manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. YURAKU
  6. •
  7. Control Unit
  8. •
  9. YURAKU A-P 196 Setup guide

YURAKU A-P 196 Setup guide

YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
Safety and Installation Instructions
Safety and Installation InstructionsSafety and Installation Instructions
Safety and Installation Instructions
This document applies to the followin Yuraku Standard Modules:
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-P
P P
P 196
196196
196
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-P 2
P 2P 2
P 214
1414
14
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-P 2
P 2P 2
P 21
11
16
66
6
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-P 2
P 2P 2
P 220
2020
20
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-P 2
P 2P 2
P 225
2525
25
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-P 2
P 2P 2
P 230
3030
30
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-P 2
P 2P 2
P 260
6060
60
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-M
MM
M
182
182182
182
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-M
MM
M
204
204204
204
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-M
MM
M
2
22
227
2727
27
Yuraku
Yuraku Yuraku
Yuraku A
AA
A-
--
-M
MM
M
2
22
272
7272
72
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
General Installation Manual for Yuraku Photovoltaic Modules.
Please read this manual completely before installation or use of
YURAKU modules.
Important!
Read this instruction sheet in its entirety before installin , wirin , or usin this product in any
way. Failure to comply with these instructions will invalidate the YURAKU Limited Warranty for PV
Module.
1.0 Introduction
1.0 Introduction1.0 Introduction
1.0 Introduction
Thank you for choosin YURAKU photovoltaic modules. With proper operation and
maintenance, YURAKU PV modules will provide you with clean, renewable solar electricity for
many years.
This manual contains important installation, maintenance and safety information. The word
“module” as used in this manual refers to one or more PV modules. Retain this manual for
future reference.
1.1 Disclaimer of Liability
1.1 Disclaimer of Liability1.1 Disclaimer of Liability
1.1 Disclaimer of Liability
The installation techniques, handlin and use of this product are beyond company control.
Therefore, YURAKU does not assume responsibility and expressly disclaims liability for loss,
dama e, or expense arisin out of, or in any way connected with installation, operation, use, or
maintenance by usin this manual.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
YURAKU assumes no responsibility for any infrin ement of patents or other ri hts of third parties,
which may result from use of modules. No license is ranted by implication or under any patent
or patent ri hts. The information in this manual is believed to be reliable, but does not constitute
an expressed and/or implied warranty. YURAKU reserves the ri ht to make chan es to the
product, specifications, or manual without prior notice.
1.2 Limited Warranty
1.2 Limited Warranty1.2 Limited Warranty
1.2 Limited Warranty
Module limited warranties are described in the YURAKU warranty certificates obtainable at
www.yuraku.com.s
2.0 Safety Precautions
2.0 Safety Precautions2.0 Safety Precautions
2.0 Safety Precautions
Before installin this device, read all safety instructions in this document.
Dan er!
Module interconnects pass direct current (DC) and are sources of volta e when the module is
under load and when it is exposed to li ht. Direct current can arc across aps and may cause
injury or death if improper connection or disconnection is made, or if contact is made with
module leads that are frayed or torn. Do not connect or disconnect modules when current from
the modules or an external source is present.
• Before installin modules, contact the appropriate authorities to determine permissions,
installation and inspection requirements, which should be followed.
• All installations must be performed in compliance with the National Electrical Code
(NEC) and any applicable local codes and also be performed only by authorized
personnel.
• To avoid the hazard of electric shock and injury, cover the entire front surface of the PV
modules with a dense, opaque material such as a cardboard box, durin installation and
handlin of the modules or makin /breakin electrical connections.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
• To avoid the hazard of electric shock, work only in dry conditions, with dry modules and
adequate dry insulated tools.
• To avoid the hazard of electric shock and injury, be sure to completely round all
modules.
• Do not install or handle the modules when they are durin periods of hi h wind.
• Do not touch the junction box terminals to avoid the hazard of electric shock and injury.
• Remove all metallic jewelry prior to installin this product to reduce the chance of
accidental exposure to live circuits.
• The shock hazard increases as modules with nominal open-circuit volta e (Voc) in excess
of 50 V, and/or modules rated for maximum system volta e in excess of 50 V.
• The installer assumes the risk of all injury that mi ht occur durin installation, includin ,
without limitation, the risk of electric shock.
• Since sparks may occur, do not install the module where flammable ases or vapors are
present.
• Be sure that the construction or structure (roof, façade, etc.) has enou h stren th where
the modules are bein installed.
• For modules mounted on roofs, special construction or structures may be required to
help provide proper installation support.
• Both roof construction and module installation desi n have an effect on the fire
resistance of a buildin . Improper installation may contribute to fire hazards.
• Additional devices such as round fault, fuses, and disconnects may be required.
• Do not treat the back sheet or front surface with paint or adhesives, to avoid reducin its’
functionality, dama e, inoperable conditions, and other unknown troubles.
• Do not stand on, drop, scratch, or allow objects to fall on modules.
• If the front lass is broken, or the back sheet is torn, contact with any module surface or
module frame can cause electric shock.
• There are no user serviceable parts within the module. Do not attempt to repair any part
of the module.
• Do not artificially concentrate sunli ht on a module to avoid the hazard of fire or
dama e.
• Do not use modules of different specifications in the same system.
• Do not disconnect terminals while PV modules enerate electricity and connect electrical
load to avoid the hazard of electrical shock.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
• Follow all safety precautions of other system components used.
• Use a module for its intended purpose only.
• Contact your module supplier if maintenance is necessary.
3.0 Electrical Characteristics
3.0 Electrical Characteristics3.0 Electrical Characteristics
3.0 Electrical Characteristics
The module electrical ratin s are measured under Standard Test Conditions (STC) of 1 kW/m²
irradiance with AM 1.5G spectrum and a cell temperature of 25º C. YURAKU modules deliver
specific electrical characteristics.
A photovoltaic module may produce more current and/or volta e than reported at STC.
Sunny, cool weather and reflection from snow or water can increase current and power output.
Therefore, the values of Isc and Voc marked on the module should be multiplied by a factor of
1.25 when determinin component volta e ratin s, conductor ampacities, fuse sizes, and size of
controls connected to PV output. An additional 1.25 multiplier may be required by the NEC for
sizin fuses and conductors as described in the NEC Section 690-8.
3.1 Fire Ratin
3.1 Fire Ratin3.1 Fire Ratin
3.1 Fire Ratin
The module is Class C fire rated.
3.2 Bypass Diode Ratin
3.2 Bypass Diode Ratin3.2 Bypass Diode Ratin
3.2 Bypass Diode Ratin
The bypass diode of Junction Box is Tyco -SL1010, 40V, 11A rated.
4.0 Installation
4.0 Installation4.0 Installation
4.0 Installation
• Modules should be firmly fixed in place in a manner suitable to withstand all expected
loads, includin wind and snow loads.
• We recommend installation methods shown in Fi ure 1. In some areas, local electrical
codes may overn the installation and use of PV modules.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
Fi ure 1
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
5.0 Electrical Connections
5.0 Electrical Connections5.0 Electrical Connections
5.0 Electrical Connections
• Modules may be connected in series and/or parallel to achieve the desired electrical
output as lon as certain conditions are met. Please use only the same type of modules
in a combined source circuit.
• All connections should be secure, ti ht and electrically and mechanically sound.
• UV-resistant cables and connectors approved for outside use should be used. Ensure that
they are electrically and mechanically sound.
• Conductor au e should be chosen so as to ensure that DC power losses (volta e drop)
are kept to a minimum (less than 1% is preferred).
5.1 Equipment Groundin
5.1 Equipment Groundin5.1 Equipment Groundin
5.1 Equipment Groundin
To avoid electrical shock, round the frame of the module or array before wirin the circuit
usin a roundin method that meets NEC requirements for roundin solar electrical systems.
YURAKU recommends the followin two methods of roundin the module frame. Fi ure 2 is
for customer reference.
1) Usin an equipment round conductor with stainless steel hardware at one of the two
desi nated Φ3.8 roundin holes on the module frame. If a equipment round conductor
lar er in diameter than #10 AWG is necessary, a roundin lay-in lu is required. A thread-
formin 8-18 stainless steel screw is required when usin a self-drillin type screw to make the
frame round connection. Please refer to NEC Article 690 on roundin PV arrays for specific
requirements.
2) YURAKU modules can be rounded usin third-party roundin washer or clip systems
provided they have been tested and certified to meet UL 467 and UL 1703 requirement for
bondin / roundin systems and are installed accordin to the manufacturer’s specified
instructions.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
Fi ure 2
5.2 System Groundin
5.2 System Groundin5.2 System Groundin
5.2 System Groundin
• A wirin terminal or bondin location of module intended to accommodate a field
installed equipment- roundin conductor shall be identified with the appropriate symbol
(IEC 60417- 5019(DB:2002-10)) or shall have a reen-colored part.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
• To avoid alvanic corrosion, use of stainless steel fastenin materials are the preferred
choice, but alvanized or hot-dipped zinc plated fasteners are acceptable.
5.3 Module Wirin
5.3 Module Wirin5.3 Module Wirin
5.3 Module Wirin
• The modules may be wired in series to produce the desired volta e output. Do not
exceed the maximum system volta e indicated in the specification sheet of the modules.
• The modules may be combined in parallel to produce the desired current output. Each
series strin or module may be required to be fused prior to combinin with other strin s.
Please refer to the NEC Article 690 for additional fusin requirements.
• Modules shall not be wired in parallel without maximum over current protection.
• These modules contain factory installed bypass diodes. If these modules are incorrectly
connected to each other, the bypass diodes, cable, or junction box may be dama ed.
• In order to minimize volta e sur es which could be induced by indirect li htnin strikes,
DC cables of the same strin should be bundled to ether so that loops are kept as small
as possible. Strin confi urations should be checked before system commissionin . If the
open circuit volta e (Voc) and the short circuit current (Isc) deviates from the
specifications, this could indicate a confi uration fault. Correct DC polarity should be
observed at all times.
5.4 Array Wirin
5.4 Array Wirin5.4 Array Wirin
5.4 Array Wirin
• The term “array” is used to describe the assembly of several modules on a support
structure with associated wirin .
• National electrical codes and re ulations need to be followed when selectin cables.
For field connections, recommend usin minimum 4 mm
2
or #12 AWG copper wires
insulated for a minimum of 90°C.
• Cables should use UV-resistant cable ties, or other sunli ht-resistant device and are
insulated to withstand the maximum possible system open circuit volta e. Loose and
unsecured cables should be protected from mechanical dama e. Avoid, as far as
possible, exposin the cables to direct sunli ht.
• Check your local codes for requirements.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
5.5 Module Terminations
5.5 Module Terminations5.5 Module Terminations
5.5 Module Terminations
• A junction box as a terminal enclosure is equipped for electrical connections on YURAKU
modules.
• If two or more separable connectors are provided, they shall be confi ured or arran ed
so that the other and vice-versa will not accept the matin connector for one, if it will
result in an improper connection.
5.6 Conduit
5.6 Conduit5.6 Conduit
5.6 Conduit
• For applications where wire conduits are used, follow the applicable codes for outdoor
installation of wires in conduits. Minimum diameter of wire conduit is 4.0 mm
2
.
• Verify that all fittin s are properly installed to protect wires a ainst dama e and prevent
moisture intrusion
6.0 Module Mountin
6.0 Module Mountin6.0 Module Mountin
6.0 Module Mountin
The YURAKU Limited Warranty for PV Modules is contin ent upon modules bein mounted in
accordance with the requirements described in this section.
6.1 Site Considerations
6.1 Site Considerations6.1 Site Considerations
6.1 Site Considerations
YURAKU modules should be mounted in locations that meet the followin requirements:
Operating Temperature:
All YURAKU modules must be mounted in environments that ensure YURAKU modules will
operate within the followin maximum and minimum operatin temperatures:
Max. Operatin Temp. +85°C, +185°F
Min. Operatin Temp. -40°C, -40°F
Care should be taken to provide adequate ventilation behind the modules, especially in hot
environments.
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
Design Strength:
YURAKU modules are desi ned to meet a maximum positive (or upward, e. . wind) desi n
pressure of 2400 Pa and ne ative (or downward, e. . static load) desi n pressure of 5400 Pa
when mounted in one of the mountin confi urations specified in Section 6.2.
A desi n stren th of 2400 Pa corresponds approximately to a wind speed of 125 mph.
When mountin modules in snow-prone or hi h-wind environments, special care should be
taken to mount the modules in a manner that provides sufficient desi n stren th while meetin
local code requirements.
Excluded Operating Environments:
Certain operatin environments are not recommended for YURAKU modules and are excluded
from the YURAKU Limited Warranty for these modules.
• No YURAKU module should be mounted at a site where it may be subject to direct
contact with salt water. Recommended distance from the sea: 1.600 feet.
• YURAKU modules with an anti-reflective coatin on the lass should not be mounted in
basic environments (those which have a PH balance equal to or reater than 7). Basic
environments de rade the coatin , reduce module ener y ain and may cause a non-
uniform appearance. This is not a concern in most areas because most outdoor
environments are acidic and therefore do not pose a problem, but YURAKU recommends
that the site be checked before mountin the modules, especially in coastal settin s.
• Where YURAKU module could be exposed to sulfur or other corrosive chemicals, such as
near sulfur sprin s or volcanoes because of the dan er of corrosion.
6.2 Mountin Confi urations
6.2 Mountin Confi urations6.2 Mountin Confi urations
6.2 Mountin Confi urations
Modules may be mounted at any an le, from horizontal to vertical. Select the appropriate
orientation to maximize sunli ht exposure. Specific information on module dimensions and the
location of mountin and roundin holes is provided below (Fi ure 3).
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
Fi ure 3
In order to prevent water from enterin the junction box, which could present a safety hazard,
modules should not be mounted such that the front/top lass faces downward (e. ., on a
trackin structure that positions the modules with the junction box facin skyward durin sleep
mode).
Clearance between the module frames and structure or round is required to prevent wirin
dama e and allows air to circulate behind the module.
The module is only UL Listed for use when its factory frame is fully intact. Do not remove or alter
the module frame. Creatin additional mountin holes may dama e the module and reduce the
stren th of the frame.
For roof mountin , the assembly is to be mounted over a fire resistant roof coverin rate for the
application, and any slope less than 5 in/ft (127/305 mm) required to maintain a fire class
ratin .
YURAKU PTE LTD
11 Collyer Quay
#10-04 The Arcade
Sin apore 049317
www.yuraku.com.s
Modules may be mounted usin the followin methods only:
1) Frame Holes: Secure the module to the structure usin the factory mountin holes. Four 8mm
stainless steel bolts, with nuts, washers, and lock washers are recommended per module. Refer
to Table 2 for the module dimensions and hole locations. This method has been certified by a
third-party or anization accordin to UL 1703.
2) Pressure Clamps or Clips: Mount the module with the clips on the side frame of the module.
The side frames are attached to the lon er sides of the module. The centerline of the clips
should be 6 -15 from the end of the side frame. Installers should ensure the clamps are of
sufficient stren th to allow for the maximum desi n pressure of the module. Clips and clamps
are not provided by YURAKU.
3) End Mount: End mountin is the capture mountin of the len th of the module’s end frame to
a supportin rail. The end frames are on the shorter dimensions of the module.
The end-mountin rail and clips or clamps must be of sufficient stren th to allow for the
maximum desi n pressure of the module. Verify this capacity with the mountin system vendor
before installation.
7.0 Maintenance
7.0 Maintenance7.0 Maintenance
7.0 Maintenance
Inspect all modules annually for safe electrical connections, sound mechanical connection, and
freedom from corrosion. Periodically clean the module surface with water and a soft cloth or
spon e. Fin erprints may be removed with standard lass cleaner. Do not use harsh cleanin
materials such as scourin powder, steel wool, scrapers, blades, or other sharp instruments to
clean the lass surface of the module. Use of such materials will invalidate the product warranty.

This manual suits for next models

10

Popular Control Unit manuals by other brands

LIFE home integration ACER RG1R UNI DL Instructions and warnings for installation, use and maintenance

LIFE home integration

LIFE home integration ACER RG1R UNI DL Instructions and warnings for installation, use and maintenance

Emos P5630S manual

Emos

Emos P5630S manual

Beckman Coulter Power Express Aliquot Instructions for use

Beckman Coulter

Beckman Coulter Power Express Aliquot Instructions for use

Danfoss PCV-VFGS 2 DN 150-250 installation guide

Danfoss

Danfoss PCV-VFGS 2 DN 150-250 installation guide

Harvia Sentiotec A2 Instructions for installation and use

Harvia

Harvia Sentiotec A2 Instructions for installation and use

Monacor ATT-412PEU instructions

Monacor

Monacor ATT-412PEU instructions

ITR MUPASZ 710 plus user manual

ITR

ITR MUPASZ 710 plus user manual

Emerson AVENTICS 501 Series Installation and maintenance instructions

Emerson

Emerson AVENTICS 501 Series Installation and maintenance instructions

Pentair BAA A390-D.03 Select operating instructions

Pentair

Pentair BAA A390-D.03 Select operating instructions

Metal Work HDM user manual

Metal Work

Metal Work HDM user manual

JM Concept EOLIS 3000 Series user manual

JM Concept

JM Concept EOLIS 3000 Series user manual

CDVI ARD2/12 installation manual

CDVI

CDVI ARD2/12 installation manual

Control Techniques UD70 installation guide

Control Techniques

Control Techniques UD70 installation guide

Phoenix Contact PP-RJ Series datasheet

Phoenix Contact

Phoenix Contact PP-RJ Series datasheet

Wilo Smart Connect Module BT user manual

Wilo

Wilo Smart Connect Module BT user manual

Swidget WI008UWA quick start guide

Swidget

Swidget WI008UWA quick start guide

Grundig GSS SID 162 A Assembly instruction

Grundig

Grundig GSS SID 162 A Assembly instruction

Panasonic CF-BAP0128U operating instructions

Panasonic

Panasonic CF-BAP0128U operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.