
Installation and electrical connection en
Installation and operating instructions Wilo-Padus UNI 15
▶ The pump is installed, the qualified electrician can make
the electrical connection.
6.4.3 Level control
With a level control device, the current fill levels are determined
and the pump is switched on and off automatically depending on
the fill levels. Fill levels are recorded by using different sensor
types (float switches, pressure and ultrasound measurements or
electrodes). The following must be observed when using a level
control device:
ƒFloat switches can move freely!
ƒThe water level must not fall below the minimum permissible!
ƒThe maximum switching frequency must not be exceeded!
ƒIf the fill levels fluctuate strongly, a level control with two
measuring points is recommended. This makes it possible to
achieve larger differential gaps.
Use of the attached float switch
The “A” and “VA”versions are equipped with a float switch. The
pump is switched on and off depending on the fill level. The
switching level is defined as follows:
ƒAversion with float switch: by the cable length
ƒVAversion with vertical float switch: by the position of the
floater on the guide pin (factory setting)
The factory setting for the floater offers the maximum switching
volume. The floater setting can be changed if required. NO-
TICE!The top floater is set to the upper switching point. If the
switching point is reset downwards, the pump will no longer be
completely submerged in the fluid. This means that the pump
can only be operated in intermittent periodic duty S3!
Adjusting the floater switching point.
‡Pump is out of operation.
‡Pump disconnected from mains.
1. Undo interior hexagonal head screw on floater.
2. Set the required switching point: Push the floater up-
wards or downwards.
3. Fixing the floater: Tighten interior hexagonal head screw
on floater.
▶ New switching points are set.
Use of on-site level controls
When using an on-site level control device, refer to the manufac-
turer’s own installation and operating instructions for specifica-
tions on the installation.
6.4.4 Dry-running protection
Dry-running protection must prevent the pump from operating
without fluid and air from entering the hydraulics. The minimum
permissible fill level must be determined with the help of a signal
transmitter. Once the specified limit value is reached, the pump
must be deactivated with an appropriate signal. Dry-running pro-
tection can expand the available level controls by an additional
measuring point or function as an independent switch-off device.
Depending on the system security, the pump can be restarted au-
tomatically or manually. Installation of dry-running protection is
recommended for optimum operational reliability.
6.5 Electrical connection
DANGER
Risk of death due to electrocution!
Improper conduct when carrying out electrical work
can lead to death due to electric shock! Electrical
work must be carried out by a qualified electrician in
accordance with the locally applicable regulations.
ƒThe mains connection must match the specifications on the
rating plate.
ƒPower supply on mains side for three-phase current motors
with clockwise rotating field.
ƒLay the connection cable in accordance with the locally applic-
able regulations and connect it according to the wire assign-
ment.
ƒConnect the monitoring devices and check their function.
ƒEarth the device properly in accordance with applicable local
regulations.
6.5.1 Fuse on mains side
Circuit breaker
The size and switching characteristics of the circuit breakers must
conform to the rated current of the connected product. Observe
local regulations.
Motor protection switch
Make provision for an on-site motor protection switch for devices
without a plug! The minimum requirement is a thermal relay/mo-
tor protection switch with temperature compensation, differential
triggering and anti-reactivation device in accordance with the
local regulations. In case of sensitive mains, make provision for the
installation on-site of other protective equipment (e.g. over-
voltage, undervoltage or phase failure relay, etc.).
Residual-current device (RCD)
Comply with the regulations of the local energy supply company!
The use of a residual-current device is recommended.
If persons come into contact with the device and conductive flu-
ids, secure the connection with a residual-current device (RCD).
6.5.2 Maintenance tasks
Carry out the following maintenance tasks prior to installation: