STYLE SYSTEM #1 FIELD SUPPLIED WIRING
MODEL VOLTS MCA1MIN NF D.E. FU C.B. (LUGS) WIRE RANGE COMPRESSOR FANS
60 Hz DISC SW2MIN.3MAX.4MIN.5MAX.6WYE-DELTA7ACR-LINE7RLA Y LRA X LRA FLA (EA)
200 374 400 450 600 450 600 (2) #6-250 N/A 267 424 1358 10.0
230 337 400 400 500 400 500 (2) #6-250 N/A 231 362 1159 12.0
YCAS140 380 204 200 250 300 250 300 (2) #6-250 N/A 146 216 691 5.2
460 165 200 200 250 200 250 (2) #8-1/0 (1) #6-250 116 181 579 5.0
575 136 200 175 225 175 200 (2) #8-1/0 (1) #6-250 92 145 463 4.9
200 447 600 600 700 600 700 (2) 1/0-500 N/A 325 492 1575 10.0
230 404 400 500 600 500 600 (2) #6-250 N/A 284 462 1479 12.0
YCAS160 380 244 400 300 400 300 400 (2) #6-250 N/A 178 261 835 5.2
460 197 200 250 300 250 300 (2) #6-250 (1) #6-250 141 217 695 5.0
575 161 200 200 250 200 250 (2) #8-1/0 (1) #6-250 113 170 543 4.9
200 509 600 700 800 700 800 (2)1/0-500 N/A 375 587 1879 10.0
230 458 600 600 700 600 700 (2)1/0-500 N/A 328 538 1723 12.0
YCAS170 380 279 400 350 450 350 450 (2) #6-250 N/A 206 316 1013 5.2
460 224 400 300 350 300 350 (2) #6-250 (1) 1/0-500 163 262 838 5.0
575 183 200 225 300 225 250 (2) #8-1/0 (1) #6-250 130 204 655 4.9
200 509 600 700 800 700 800 (2) 1/0-500 N/A 375 587 1879 10.0
230 458 600 600 700 600 700 (2) 1/0-500 N/A 328 538 1723 12.0
YCAS180 380 279 400 350 450 350 450 (2) #6-250 N/A 206 316 1013 5.2
460 224 400 300 350 300 350 (2) #6-250 (1) 1/0-500 163 262 838 5.0
575 183 200 225 300 225 250 (2)#8-1/0 (1) #6-250 130 204 655 4.9
200 570 600 700 800 700 800 (2) 1/0-500 N/A 424 785 2492 10.0
230 508 600 600 800 600 800 (2) 1/0-500 N/A 367 641 2035 12.0
YCAS190 380 311 400 400 500 400 500 (2) #6-250 N/A 232 401 1272 5.2
460 250 400 300 400 300 400 (2) #6-250 (1) 1/0-500 183 331 1051 5.0
575 203 200 225 300 250 300 (2) #6-250 (1) 1/0-500 147 270 857 4.9
380 392 400 500 600 500 600 (2) #6-250 N/A 296 483 1531 5.2
YCAS216 460 314 400 400 500 400 500 (2) #6-250 (1) 1/0-500 235 398 1261 5.0
575 253 400 300 400 300 400 (2) #6-250 (1) 1/0-500 187 311 987 4.9
380 337 400 400 500 400 500 (2) #6-250 N/A 244 316 1013 5.2
YCAS216X 460 272 400 350 450 350 450 (2) #6-250 (1) 1/0-500 193 262 838 5.0
575 224 400 300 350 300 300 (2) #6-250 (1) #6-250 155 204 655 4.9
380 392 400 500 600 500 600 (2) #6-250 N/A 296 483 1531 5.2
YCAS236 460 314 400 400 500 400 500 (2) #6-250 (1) 1/0-500 235 398 1261 5.0
575 253 400 300 400 300 400 (2) #6-250 (1) 1/0-500 187 311 987 4.9
380 397 400 500 600 500 600 (2) #6-250 N/A 292 401 1272 5.2
YCAS236X 460 319 400 400 500 400 500 (2) #6-250 (1) 1/0-500 231 331 1051 5.0
575 260 400 350 400 350 400 (2) #6-250 (1) 1/0-500 184 270 857 4.9
380 414 400 500 700 500 700 (2) 1/0-500 N/A 314 483 1531 5.2
YCAS246 460 332 400 400 500 400 500 (2) #6-250 (1) 1/0-500 249 398 1261 5.0
575 267 400 350 450 350 400 (2) #6-250 (1) 1/0-500 198 311 987 4.9
460 324 400 400 500 400 500 (2) #6-250 (1) 1/0-500 235 398 1261 5.0
YCAS266X 575 263 400 350 400 350 400 (2) #6-250 (1) 1/0-500 187 311 987 4.9
STANDARD DUAL POWER SUPPLY
(Each Power Supply Individually Protected with Field Supplied Branch Circuit Protection)
NOTES for Electrical Data, pages 18 - 25:
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C.Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the
system #1 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440-12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLA’s (U.L. Standard 1995, Section 36.1).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22.
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2.
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2) or (3)
indicated the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information.The above recommendations are based on the
National Electric Code and using copper connectors only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compr. system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.