
9
An ongoing program of product improvement may require us to change
specifications without notice. (-W). Revised September 2009
Wood Stone Corporation
1801 W. Bakerview Rd.
Bellingham, WA 98226 USA
Toll Free (800) 988-8103
Tel (360) 650-1111
Fax (360) 650-1166
Mountain Series Installation and Operation Manual
oVen VentinG
Install venting system in accordance with the duct manufacturer's instructions and in accordance with all local
codes. All field built components should be built to the applicable codes and standards and are subject to the
approval of the authority having jurisdiction.
The following are the manufacturer’s recommendations for venting the Wood Stone MS (Mountain Series) -W (wood-fired)
ovens. It is never appropriate to use “B vent” in any part of an exhaust system connected to a Wood Stone oven. All ducting
material must be manufactured to the specifications of a grease duct and a listed building heating appliance chimney. This
is a wood-fired oven and must be vented as a solid fuel piece of equipment. Due to the possibility of sparks entering the
system, exhaust systems serving solid fuel equipment must be vented separately from other non-solid fuel equipment.
Submit your venting plans to your local authorities before proceeding with your installation, as there may be additional
requirements in your area. The duct serving this solid fuel oven should be inspected at least twice a month during the
first two months of operation, to establish rate of creosote buildup and necessary cleaning schedule. If creosote or soot
has accumulated, it should be removed to reduce the risk of a flue fire.
1. Direct Connection:A listed building heating appliance chimney, also listed as a grease duct as described in NFPA
96, connected directly to the oven flue collar and provided with a power ventilator listed for restaurant appliance
exhaust. The power ventilator should be rated for a minimum of 450 degrees Fahrenheit (F). Wood Stone does
not recommend the use of an in-line fan. A field built grease duct, constructed and installed to the specifications
of a grease duct as detailed in NFPA 96 or the International Mechanical Code, may also be used.
A static pressure of -0.14 inches water column is necessary at the oven flue collar to ensure that flue gas
temperatures do not exceed 450 degrees F at the fan inlet. The CFM required to attain this static pressure will
depend on the configuration of your particular installation but will probably be between 500 and 700 CFM.
Wood Stone provides a port in the flue collar of the oven for insertion of a magnehelic gauge. This enables
the installer to monitor the draft to ensure proper operation of the venting system. This measurement may
also be taken by inserting the end of the probe through the oven doorway, upwards to the oven flue collar.
NOTE: Double door ovens (Models ending in DD), have two flue collars, both must be connected and a static
pressure of -0.14 inches must be maintained at each collar.
OVEN MODEL SERIES FLUE COLLAR I.D. (NOMINAL)
Mt. Adams WS-MS-5 10 inch
Mt. Baker WS-MS-6 10 inch
Mt. Rainier WS-MS-7 10 inch
NOTE: MS-4 ovens come standard with a round 8" O.D. collar and do not
require the flue adapter for a direct connection.
NOTE: If your MS-5, MS-6, or MS-7 oven is ordered from Wood Stone without a hood, it will have a round flue
adapter installed to facilitate direct connection to a round duct. If the oven is to be installed under a hood, it MAY
be necessary to remove the round adapter to properly position the hood. This is done by removing the screws
that attach the adapter to the oven. Please contact Wood Stone if you have any questions.
Collar I.D.
THERE ARE THREE OPTIONS:
THIS OVEN MUST BE VENTED AS A SOLID FUEL APPLIANCE
Flue Adapter