INSTALLATION/OPERATION
VARIABLE SPEED OIL PUMP DRIVE
REMOTE KEYPAD UNIT
Supersedes: Nothi g Form 160.00-NO7 (599)
OPERATING INSTRUCTIONS
The Remote Keypad Unit (RKU) is a portable, hand
held accessory for use with the York Variable Speed
il Pump Drive (VS P). When connected to a VS P
Drive it provides the ability to view the different con-
trols within the VS P Drive. Typically, the RKU will
be used to determine what condition is causing the VS P
Drive to fault. The RKU is powered by a 9 volt alkaline
battery (supplied). Auto Power-Down and backlight con-
trol features conserve battery life by automatically turn-
ing the RKU off after a specified time period and by
allowing selected use of the display backlight.
The Remote Keypad Unit has the abil-
ity to program many different controls
within the VSOP Drive DO NOT
change any of these controls, they are
programmed at the factory and do not
require any adjustment Problems as-
sociated with modifying any of these
controls WILL NOT be covered by war-
ranty
QTY DESCRIPTION
1Remote Keypad U it
14-co ductor modular i terco ectio cable
19-volt alkali e battery
INITIAL INSPECTION
Upon receipt, unpack and carefully inspect for any dam-
age sustained in transit (depression in the enclosure,
damage to parts, missing parts). If damage is apparent,
the shipping agent should be notified. If there are parts
missing, consult the Baltimore Parts Center.
The Remote Keypad Unit option consists of the follow-
ing components:
REMOTE KEYPAD UNIT SPECIAL PARAMETERS
The Remote Keypad Unit is an intelligent device con-
taining its own micro-computer, memory and special
parameters. Table 2 below lists these special param-
eters.
Ap Auto Powe Down
This special parameter sets the length of time, in min-
utes, before the Remote Keypad Unit turns itself off if
no keys are pressed. If a data code of 0 is entered, the
Auto Power Down feature is disabled and the RKU
will remain on indefinitely. Figure 8 shows a typical dis-
play for this parameter.
PARAMETER DESCRIPTION RANGE FACTORY
SETTING
Ap Auto Power Dow 0-10 1
bL Backlight Co trol 0-2 1
L RKU Software Revisio Level - 1.1
TABLE 2 PARAMETERS
TABLE 3 DATA CODES
DATA CODE DESCRIPTION
0The backlight is o whe ever the RKU is powered
1The backlight tur s o whe ever a key is pressed a d
tur s off 1 mi ute after the last key is pressed.
2The backlight is always off
Note: For maximum battery life select data code = 2.
PROGRAMMING THE SPECIAL PARAMETERS
To access these special parameters, press and hold the
PROGram key for two seconds from either the opera-
tion or programming mode. After initial application of
power, the first parameter displayed will be AP - Auto
Power Down.
The parameter block area can be accessed while the
RKU is connected or disconnected from an VS P
Drive. To program parameter AP - Auto Power Down
or bL - Backlight Control, use the following program-
ming method:
1. Press the UP/DOWN arrow keys to access the de-
sired parameter. The parameter number will be dis-
played in the upper left corner of the digital display.
2. Press the SHIFT key to allow the data code to be
changed. The PRG indicator will start to blink .
3. Press the UP/DOWN arrows to select the new data
code.
Note: To automatically load the current default data
code, press and release both the UP and DOWN
arrow keys simultaneously.
4. Press the ENTER key to store the new data code.
The display shows STOred for one second.
5. Press the UP/DOWN arrows to select a new pa-
rameter or press the PROGram key to return to
the operating mode.
LOW BATTERY POWER
The Remote Keypad Unit can be programmed to con-
serve power when operating from the 9 volt alkaline
battery (see parameters AP - Auto Power Down and
dL - Display Backlight). To protect the data and ensure
proper operation, the RKU will execute warning and
power conservation steps as outline in Table 4. Figure
11 shows the LCD display with the battery symbol ac-
tive indicating a low battery condition.
Proud Spo sor
of the 2000
U.S. Olympic Team
36USC380
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 1999 ALL RIGHTS RESERVED
Form 160.00-NO7 (599)
Supersedes: Nothing
FIG. 11 LOW BATTERY CONDITION
TROUBLESHOOTING
The display shown in Figure 12 indicates that an error
was detected during the transmission of data to or from
the RKU. If this condition occurs, check that the RKU
interconnection cable is properly installed and is not bro-
ken or worn. Replace if necessary.
FIG. 12 ERROR
BATTERY INDICATION DESCRIPTION
7.0 volts Battery symbol visible Backlight is automatically tur ed off.
5.8 volts Bla k display RKU automatically tur ed off.
TABLE 4
00102VIP
60.00
FWD
Hz
EFF
L Remote Keypad Unit Softwa e Revision
This parameter indicates the current revision level of
the RKU operating software. Figure 10 shows a typical
display with parameter rL shown.
FIG. 10 REVISION LEVEL
FL i.i0
PRG
FIG. 8 AUTO POWER DOWN
ap i
PRG
bL Backlight Cont ol
This parameter controls the operation of the display
backlight when the RKU is used under battery power.
Figure 9 shows a typical display for this parameter.
FIG. 9 BACKLIGHT
i
PRG
79
When the RKU is used with an VSOP
Drive having software revision 12 3,
a stop will be initiated when the Auto
Power Down function activates
FAULT CODES
The fault codes range in value from 1-22. They are dis-
played in parameter 7, 8, & 9. The time since the fault is
displayed (in tenths of an hour) as the right most digit.
The fault code is the two left most digits. (See Fig. 7)
07 139
FWD
DRIVE
DIRECTION
PARAMETER
NUMBER FAULT
CODE
TIME SINCE
LAST START
(TENTHS OF
AN HOUR)
FIG. 7 PARAMETERS