12
7
34
6
5
98
Figure 9

7
Owner’s Manual WPC-23000
9. CURRENT TEMP: Displays ambient temperature (In ROOM/COOL mode only) / Displays outlet
(cool air) temperature during normal operaons (In SPOT/COOL mode only)
In order to change ℃to ℉, press BLOWER and COOL buons together for 2 seconds.
F will blink 2 mes and Figure will change to °F. ALARM codes blink and are displayed
when abnormal operaon occurs.
SPOT/COOL mode → ROOM/COOL mode : Enter to ROOM/COOL mode if COOL BUTTON and
TIMER BUTTON are pressed together for 1 seconds.
ROOM/COOL mode → SPOT/COOL mode : Enter to SPOT/COOL mode if COOL BUTTON is
pressed for 1 seconds.
AUTO RESTART: If the unit goes o due to an electrical interrupon, the unit will automacally
restart when the power resumes.

8 9
Owner’s Manual WPC-23000
– Loosen up 2 bolts on
the front filter guard.
– Slide filter up and use
a vacuum cleaner to remove
the dust from the filter.
– Remove dust from the filter
using a vacuum cleaner
hose aachment.
– If required wash the filter i
n
luk
ewarm water with a mild
detergent. Leave to dry in
a shaded area before
reinstalling.

9
Owner’s Manual WPC-23000
Product Portable Air Condioner
Model No.
Date of Purchase
Place of Purchase
Serial No.
Period of Warranty

10 11
Owner’s Manual WPC-23000
Table 1- Alarm Codes
SELF-DIAGNOSTIC ALARM CODES
Alarm
Display Problem CauseCorrecve Acon
愚決檺律
;ΠΕΖΝ ͽͲ΅ͶʹͲΆ΅ͺͿ
Ͳ΅Ϳ
͵Ͳ;ͶͺʹͽΈʹ
惾剳
岂憮斲決溎 Ω
惾剳殯Έʹ
洇殯微塾
沗昷 円皦 筛汾
朞洛斲穳
沲滎汆怺塶姷嵷滆惾畲嵦
汾曊愯憛樮廇汾曊
汾曊族旇籗族壊
祢彺熞庲岂惾嘪決砋瑚砋
汾曊匶渆壊彺愕昪凊洢击穊床
歾刃汞獞朞昦抏汆昦汆汾曊篊洎埮昦沊
ʹ怾割犚儆
Frost on heat
exchanger
Abnormal
temperature
sensor value
Abnormal
temperature
sensor value
Abnormal
temperature
sensor value
Evaporator motor
overload
(for wpc-23000)
Drain pump
alarm
High pressure
Indoor heat exchanger
temperature too low
TH1(Outlet) temperature
sensor has a loose or
broken connecon
TH2(Inlet) temperature
sensor has a loose or
broken connecon
TH3(Evaporator coil)
temperature sensor has
a loose or broken connecon
Drain pump defecve or
improper hose connecon
(including kink or blockage)
Improper air circulaon
High ambient
temperature
Clean the air filter
Ensure exhaust duct is not
blocked or kinked
Ambient temperature must
be under 45°C(113°F)
Ambient temperature is
too high
Unstable voltage supply
Defecve compressor
Abnormal operaon of
evaporator motor
(for wpc-23000)
Abnormal operaon of
condenser motor
(for wpc-23000)
Do not use the air
condioner if ambient
temperature is lower than
18°C (64°F)
Contact a qualified service
agent
Contact a qualified service
agent
Contact a qualified service
agent
Contact a qualified service
agent
Do not use the air condioner
if ambient temperature is
higher than 45°C (113°F)
Contact a qualified service
agent
Replace compressor
Contact a qualified service
agent
Check the hose connecon
and hose
Replace drain pump
Compressor
overload
Condenser motor
overload
(for wpc-23000)
SELF-DIAGNOSTIC ALARM CODES
Alarm
Display ProblemCause Correcve Acon
Frost on heat
exchanger
Abnormal
temperature
sensor value
Abnormal
temperature
sensor value
Abnormal
temperature
sensor value
Evaporator motor
overload
(for wpc-23000)
Drain pump
alarm
High pressure
Indoor heat exchanger
temperature too low
TH1(Outlet) temperature
sensor has a loose or
broken connecon
TH2(Inlet) temperature
sensor has a loose or
broken connecon
TH3(Evaporator coil)
temperature sensor has
a loose or broken connecon
Drain pump defecve or
improper hose connecon
(including kink or blockage)
Improper air circulaon
High ambient
temperature
Clean the air filter
Ensure exhaust duct is not
blocked or kinked
Ambient temperature must
be under 45°C(113°F)
Ambient temperature is
too high
Unstable voltage supply
Defecve compressor
Abnormal operaon of
evaporator motor
(for wpc-23000)
Abnormal operaon of
condenser motor
(for wpc-23000)
Do not use the air
condioner if ambient
temperature is lower than
18°C (64°F)
Contact a qualified service
agent
Contact a qualified service
agent
Contact a qualified service
agent
Contact a qualified service
agent
Do not use the air condioner
if ambient temperature is
higher than 45°C (113°F)
Contact a qualified service
agent
Replace compressor
Contact a qualified service
agent
Re-connect the power cable
to the correct power source
Check the hose connecon
and hose
Replace drain pump
Compressor
overload
Condenser motor
overload
(for wpc-23000)
Incorrect power
cable connecon
Out of phase

11
Owner’s Manual WPC-23000
136
116
바이어명
Model WIRING DIAGRAM
PART NO.
웰템
라벨 사이즈 136x116
적용모델
작 성 검 토 확 인
수정사항
1
2
3
4
5
6
7
8
1
2
3
4
5
1. 재질 : 은무데드롱 25미크론
2. 인쇄방법: 씨링인쇄
3. 인쇄색상: 흑색 1도
4. 표면처리: 라미네이팅(OPP코팅)
5. 인쇄기준 : 도면 및 설계 제공 필름
6 외곽의 치수선(붉은선)은 인쇄후 절단선임.
W - 23000 CP1.3
MCCB
Power
3P AC 380V-50/60Hz
3P AC 460V-60Hz
E
R
S
T
CP
PU
HT
EXT
COM
EMC
L
H
TH1
TH1
OUT_TEMP
SENSOR
SEN1
SEN2
SEN3
TH2
TH2
TH3
TH3
IN_TEMP
SENSOR
ICE_TEMP
SENSOR
MC 1 OCR 1
R
T
COMP'
FND
PS (HP)
COM
COM
EXT
FU
FT
CO
COM
R
COM
L
H
COM
CP
N-1
L-1
COM
CO
Power Remote
Control (Option)
EXT
COM
(FUSE)
(FUSE)
HIGH
PRESSURE
SWITCH
PHASE
PROTECTOR
C (CM)
B (NC)
A (NO)
R (L1)
S (L2)
T (L3)
TR
220V
R
T
380-460V
R
S
T
R
S
T
R
S
T
S
MC 2 OCR 2
R
S
T
R
T
S
S
T
R
S
T
MC 3 OCR 3
R
S
T
R
T
COND'
MOTOR
S
R
S
T
COM
E VA '
MOTOR
R
T
CP
COM
H
COM
COM
CO
R
S
T
CP
DRAIN
PUMP
FU COM
HP
WIFI & RF ON/OFF
SWITCH (Option)
LOW
PRESSURE
SWITCH
(Option)
IR/FT
LP
LP
HOT GAS
HG
HG
Solenoid
Valve
(Hot Gas Bypas)
HG
HG
T (AC) S R
POWER BLOWER COOL TIMER
SPOT/COOL
ALARM
CURRENT
TEMP/HUMID
TARGET
TEMP/HUMID

12 13
Owner’s Manual WPC-23000
Symptom Possible Cause(s) Correcve Acon
Water leakage High water level in
condensate tank
1. Remove blockage from drain
hose
2. Remove any object stuck under-
neath of the black panel under
the water tank
The unit doesn’t work
1. Check the power supply
to verify that power is
available to the unit
1. Reset the circuit breaker and
restart the unit
2. Verify that the power
cord is connected
2. Connect power cord
No cold air ows from the
cold air outlet
1. Ambient air cannot be
properly cooled if the
lter is dirty and not
regularly cleaned
1. Clean the lter
2. Compressor will not
work if the unit is
turned o and on
quickly.
2. Wait 2 minutes aer unit is
turned o before turning the
unit back on.
3. The ambient air tem-
perature may be too
high
3. The temperature of the com-
pressor can be higher when
the ambient temperature is
too high. The compressor will
not work unless the ambient
air temperature is within the
acceptable operang range of
the unit
Water ow can be heard
aer compressor shuts o No cause Common to hear coolant owing
aer unit shuts o

13
Owner’s Manual WPC-23000

14 15
Owner’s Manual WPC-23000

15
Owner’s Manual WPC-23000

16 PB
Owner’s Manual WPC-23000
Manufactured in Weltem co., Ltd., 154, Jayumuyeok 3-gil, Masanhoewon-gu, Changwon-City,
Gyeongsangnam-do, 51340 Korea www.weltem.com Printed in December, 2019
Table of contents
Other Weltem Air Conditioner manuals

Weltem
Weltem WSC-4000 User manual

Weltem
Weltem WPC-3000 User manual

Weltem
Weltem WPC-6000 User manual

Weltem
Weltem AmeriCool WMC-2500 User manual

Weltem
Weltem AmeriCool WPC-18000 User manual

Weltem
Weltem WPW-4000 User manual

Weltem
Weltem WPW-4000 User manual

Weltem
Weltem WPC-5000 User manual

Weltem
Weltem AMERICOOL WPC-36003 User manual

Weltem
Weltem AMERICOOL User manual