ZIEHL UFR1001 User manual

ZIEHL industrie –elektronik GmbH + Co KG
Daimlerstr.13, 74523 Schwäbisch Hall, Germany
+ 49 791 504-0, info@ziehl.de, www.ziehl.de
Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection
Operating Manual UFR1001
updated: 2017-11-09/Fu
from Firmware: 1-04
UFR1001 12290-0702-05 Page
1
/ 25 www.ziehl.de
- Sealable voltage and frequency relay with integrated vector-surge relay
Quick installation guide
System disconnection of photovoltaic plants
See Quick installation system disconnection on photovoltaic plants
Applicable from software version: 12290-1401-02 (press key Set for 10s)
ATTENTION: new default setting 51,5 Hz for over-frequency from software version 1-04 and higher.
(To display software version press button "Set" for >10 s)
- archive data

UFR1001 12290-0702-05 Page
2
/ 25 www.ziehl.de
Table of contents
1Display and controls .............................................................................................................................. 3
2Factory settings and software version ................................................................................................. 4
3Application and brief description.......................................................................................................... 5
4Summary of the functions ..................................................................................................................... 5
5Connection diagram............................................................................................................................... 6
6Important notice ..................................................................................................................................... 6
7Mounting................................................................................................................................................. 7
8Detailed description ............................................................................................................................... 7
8.1 Description of the connections....................................................................................................... 7
8.2 Functional characteristics .............................................................................................................. 8
9Commissioning....................................................................................................................................... 9
9.1 Program setup............................................................................................................................... 9
9.2 Control chart................................................................................................................................ 10
9.3 Description of the parameters...................................................................................................... 15
9.4 Display mode (last decimal point off) ........................................................................................... 16
9.5 Menu mode (last decimal point on).............................................................................................. 16
9.6 Configuration mode (last decimal point flashes)........................................................................... 16
9.7 Configuring the alarms................................................................................................................. 16
9.8 Delay Enable On, Delay Display, vector surge configuration ....................................................... 18
9.9 Code lock .................................................................................................................................... 19
9.10 Sealing ............................................................................................................................... 19
9.11 Possible indications in display...................................................................................................... 20
10 Maintenance and repair........................................................................................................................ 21
11 Troubleshooting and measures .......................................................................................................... 21
12 Technical data ...................................................................................................................................... 22
13 Mounting type V4: ................................................................................................................................ 23
14 Quick installation system disconnection on photovoltaic plants..................................................... 24

UFR1001 12290-0702-05 Page
3
/ 25 www.ziehl.de
1 Display and controls
1
Sealable button + LED (yellow)
Press for >
2 s
LED ON - Lock activated
LED OFF - Lock
deactivated
2
Last decimal point (red)
Off
Display mode
Illuminated
Menu mode
Flashes
Configuration mode
3
LEDs relay status (yellow)
OFF
Relay is released
ON
Relay operating
4
LED vector surge (VSR, red)
OFF
Vector surge limit not exceeded
ON, A 2 8
Vector surge limit exceeded
FLASHING, 8A 2L8
Ready for reset after exceeding the limit
FLASHING, 8A 28
Reset delay 8dof 8running out
5
LEDs frequency / voltage limit value undercut / exceeded (red)
ON, 8A 18or 8A 28or 8Am
18or 8Am 28
Limit value undercut / exceeded
FLASHING, 8A1-L8or 8A2-L8
or 8Am1L8or 8Am2L8
Ready for reset after undercutting / exceeding the limit value
FLASHING, 8A 18or 8A 28
or 8Am 18or 8Am 28
Reset delay 8dof 8running out
OFF
Limit value not undercut / exceeded
6
Up / Down key (in display mode, normal state)
Press briefly
Change into the menu mode (see Point 8.5), display of alarm-counter
(down) and added time of alarms (up), pushing of key Set for 2s makes
a reset of stored values.
Press for > 2 s
Displays the MAX (Up) and MIN (Down) measurement; additionally
pressing the Set key for ≥ 2 s deletes the saved value
7
Set/Reset key (in display mode, normal state)
Press briefly
Displays the next measurement / alarm-counter
Press for > 2 s
Reset after locked alarm (manual restart)
(not possible if DoF Reset delay is expiring)
Press for > 4 s
Displays the program, e.g. 8Pr 18
Press for > 10 s
Displays the software version e.g. 800008
8
LEDs measurement allocation (yellow)
LEDs
Measurement
Lx and N ON
Voltage value (L1 against N, L2 against N, L3 against N)
Lx and Ly ON
Voltage value (L1 against L2, L2 against L3, L1 against L3)
Lx FLASHING quickly
Vector surge (L1, L2, L3)
L1 FLASHING
Frequency
9
Digital display 4-digits (red)
Depending on the program display, actual voltage, frequency, vector surge
Displays the alarm signals, e.g. 8A 18, 8a2-L8,…
Displays the errors with error code e.g. 8Err98

UFR1001 12290-0702-05 Page
4
/ 25 www.ziehl.de
2 Factory settings and software version
When changing programs, all parameters are reset to the factory settings.
Menu
point
Parameter / Unit
Factory setting
My
data
Pr1
Pr2
Pr3
Pr4
Pr5
AL1u
8Fvn 8(Function)
8™««k8
8™««k8
8™««k8
8™««k8
8™««k8
8aL1,8(Upper limit)
V
82648
84608
82648
84608
82648
8aL 18(Limit value)
V
81848
83208
81848
83208
81848
8aLm18(10 min mean value)
V
82538
84408
82538
84408
82538
8H 8(Hysteresis)
V
858
858
858
858
858
AL1F
8Fvn 8(Function)
8™««k8
8™««k8
8™««k8
8™««k8
8™««k8
8aL1,8(Upper limit)
Hz
851.508
851.508
851.508
851.508
851.508
8aL 18(Limit value)
Hz
847.508
847.508
847.508
847.508
847.508
8H 8(Hysteresis)
Hz
81.458
81.458
81.458
81.458
81.458
AL 1
8dal8(Alarm delay)
s
8 0.108
8 0.108
8 0.108
80.108
8 0.108
8dof 8(Reset delay)
s
8 308
8 308
8 308
8 308
8 308
8rel8(Relay function)
8 r8
8 r8
8 r8
8 r8
8 r8
AL2u
8Fvn 8(Function)
8™««k8
8™««k8
8™««k8
8aL2,8(Upper limit)
V
82648
84608
82648
8aL 28(Limit value)
V
81848
83208
81848
8aLm28(10 min mean value)
V
82538
84408
82538
84408
82538
8H 8(Hysteresis)
V
858
858
858
AL2F
8Fvn 8(Function)
8™««k8
8™««k8
8™««k8
8aL2,8(Upper limit)
Hz
851.508
851.508
851.508
8aL 28(Limit value)
Hz
847.508
847.508
847.508
8H 8(Hysteresis)
Hz
1.458
1.458
81.458
AL 2
8Al 28(Limit value)
°
5.08
5.08
8dal8(Alarm delay)
s
80.108
80.108
80.108
8dof 8(Reset delay)
s
8308
8308
8308
838
838
8rel8(Relay function)
8 r8
8 r8
8 r8
8 r8
8 r8
dEon
8deon8(Switch-on delay)
838
838
vsr
8vsr 8(Vector surge)
83ph8
83ph8
ddi
8ddi 8(Display delay)
s
80.58
80.58
80.58
80.58
80.58
Si
8U 8(Voltage)
V
82308
84008
82308
8 4008
82308
8F 8(Frequency)
Hz
850.008
850.008
850.008
850.008
850.008
8vsr 8(Vector surge)
°
80.08
80.08
Code
8 On8/8 off8
8 off8
8 off8
8 off8
8 off8
8 off8
8pin 8(Pincode)
85048
85048
85048
85048
85048
Display the program: Press the "Set" key for 4 s in the display mode.
Display the software version: Press the "Set" key for 10 s in the display mode.

UFR1001 12290-0702-05 Page
5
/ 25 www.ziehl.de
3 Application and brief description
The voltage and frequency relay UFR 1001 monitors the voltage and the frequency in one- or three-phase
voltage grids with or without N and, if required, switches rapidly off. The unit can be easily adapted to the
network operator's requirements.
With the integrated vector-surge relay, it is also suited for monitoring synchronous generators.
After selecting a basic program, the limits for over/undervoltage and the over/under frequency can be
programmed.
When using programs with vector-surge monitoring, the K2 relay only reports the vector surge.
4 Summary of the functions
Applications include monitoring the network in large photovoltaic plants, power system protection in
combined heat and power plants, also with synchronous generators
(vector surge) or in general, monitoring the network quality in systems, on machines or
in power supply systems.
The device complies with the requirements of the power suppliers for conventional
protection in low-voltage systems >30 kVA.
•4-digit digital display for voltages, frequency and vector surge
•Under and overvoltage monitoring 40…520 V
•Under and overfrequency monitoring 45.00…65.00 Hz
•Monitoring the voltage quality (10 minute mean average value)
•Vector-surge monitoring 2.0…20.0 °
•Response time adjustable 50 ms…60 s
•Reset delay (zero voltage maintenance) can be set 0…1000 s (Vector surge 3…240 s)
•Alarm-counter for up to 100 alarms (with measured value and reason)
•Added time of alarm up to 999 hours. Displays the time, alarms have been active (while supply voltage
applied only).
•LEDs for alarm signals, measurement value allocation and relay status
•2 output relays, each for frequency and/or voltage monitoring
•Relay function operating or idle current programmable
•Locked shutdown or auto-reset programmable
•External input for Enable / Reset
•Delay time for Enable input during vector-surge monitoring
•Easy to program with 5 selectable basic programs
•Code protection against manipulation of the setpoint values
•Sealing facility for set point values
•Control voltage AC/DC 24-270 V
•Distributor housing for panel mounting 4 TE, front-to-back size 69 mm
•Mounting on 35 mm mounting rails DIN EN 60715

UFR1001 12290-0702-05 Page
6
/ 25 www.ziehl.de
5 Connection diagram
3 phase
*with N PR1,PR5
without N PR2, PR4
1-phase (only PR3, no vector-surge monitoring)
6 Important notice
WARNING
Hazardous electrical voltage!
Can lead to electric shock and burns.
Before starting work, switch plant and device voltage-free.
The flawless and safe operation of a device requires that it is shipped and stored appropriately,
professionally installed and put into operation and operated according to its intended use.
Only people who are familiar with the installation, commissioning and operation and who have qualifications
corresponding to their job are permitted to work on the device. They must comply with the contents of the
operating instructions, the notices attached tothedevice and the relevant safety regulations for constructing
and operating electrical plants.
The devices are built and certified in accordance with EN 60255 and leave the factory in a safe and
technically flawless condition. To maintain this state you must comply with the safety regulations indicated
with "Caution" in the operating instructions. Non-compliance with the safety regulations can lead to death,
bodily injury or property damage on the device itself and on other devices and equipment.
If the information in the operating instructions is insufficient at any time, please contact us directly or
contact the representation responsible for you.
Instead of the industrial norms and stipulations stated in the operating instructions and applicable in Europe,
you must comply with the valid and applicable regulations in the country of utilization if the device is used
outside of the area of application.

UFR1001 12290-0702-05 Page
7
/ 25 www.ziehl.de
Caution! If the operating current execution is programmed for all relays, a failure of
the control voltage or the device will not be detected.
When using as a monitoring device, the operator must ensure that this error
is detected through periodic performance tests.
We recommend programming and correspondingly evaluating at least one relay
in closed-circuit (idle) current execution.
Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure
sufficient clearance to other devices or heat sources. If cooling is inhibited, e.g., through close
proximity to devices with increased surface temperature or interference with the cooling-air current,
the permissible ambient temperature is decreased.
Caution!
Before you apply mains voltage to the device, make sure that the permissible control
voltage Uson the side rating plate matches the mains voltage connected to the device!
7 Mounting
The device can be mounted:
•Distribution board or switch cabinet on 35 mm rails according to EN 60715
8 Detailed description
8.1 Description of the connections
Connection
Function
A1 and A2
Control voltage Us, see 12. Technical data
11, 12, 14
Relay K1, menu item 8AL1U.8, 8aL1F.8
21, 22, 24
Relay K2, menu item 8AL2U.8, 8aL2F.8
E1 –E2 (Pr 4-5)
Enable input
Floating opener
Contact closed = UFR 1001 disabled, no evaluation of voltage,
frequency and vector surge
Open = UFR 1001 enabled, voltage, frequency, and vector surge will
be evaluated
Y1 –Y2 (Pr 1-3)
external reset
Floating closing contact
Function same as pressing the Set/Reset key for >2 s
nc
Not used
N
Neutral conductor
L1
Phase L1
L2
Phase L2
L3
Phase L3

UFR1001 12290-0702-05 Page
8
/ 25 www.ziehl.de
8.2 Functional characteristics
Functional characteristics
Explanation
VSR display value
The highest measured value is always displayed. The display value is
reset to 0 by deleting the max. value and when resetting into the go
(good) state.
VSR MIN / MAX value
During a vector-surge alarm, the trigger value is always saved as the
max. value; it is available until the max. value is deleted.
Enable input
Only in Pr 4 and 5, closed = disabled, no evaluation of voltage,
frequency and vector surge
Delay Enable On time
Only in Pr 4 and 5, expires while starting the unit and after opening the
Enable input; during this time, no evaluation of voltage, frequency and
vector surge takes place
Reset delay
If an alarm is present while disconnecting the control voltage, after
reconnection the programmed reset delay, 8dof 8, runs out for the
respective alarm; whenever a reset delay time 8dof 8is expiring, it is
counted down in the display (shortest first)
Reset
Use the Reset key or interrupt the control voltage for > 5 s (comply
with reset delay)
Alarm-counter
The UFR records max. 50 alarms/relay (reason, measured value).
When only 1 alarm is used (function Fun off at AL2U and AL2F, 100
alarms are stored. In the memory with the highest number, the last
alarm is stored. LEDs show the reason of the alarm and the relay. The
7-segment-display shows the value, that has caused the alarm. At
overflow all memories are deleted.
Added Time of Alarm
The added time of alarms shows for every alarm, how long the relay
has been switched off because a limit had been exceeded. The
resolution of the record is 1 minute. Time is only added as long as
supply-voltage is applied. Readout in display mode under Ac. Up =
added time of alarms TAL, Down = alarm-counter Ac xx…Ac00
(xx=last alarm)

UFR1001 12290-0702-05 Page
9
/ 25 www.ziehl.de
9 Commissioning
9.1 Program setup
The suitable program must be set on the UFR 1001 in accordance with the application (see table). That is
taken care of during commissioning. If the UFR 1001 is sealed/locked (LED illuminated), it is not possible
to change the set program.
Pr
Connection
Limit AL1
Limit AL2
*1
3 AC with N
Voltage, mean value, frequency
Voltage, mean value, frequency
2
3 AC without N
Voltage, mean value, frequency
Voltage, mean value, frequency
3
1 AC with N
Voltage, mean value, frequency
Voltage, mean value, frequency
4
3 AC without N
Voltage, mean value, frequency
Vector surge
5
3 AC with N
Voltage, mean value, frequency
Vector surge
* factory set
Adjustment process:
•If present, remove seal (only authorised person)
•Switch on control voltage on UFR 1001
•Slightly lift the key cover and turn 180°
•Press buttons on the key cover until locked LED is off
•Switch off control voltage on UFR 1001
•Keep the Set key pressed and switch the control voltage on again
8Pr 1.8
•Release the Set key
•Set the program with the UP/DOWN keys
•Press the Set key
Device resets and starts
Hint: When changing programs, all parameters of the selected program are reset to "factory settings" (see
table "Factory settings"); only change the parameters after selecting the correct program.

UFR1001 12290-0702-05 Page
10
/ 25 www.ziehl.de
9.2 Control chart
8Pr 183AC with N AL1: Voltage, frequency AL2: Voltage, frequency
[ ] = Unit
Up/Down simultaneously sets the
value to Zero.
Code-Reset = 2 s Set when mains
are switched on. (Pin = 504)
Error messages:
Err5 = Hysteresis error
Err6 = Parameter error AL1U
Err7 = Parameter error AL2U
Err8 = Parameter error AL1F
Err9 = Parameter error AL2F
Display flashes
alternating
Display mode
Configuration mode
Menu mode

UFR1001 12290-0702-05 Page
11
/ 25 www.ziehl.de
8Pr 283AC without N AL1: Voltage, frequency AL2: Voltage, frequency
[ ] = Unit
Up/Down simultaneously sets the
value to Zero.
Code-Reset = 2 s Set when mains
are switched on. (Pin = 504)
Error messages:
Err5 = Hysteresis error
Err6 = Parameter error AL1U
Err7 = Parameter error AL2U
Err8 = Parameter error AL1F
Err9 = Parameter error AL2F
Display flashes
alternating
Display mode
Configuration mode
Menu mode

UFR1001 12290-0702-05 Page
12
/ 25 www.ziehl.de
8Pr 381AC with NAL1: Voltage, frequency AL2: Voltage, frequency
[ ] = Unit
Up/Down simultaneously sets the
value to Zero.
Code-Reset = 2 s Set when mains
are switched on. (Pin = 504)
Error messages:
Err5 = Hysteresis error
Err6 = Parameter error AL1U
Err7 = Parameter error AL2U
Err8 = Parameter error AL1F
Err9 = Parameter error AL2F
Display flashes
alternating
Display mode
Configuration mode
Menu mode

UFR1001 12290-0702-05 Page
13
/ 25 www.ziehl.de
8Pr 483AC without N AL1: Voltage, frequency AL2: Vector surge
[ ] = Unit
Up/Down simultaneously sets the
value to Zero.
Code-Reset = 2 s Set when mains
are switched on. (Pin = 504)
Error messages:
Err5 = Hysteresis error
Err6 = Parameter error AL1U
Err7 = Parameter error AL2U
Err8 = Parameter error AL1F
Err9 = Parameter error AL2F
Display flashes
alternating
Display mode
Configuration mode
Menu mode

UFR1001 12290-0702-05 Page
14
/ 25 www.ziehl.de
8Pr 583AC with N AL1: Voltage, frequency AL2: Vector surge
[ ] = Unit
Up/Down simultaneously sets the
value to Zero.
Code-Reset = 2 s Set when mains
are switched on. (Pin = 504)
Error messages:
Err5 = Hysteresis error
Err6 = Parameter error AL1U
Err7 = Parameter error AL2U
Err8 = Parameter error AL1F
Err9 = Parameter error AL2F
Display flashes
alternating
Display mode
Configuration mode
Menu mode

UFR1001 12290-0702-05 Page
15
/ 25 www.ziehl.de
9.3 Description of the parameters
Parameter
Display
Explanation
Adjustment range
Measured
quantity
8Al1U8
8AL2U8
8Al1F8
8AL2F8
Voltage monitor Alarm 1
Voltage monitor Alarm 2
Frequency monitor Alarm 1
Frequency monitor Alarm 2
Switching
function
8Fvn 8
With 8™««k8, an upper limit must be set in
addition
8•,,∆8,8w__r8,
8™««k8
Upper
limit
8al1, 8
Upper limit with switch function ™««k8,
when 8AL1:8<8AL 18Error message
8408… 82658
8408… 85208
845.008… 865.008
Limit value
8Al 18
8AL 28
Limits for the alarms, Alarm 1 for Relay K1 and
Alarm 2 for Relay K2
8408… 82658
8408… 85208
845.008… 865.008
Limit value
8Alm18
8ALm28
Limits for 10 minutes mean value, Alarm 1 for
Relay K1 and Alarm 2 for K2
8408… 82658
8408… 85208
Hysteresis
8H 8
Switching function: 8•,,∆8,8™««k8
240 (limit) - 10(Hysteresis) = 230 (Reset
value)
8w__r8,8™««k8
220 (Limit) + 10(Hysteresis) = 230 (Reset
value)
818… 8998
80.058… 85.008
Alarm
delay
(delay Alarm)
8dAL 8
An alarm is suppressed for the set time
(seconds)
80.058… 860.008
Reset
delay
(delay Off)
8dOF 8
Reset is delayed for the set time even with
restoration of voltage if a trigger was present
when disconnecting the control voltage (reset
not possible); this time (seconds) is always
counted down in the display
808… 810008
Relay function
8rEL 8
Idle current 8 r8:Relay is pulled up in good
state (= no alarm) and releases when the alarm
value is reached. Alarm even when the control
voltage is switched off.
Locked (locked) 8 r-L8:Reset only possible
through Reset
8R8
8A8
8r-L8
8A-L8
Operating current 8 a8:Relay has released
in good state and operates (attracts) when the
alarm value has been reached. No alarm when
the control voltage is switched off and during
device faults.
Locked (locked) 8 A-L8:Reset only possible
through Reset
Enable time
(delay On)
8dEon8
There is no evaluation this time; starts with
applying the control voltage and when opening
the Enable input
828… 8208
VSR
8 VSR8
81 Ph8: a vector surge on one phase leads to
an alarm
83 Ph8: a vector surge on all phases
simultaneously leads to an alarm
81 Ph8… 83 Ph8
delay Display
8ddi 8
Interval during which the display is updated in
the display mode,
80.18… 82.08

UFR1001 12290-0702-05 Page
16
/ 25 www.ziehl.de
9.4 Display mode (last decimal point off)
In the display mode, the UFR 1001 is in its normal state; here, depending on the program, the actual
voltage, the highest actual 10 minute mean value, the frequency or the vector surge is displayed. In
addition, the alarm signals (e.g., 8a1 8, 8a2-L8, 8am 28, …) and error codes (e.g. 8err98) are
displayed.
Function key
Set / Reset
Press briefly: Switches the measurement, alarm-counter
Press for > 2 s: Resets after locked alarm
(not possible if DoF Reset delay is expiring)
Press for > 4 s: Displays the program, e.g. 8Pr 18
Press for > 10 s: Displays the software version e.g. 800008
Function key
Up / Down
Press briefly: Changes into the menus mode
Display alarmcounter: Down = readout memories
Up = display added time of
Press for ≥2 s: Displays MAX and MIN measurements,
additionally pressing the Set key for ≥ 2 s deletes the saved values
9.5 Menu mode (last decimal point on)
The menu mode is used to select the menu items. If no key is pressed for 30 s, one automatically returns
to the display mode.
Function key
Set / Reset
Press briefly: Changes into the configuration mode
Press for ≥2 s: Returns to the display mode (the most recently set
values are then applied)
Function key
Up / Down
Press briefly: Selects menu item; switches to the
display mode
9.6 Configuration mode (last decimal point flashes)
The value of a parameter can be set in the configuration mode. The display continually alternates between
the parameter name and the currently set value until the Up/Down key is pressed, which changes the
value of the parameter. If no key is pressed for 2 s, the display starts alternating again.
If no key is pressed for 30 s (simulation mode 15 min), one automatically returns to the display mode (the
most recently set value is applied during this)
Function key
Set / Reset
Press briefly: The settings are applied; continues to next
parameter. After the last parameter, change into
menu mode
Press for ≥2 s: Returns to the display mode (the most recently
set values are then applied)
Function key
Up / Down
Press short/long: Changes the parameter value
(fast/slow)
Hint: Pressing the Up and Down keys simultaneously sets the adjustable value to zero. If you keep the Up or
Down key pressed while setting a value, the speed of the change in the display is accelerated.
9.7 Configuring the alarms
Adjustment process:
•Select the menu item with the Up/Down key until …
Display 8al1U.8
•Press the Set key
Display 8fvn 8/ 8•,,∆8(Function / switching function) flash alternately
•Set the desired switching function using the Up and Down keys
•Press the Set key

UFR1001 12290-0702-05 Page
17
/ 25 www.ziehl.de
Upper switch point, ONLY during window function! ( ™««k )
Display 8AL1,8/ 82648(Alarm 1 / Limit value) flash alternately
•Set the desired limit using the Up and Down keys
•Press the Set key
Display 8AL 18/ 81848(Alarm 1 / Limit value) flash alternately
(during window function ™««k - lower switch point)
•Set the desired limit using the Up and Down keys
•Press the Set key
Display 8H 8/ 858(Hysteresis / Value) flash alternately
•Set the desired value with the Up and Down keys
•Press the Set key
Display 8al1U.8
•Press Down key
Display 8al1F.8
•Press the Set key
Display 8fvn 8/ 8•,,∆8(Function / switching function) flash alternately
•Set the desired switching function using the Up and Down keys
•Press the Set key
Upper switch point, ONLY during window function! ( ™««k )
Display 8AL1,8/ 851.508(Alarm 1 / Limit value) flash alternately
•Set the desired limit using the Up and Down keys
•Press the Set key
Display 8AL 18/ 847.508(Alarm 1 / Limit value) flash alternately
(during window function ™««k - lower switch point)
•Set the desired limit using the Up and Down keys
•Press the Set key
Display 8alm18/ 82538(Alarm 1 10 min / Limit value) flash alternately
•Set the desired value with the Up and Down keys
•Press the Set key
Display 8H 8/ 80.058(Hysteresis / Value) flash alternately
•Set the desired value with the Up and Down keys
•Press the Set key
Display 8al1F8
•Press Down key
Display 8al 1.8
•Press the Set key
Display 8dal.8/ 80.10.8(Delay Alarm / Time) flash alternately
•Set the desired time using the Up and Down keys
•Press the Set key
Display 8dof .8/ 8308(Delay Off / Time) flash alternately
•Set the desired time using the Up and Down keys
•Press the Set key
Display 8rel 8/ 8 r8(Relay / Parameter) flash alternately
•Set the desired parameter using the Up and Down keys
•Press the Set key

UFR1001 12290-0702-05 Page
18
/ 25 www.ziehl.de
Display 8al 1.8
•Repeat configuration for Alarm 2
9.8 Delay Enable On, Delay Display, vector surge configuration
Adjustment process:
•Select the menu item with the Up/Down key until …
Display 8deon.8(Delay Enable On)
•Press the Set key
Display 8deon8/ 838(Delay Enable On / Time) flash alternately
•Set the desired time using the Up and Down keys
•Press the Set key
Display 8deon.8(Delay Enable On)
•Press Down key
Display 8 vsr.8(Vector surge)
•Press the Set key
Display 8 vsr8/ 81 PH8(Vector surge / Parameter) flash alternately
•Set the desired parameter using the Up and Down keys
•Press the Set key
Display 8 vsr.8(Vector surge)
•Press Down key
Display 8ddi.8(Delay display)
•Press the Set key
Display 8ddi8/ 0.58(Delay display / Current time) flash alternately
•Set the desired time using the Up and Down keys
•Press the Set key
Display 8ddi.8(Delay display)

UFR1001 12290-0702-05 Page
19
/ 25 www.ziehl.de
9.9 Code lock
Here, the set parameters can be protected by activating a code lock.
The device acknowledges an incorrect entry with 8err8(flashes three times).
Adjustment process:
•Select the menu item with the Up/Down key until…
Display 8Cod.8(Code lock)
•Press the Set key
Display 8Pin8/ 808(Pin / Pin code) flash alternately
•Use the Up and Down keys to set the saved pin code (factory setting is 8504.8)
•Press the Set key
•Set the desired code lock using the Up and Down keys:
o8 off8off, all parameters can be changed
o8 On8on, no parameters can be changed
•Press the Set key
Display 8Pin8/ 85048(Pin / Pin code) flash alternately
•Set the desired new pin code with the Up and Down keys
(caution: write down the pin code)
•Press the Set key
Code lock on, display 8 on8flashes three times
Code lock off, display 8 off 8flashes three times
Return to menu mode, menu item code lock
If there are any problems with the code lock (pin forgotten), the lock can be switched off and the pin can be
reset to 504 by keeping the Set key pressed while switching on the mains until Code /off appears in the
display.
9.10 Sealing
All the settings and the simulation mode can be locked.
If the LED is illuminated, the UFR 1001 is locked.
If an attempt is made in the locked state to change a setting, the display shows 8LOc 8for 3s.
Adjustment procedure Sealing/Lock ON (OFF):
•If present, remove seal (only authorised person)
•Slightly lift the key cover and turn 180°
•Keep keys pressed by pushing on the key cover (locked - LED flashes) until Locked –
LED is permanently OFF (ON)

UFR1001 12290-0702-05 Page
20
/ 25 www.ziehl.de
9.11 Possible indications in display
Display mode
8A1 ,8A 2 ,
8Am 18,8Am 28,
8A 1L8,8A 2L8,
8Am1L8,8Am2L8,
8Ac 8 ,8tal 8
Alarm1, Alarm2, Alarm1(10min), Alarm2(10min) active
in addition "L", (locked), Reset required to reset
alarm-counter, added time of alarms
8Err58…8err98
Error messages (see 11. Error messages and measures)
Menu mode / Configuration mode
8 U8
Voltage
8Al1U8,8al2U8
Alarms for voltage
8 F8
Frequency
8Al1F8,8al2F8
Alarms for frequency
8 Vsr8
Vector surge
8Fvn 8
Switching function
8Al 18,8al 28
Limits
8Al1,8,8al2,8
Upper limit during window monitoring
8•,,∆8
Monitoring exceeding of the limit value (Max)
8w__r8
Monitoring falling below the limit value (Min)
8™««k8
Monitoring the limit value of falling below and exceeding (window)
8H 8
Hysteresis
8dal 8
Alarm delay
8dof 8
Reset delay, Reconnection delay if an alarm is present when the UFR
1001 is shutting down (no reset possible); is always counted down in
the display
8rel 8
Relay function
8 R8,8 A8
Zero signal (idle) current, operating current
8 R-L8,8 A-L8
Zero signal current locked, operating current locked
8 on8,8 oFF8
On, Off
8Deon8
Delay Enable On, delay time during power up and after opening the
enable input
81 Ph8
Single-phase vector surge evaluation
83 ph8
Three-phase vector surge evaluation
8ddi 8
Delay display, to quiet down the display
8Si 8
Simulation
8Code8,8Loc 8
Code lock, sealed/locked
8Pin 8
Pin code (factory setting 504)
Table of contents
Other ZIEHL Measuring Instrument manuals

ZIEHL
ZIEHL MSF 220 SV User manual

ZIEHL
ZIEHL SPI1021 User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL MINIPAN NS43V User manual

ZIEHL
ZIEHL MINIPAN TR210 User manual

ZIEHL
ZIEHL TMU104V User manual

ZIEHL
ZIEHL TR640IP User manual

ZIEHL
ZIEHL MSF220K User manual

ZIEHL
ZIEHL MINIPAN 300 User manual

ZIEHL
ZIEHL TR660IP User manual