IM 05P08D31-11EN page 2/12
4. HardwareSpecications
This instrument is for Measurement Category No.1.
Do not use it for measurements in locations falling under Measure-
ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
IV
III T
O( I )
II
Category IEC/EN/CSA/UL
61010-1 EN 61010-2-030 Remarks
No.1 Measurement
CategoryI O(Other) For measurements performed on circuits not direct-
lyconnectedtoMAINS.
No.2 Measurement
CategoryII
Measurement
CategoryII
For measurements performed on circuits directly
connectedtothelow-voltageinstallation.
No.3 Measurement
CategoryIII
Measurement
CategoryIII
Formeasurementsperformedinthebuildinginstal-
lation.
No.4 Measurement
CategoryIV
Measurement
CategoryIV
For measurements performed at the source of the
low-voltageinstallation.
■ InputSpecications
●UniversalInput(Equippedasstandard)
• Numberofinputs:1
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,
Input Type Instrument Range Accuracy
ºC ºF
Thermo-
couple
K
-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±2%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleK
±1%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF
-200.0to500.0ºC -200.0to1000.0ºF
J-200.0to1200.0ºC -300.0to2300.0ºF
T
-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digit
for400°Cormore
±5%ofinstrumentrange±1digitfor
lessthan400°C
S0.0to1700.0ºC 32to3100ºF ±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF
±0.1%ofinstrumentrange±1digit
±0.25%ofinstrumentrange±1digit
forlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±1.5%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U
-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit
(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor
800°Cormore
Accuracyisnotguaranteedforless
than800°C.
W97Re3-
W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100 -200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100
-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0ºC -300.0to1000.0ºF
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal
0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V
4.00to20.00mA
DCvoltage/current
0.000to2.000V
0.00to10.00V
0.00to20.00mA
-10.00to20.00mV
0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpower
frequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange
between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:200ms
•Burnoutdetection:
FunctionsatTC,RTD,andstandardsignal.
Upscale,downscale,andocanbespecied.
Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4
mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)
•Measuredcurrent(RTD):About0.16mA
•Inputresistance:
TCormVinput:1MΩormore
Vinput:About1MΩ
mAinput:About250Ω
•Allowablesignalsourceresistance:
TCormVinput:250Ωorless
Eectsofsignalsourceresistance:0.1µV/Ωorless
DCvoltageinput:2kΩorless
Eectsofsignalsourceresistance:About0.01%/100Ω
• Allowablewiringresistance:
RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires
shallbeequal.)
Wiringresistanceeect:±0.1ºC/10Ω
• Allowableinputvoltage/current:
TC,mV,mAandRTDinput:±10VDC
Vinput:±20VDC
mAinput:±40mA
• Noiserejectionratio:
Normalmode:40dBormore(at50/60Hz)
Commonmode:120dBormore(at50/60Hz)
For100-240VAC,the power frequencycan beset manually.Automatic
detectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.
• Referencejunctioncompensationerror:
±1.0ºC(15to35ºC),±1.5ºC(-10to15ºCand35to50ºC)
• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
■ ContactInputSpecications
• Numberofinputs:SeethetableofModelandSuxCodes.
• Inputtype:No-voltagecontactinputortransistorcontactinput
• Inputcontactrating:12VDC,10mAormore
Useacontactwithaminimumon-currentof1mAorless.
• ON/OFFdetection:
No-voltagecontactinput:
Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact
resistanceof50kΩormoreas“OFF.”
Transistorcontactinput:
Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust
notexceed100µAwhen“OFF.”
• Minimumstatusdetectionholdtime:Controlperiod+50ms
• Use:SPswitch,operationmodeswitch,andeventinput
■ AnalogOutputSpecications(OUT,OUT2)
• Numberofoutputs:
Controloutput:2
• Outputtype:Currentoutputorvoltagepulseoutput
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
• Voltagepulseoutput:
Use:Timeproportionaloutput
On-voltage:12Vormore/loadresistanceof600Ωormore
O-voltage:0.1VDCorless
Timeresolution:10msor0.1%ofoutput,whicheverislarger
■ RelayContactOutputSpecications(OUT,OUT2)
• Contacttypeandnumberofoutputs:1a;2points(commonisindependent)
• Contactrating:240VAC,3Aor30VDC,3A(resistanceload)
• Use:Timeproportionaloutput,ON/OFFoutput
• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislarger
Note:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore.
■ AlarmRelayContactOutputSpecications(ALM)
• Contacttypeandnumberofoutputs:3points(commonisindependent)
• Contactrating:240VAC,1Aor30VDC,1A(resistanceload)
• Use:Alarmoutput,FAILoutput,etc.
Note:Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.
■ HeaterBreakAlarmSpecications(for/HAoption)
• Numberofinputs:2
• Numberofoutputs:2(transistorcontactoutput)
• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)and
generatesaheaterbreakalarmwhenthemeasuredvalueislessthanthebreak
detectionvalue.
• Currenttransformerinputresistance:About9.4Ω
•
Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeapplied.)
• Heatercurrentsettingrange:OFF,0.1to300.0Arms
Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms
Note:TheCTratiocanbeset.CTratiosettingrange:1to3300
• RecommendedCT:CTfromU.R.D.,Ltd.
CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms
CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms
• Heatercurrentmeasurementperiod:200ms
• Heatercurrent measurementaccuracy:±5%ofcurrenttransformerinputrange
span±1digit(CTerrorisnotincluded.)
•
Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan
• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)
■ SafetyandEMCStandards
• Safety:
CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-
2-030(CE),approvedby CAN/CSAC22.2No.61010-1(CSA),approvedbyUL
61010-1.
Installationcategory:II
Pollutiondegree:2
Measurementcategory:I(CATI)(UL,CSA)
O(Other)(CE)
Ratedmeasurementinputvoltage:Max.10VDC
Ratedtransientovervoltage:1500V(*)
*ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-
1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilya
guaranteeofinstrumentperformance.
• EMCstandards:
CompliantwithCEmarking
EN61326-1ClassA,Table2(Foruseinindustriallocations),
EN61326-2-3
*Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting.
EN55011ClassA,Group1
EN61000-3-2ClassA
EN61000-3-3
EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A)
EN55011ClassA,Group1
• KCmarking:
Electromagneticwaveinterferencepreventionstandard,electromagneticwave
protection standard compliance
■ Construction,Installation,andWiring
• Dust-proofand drip-proof: IP66 (forfrontpanel)(Notavailableforside-by-side
closemounting.)
• Material:Polycarbonate(Flameretardancy:UL94V-0)
• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)
• Weight:0.5kgorless
• Externaldimensions(mm):48(W)×96(H)×65(depthfromthepanelface)
(Depthexcepttheprojectionontherearpanel)
• Installation:Directpanelmounting;mountingbracket,oneeachforupperand
lowermounting
• Panelcutoutdimensions(mm):45+0.6/0(W)×92+0.8/0(H)
•
Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.
• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
■ PowerSupplySpecicationsandIsolation
• Powersupply:
Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz
24VAC/DC(+10%/-15%)(for/DCoption)
• Powerconsumption:15VA(DC:7VA,AC:11VAif/DCoptionisspecied)
• Databackup:Nonvolatilememory
• Powerholduptime:20ms(for100VACdrive)
• Withstandingvoltage
Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA)
Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE)
Betweenprimaryterminals:1500VACfor1minute
Betweensecondaryterminals:500VACfor1minute
(Primary terminals:Power*andrelayoutputterminals;Secondaryterminals:
AnalogI/Osignalterminals,contactinputterminals,communicationterminals
andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.
• Insulationresistance:Between power supply terminalsandagroundingterminal
20MΩormoreat500VDC
• Isolationspecications
The circuits divided by lines are insulated mutually.
Control (analog) output terminal (OUT, OUT2)
(not isolated between the analog output terminals)
PV1 (universal) input terminal
PV2 (universal) input terminal
Control relay (2 a-contact) output terminal (OUT, OUT2)
Alarm-1 relay (a-contact) output terminal
Alarm-2 relay (a-contact) output terminal
Alarm-3 relay (a-contact) output terminal
Internal
circuits
Power
supply
Contact input terminal (3 points)
RS485 communication terminal
Current transformer input terminal
■ EnvironmentalConditions
Normal Operating Conditions:
• Ambienttemperature:-10to50°C(side-by-sidemounting:-10to40°C)
• Ambienthumidity:20to90%RH(nocondensationallowed)
• Magneticeld:400A/morless
• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90
minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseach
inthethreeaxisdirections
• Short-periodvibration:14.7m/s2, 15 seconds or less
• Shock:98m/s2or less, 11 ms
• Altitude:2000morlessabovesealevel
• Warm-uptime:30minutesormoreafterthepoweristurnedon
• Startuptime:Within10seconds
*: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.
TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow
temperature.However,thecontrolfunctionisnotaffected.
Transportation and Storage Conditions:
• Temperature:-25to70ºC
• Temperaturechangerate:20ºC/horless
• Humidity:5to95%RH(nocondensationallowed)
EectsofOperatingConditions
• Eectofambienttemperature:
VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger
Currentinput:±0.01%ofF.S./ºC
RTDinput:±0.05ºC/ºC(ambienttemperature)orless
Analogoutput:±0.02%ofF.S./ºCorless
• Eectofpowersupplyvoltageuctuation
Analoginput:±0.05%ofF.S.orless
Analogoutput:±0.05%ofF.S.orless
(Eachwithinratedvoltagerange)