InstructionsforInstallationandUseof
theC3100/200/400ControlPanel
Version:1.0.1
Date: Oct. 2010
AboutThisManual
ThismanualisaguidetoinstallationandconnectionoftheC3100/200/400access
controloperatorpanel.Forhowtousethesoftwareoftheproduct,seeZKAccess4.0
UserManual.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
I
Contents
1ImportantSecurityInstructions.......................................................................1
1.1Important SecurityInstructions.................................................................1
1.2InstallationCautions.................................................................................2
2Introduction......................................................................................................5
2.1SystemFunctionParameters.....................................................................5
2.2ProductTechnicalParameters ...................................................................5
2.3ControlOperatorPanelIndicators.............................................................6
3ConnectionandInstallation..............................................................................8
3.1CaseInstallation.......................................................................................8
3.2InstallationofAccessControlOperatorPanelWires..................................9
3.3ControlOperatorPanelSystemInstallation .............................................10
3.4ControlOperatorPanelConnectionTerminals.........................................12
3.5ConnectionwithDoorSensors,ExitSwitches,andAuxiliaryInputDevices
...................................................................................................................16
3.6ConnectionwithWiegandReaders..........................................................18
3.7RelayOutputConnection........................................................................20
3.8AccessControlOperatorPanelSystemPowerSupplyStructure...............25
4AccessControlOperatorPanelSystemNetworking ......................................27
4.1AccessControlNetworkingWiresandWiring.........................................27
4.2TCP/IPNetworkCommunication............................................................29
4.3RS485NetworkCommunication ............................................................29
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
II
4.4 DIP Switch Setting (485 Address Setting, Factory Setting, and Terminal
ResistanceSetting).......................................................................................31
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
1
1ImportantSecurityInstructions
1.1ImportantSecurityInstructions
1. Read,followandkeepinstructions:Beforeoperatingtheequipment,readand
follow strictly all security and operation instructions. Please keep the
instructionsingoodconditionforfuturereference.
2. Accessories: Pleaseusetheaccessories recommendedbythemanufactureror
deliveredwiththeproduct. Anyotherrelated productisnotrecommendedas
the major alarming or monitoringsystem. The majoralarming ormonitoring
system should comply with the local applicable fireprevention and security
standards.
3. Installationcautions:Donotplacethisequipmentonanyunstabletable,tripod
mount, support or base, lest the equipmentshouldfall and get damaged, and
more undesirably cause severe personal injuries.Therefore, it isimportant to
installtheequipmentasinstructedbythemanufacturer.
4. Allperipheraldevicesmustbegrounded.
5. No external connection wirescan be exposed. All connectionsand idle wire
endsmustbewrappedwithinsulatingtapestopreventaccidentalcontactwith
exposedwiresfromdamagingtheequipment.
6. Repair:Donotattemptunauthorizedrepairoftheequipment.Disassemblyor
detachment is likely to cause shock or other risks. All repair jobs should be
donebyqualifiedrepairpersonnel.
7. Damagesinneed ofrepair:Inanyofthefollowingcases,firstdisconnectthe
AC/DC power supply from the equipment and notify qualified repair
personnel forrepairs:
Thepowercordorconnectorisdamaged.
Thereisentryofliquidoranyotherforeignobjectintotheequipment.
Theequipmentiswettedorexposedtobadweather(rain,snow,etc.).
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
2
If the equipment cannot work normally even though operated as
instructed,pleasebesuretoadjustonlythecontrolcomponentsspecified
in the operation instructions. Incorrect adjustment of other control
components may cause damage to the equipment, and add to
troubleshootingworkloadofthequalifiedtechnicians.
Theequipmentfallsdownoritsperformancechangesobviously.
8. Replacing components: If it is necessary to replace a component, the repair
personnelmustuseonlythesubstitutesspecifiedbythemanufacturer.
9. Security inspection: After the equipmentis repaired,the repair personnel are
supposed to conduct security inspection to ensure the equipment can work
normally.
10. Power supply: Operate the equipment with only the type of power supply
indicatedonthelabel.Contacttheoperatorforanyuncertaintyaboutthetype
ofpowersupply.
1.2InstallationCautions
1. Allwiresmustrunthroughcasingpipes,forexamplePVCorgalvanizedpipes,to
prevent failure causedby rodent damage.Although a control panel is designed
with good antistatic, lightningproof, andleakageproof functions, ensureits
chassisand the AC ground wireare connected properly and theAC ground
wireisgroundedphysically.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
3
2. It is recommended not to plug/unplug connectionterminals frequently when
the system is energized. Be sure to unplug the connection terminals before
startinganyrelevantweldingjob.
3. Do not detach or replace any control panel chip withoutpermission, because
unprofessionaloperationmaycausedamagetothecontrolpanel.
4. It is recommended not to connect any other auxiliary devices without
permission. All nonroutine operations must be communicated to our
engineersinadvance.
5. A control panel should not share one power socket with any other
largecurrentdevice.
6. Itispreferabletoinstallcardreadersandbuttonsatheightsof1.41.5m above
the ground, but the heights are subject to proper adjustment according to
customers’usualpractice.
7. It is advised to install control panels at places easy of maintenance, like a
weakelectricwell.
8. It is strongly recommended that the exposed part of any connection terminal
shouldnotbelongerthan4mm,andspecializedclampingtoolsmaybeused
to avoid shortcircuit or communication failure resulting from accidental
contactwithexcessiveexposedwires.
9. To save access control event records, read data periodically from control
panels.
10. Get prepared countermeasures according to application scenarios for
unexpectedpowerfailure,like selectingpowersupplywithUPS.
11. The connection between a card reader and a control panel should not be
longerthan100m.
12. The connection between a PC and a control panel should be shorter than
1200mforRS485communications.Alengthwithin600m isrecommendedto
makecommunicationsmorestable.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
4
13. To protect the access control system against the selfinduced electromotive
force generated by an electronic lock at the instant of switching off/on, it is
necessaryto connectadiodeinparallel (pleaseusetheFR107deliveredwith
thesystem) with theelectronic lockto releasethe selfinduced electromotive
forceduringonsiteconnectionforapplicationoftheaccesscontrolsystem.
14. It is recommended that an electronic lock and a control panel should use
respectivepowersupplies.
15. It isrecommended to usethe power supply delivered with the system asthe
controlpanelpowersupply.
16. Inaplacewithstrongmagneticinterference,galvanizedsteelpipesorshielded
cables arerecommended, andpropergroundingisrequired.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
5
2Introduction
Theaccesscontrolmanagementsystemisanewmodernizedsecuritymanagement
system,whichisaneffectivemeasureforsecurityandprotectionmanagement.Itis
mainlyusedtomanageentrancesandexitsofimportantplaces, suchas banks,hotels,
equipmentrooms,offices,smartcommunities,andfactories.
2.1SystemFunctionParameters
Highspeed32bit400MHzCPU,32MRAM,and256MFlash.
EmbeddedLINUXoperatingsystem.
Onedoor/twodoortwowayaccessorfourdooronewayaccess.
Amaximumof30,000cardholdersand100,000offlineeventrecords.
SupportofmultipleWiegandcardformatsandapasswordkeypad,compatible
withvarioustypesofcards.
Use of dual communication technologies: the Ethernet plus the RS485
industrialbus,forreliablecommunications.
Withawatchdog(hardware)builtin thecontrolpaneltopreventcrash.
Overcurrent, overvoltage, and inversevoltage protection for input of power
supplyto the controlpanel.
Overcurrentprotectionforthepowersupplytocardreaders.
Instantovervoltageprotectionforallinput/outputports.
Instantovervoltageprotectionforcommunicationports.
2.2ProductTechnicalParameters
Workingpowersupply:ratedvoltage12V(±20%)DC;ratedcurrent≤0.5A.
Workingenvironment:temperature0°C55°C;humidity10%80%.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
6
Outputload:workingvoltageAC≤30V,ratedcurrent≤8A;DC≤36V,rated
current≤5A.
Ctype electronic lock relay output terminal: 10A contact current, 12V DC,
withLEDstatusindications.
Outputterminaloftheauxiliaryrelay:2Acontactcurrent,30VDC,withLED
statusindications.
Withdetachableconnectionterminalsmadeofalloysteelnonmagneticflange
materials.
OutlinedimensionsofthecontrolPCB:160mm(length)×106mm(width)for
C3100/200;218mm(length)×106mm(width)forC3400.
MountingholedimensionsofthecontrolPCB:147.32mm(length)×91.44mm
(width)forC3100/200;203.2mm(length)×106mm(width)forC3400.
External boxdimensions:345mm×275mm×70mm.
2.3ControlOperatorPanelIndicators
WhentheC3100/200/400ispoweredon,normallythePOWERindicator(red)islit
constantly,theRUNindicator(green)flashes(indicatingthesystemisnormal),and
otherindicatorsarealloff.
Exceptthecasesasfollows:
1. LINK indicator (green): indicates proper TCP/IP connection if it is lit
constantly;
2. ACTindicator(yellow):indicatestransmissionofTCP/IPdataifitflashes;
3. TXindicator(yellow):indicatessendingof485dataifitflashes;
4. RXindicator(green):indicatesreceivingof485dataifitflashes;
5. Lock indicator (green): indicates unlocking if it is lit constantly (if the
auxiliary output indicator is lit in green constantly, it indicates the auxiliary
deviceisenabled);
6. CARDindicator(yellow):indicatesinputofWiegandsignalifitislit.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
7
SeetheC4indicatorsinthefollowingfigure:
Figure21IndicatorsintheC3400
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
8
3ConnectionandInstallation
3.1CaseInstallation
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
9
3.2InstallationofAccessControlOperatorPanel
Wires
Figure31 AccessControl OperatorPanelWireInstallationDiagram
Notes:
1. Before connection, make sure the power supply is disconnected, because
connectionwithpowerconnectedwillcauseseveredamagetotheequipment.
2. The access control wires must be separated according to heavy and light
current; the control panel wires, electronic lock wires, and exit button wires
mustrunthroughtheir respectivecasingpipes.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
10
3.3ControlOperator PanelSystemInstallation
TCP/IPEthernet Hub
Managementhost
Printer
Cardissuer
C3400 controloperatorpanel
Internal
button
Cardreader 1 Cardreader2 Cardreader3 Cardreader 4
Controllingonewayentry/exitoffourdoors
Controllingtwowayentry/exitoftwodoors
Door1 Door2 Door3 Door4
Door1 Door2
Internal
button
Internal
button
Internal
button
Figure32 SchematicDiagramofC3400SystemInstallation
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
11
Note: The diagram above takes the C3400 for example. By contrast, only
onedoor twoway access isapplicable tothe C3100 system; only twodoor
onewayortwodoortwoway accessisapplicabletotheC3200system.
The access control management system consists of two parts: management
workstation (PC) and control operator panel. They communicate via TCP/IP and
RS485 networks. On a 485 bus, each management workstation can be connected
with up to 63 C3 control operator panels (preferably fewer than 32). The
communication wires should be kept away from highvoltage wires as far as
possible,andshouldbe neitherroutedinparallelwithnorbundledwithpowerwires.
A management workstation isactually a PC connectedto the network. By running
the access control management software installed in the PC, access control
management personnel can remotely perform various management functions, like
adding/deleting a user, viewing event records, opening/closing doors, and
monitoringstatusofeachdoorinrealtime.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
12
3.4ControlOperator PanelConnectionTerminals
C3100terminalconnectiondiagram
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
13
C3200terminalconnectiondiagram
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
14
C3400terminalconnectiondiagram
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
15
Descriptionsoftheterminals:
1. The auxiliary input may be connected to infrared body detectors, fire
alarms,smokedetectors,etc.
2. The auxiliary output may be connectedto alarms, cameras, door bells,
etc.
3. Alltheterminalsmentionedabovearesetthroughrelevantaccesscontrol
software.Pleaseseetherespectivesoftwareinstructionsfordetails.
PortsontheC3control operator panel:
No. FunctionalPort
C3100
(OneDoor
TwoWay)
C3200
(TwoDoor
TwoWay)
C3400
(FourDoor
OneWay/TwoD
oorTwoWay)
1 Wiegand card reader
interface2 4 4
2 Exitbutton1 2 4
3 Controllockrelay1 2 4
4 Doorsensor1 2 4
5 Extensioninput× 2 4
6 Extensionoutput1 2 4
7 RS485 & PC
communication√ √ √
8 RS485 extension
communication× √ √
9 TCP/IP√ √ √
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
16
3.5ConnectionwithDoorSensors,ExitSwitches,and
AuxiliaryInputDevices
Doorsensor
A door sensorisusedtosensetheopen/closedstatusofadoor.Withadoor sensor
switch,anaccesscontrolpanelcandetectillegalopeningofadoor,andwilltrigger
an output of alarm. Moreover, if a door isnot closed within a specified period of
time after it is opened, the door control panel will also prompt an alarm. It is
recommendedtoselecttwocorewireswitha gauge over0.22mm
2
. Adoorsensormaybe
omittedifitisunnecessarytomonitoronlinetheopen/closedstatusofadoor,giveoutan
alarm whenthedoorisnot closed for a longtime orthere isillegal access, and use the
interlockfunction.
Exitswitch
Anexitswitchisaswitchinstalledindoorstoopenadoor.Whenitisswitchedon,
thedoorwillbeopened.Anexitbuttonisfixedataheightofabout1.4mabovethe
ground.Ensureitislocatedintherightpositionwithoutslant,anditsconnectionis
correct and secure.(Cut off the exposed end of any unused wireand wrap it with
insulating tape.) Note to guard against electromagnetic interference (such as light
switches and computers). Itisrecommended to usetwocorewireswith agaugeover
0.3mm
2astheconnectionwirebetweenanexitswitchandacontrolpanel.
Auxiliaryinput
C3100 provides no auxiliary input interface; C3200 provides two, and C3400
providesfour,whichareconnectedtoinfraredbodydetectors,smokedetectors,gas
detectors,windowmagneticalarms,wirelessexitswitches,etc.Auxiliaryinputsare
set through relevant access control software. For details, please see ZKAccess4.0
UserManual.
InstructionsforInstallationandUseoftheC3100/200/400ControlPanel
17
Figure33ConnectionsbetweenC3400andDoorSensors,ExitSwitches,and
AuxiliaryInputDevices

This manual suits for next models

4

Other ZKaccess Control Panel manuals

ZKaccess C3-200 User manual

ZKaccess

ZKaccess C3-200 User manual

ZKaccess Inbio460 User manual

ZKaccess

ZKaccess Inbio460 User manual

Popular Control Panel manuals by other brands

Fike FIK-RA100BD Product installation document

Fike

Fike FIK-RA100BD Product installation document

Erreka CLEVER02 Installer manual

Erreka

Erreka CLEVER02 Installer manual

Spectrum MULTISPORT 500 manual

Spectrum

Spectrum MULTISPORT 500 manual

Vallox Pureo quick guide

Vallox

Vallox Pureo quick guide

Miranda NV9640 user guide

Miranda

Miranda NV9640 user guide

Bentel Omnia user manual

Bentel

Bentel Omnia user manual

DSC Envoy NT9010DMK installation instructions

DSC

DSC Envoy NT9010DMK installation instructions

SeaLand VACUFLUSH Product guide

SeaLand

SeaLand VACUFLUSH Product guide

Zeta PREMIER EX8 user manual

Zeta

Zeta PREMIER EX8 user manual

Crow serenity Technician's handbook

Crow

Crow serenity Technician's handbook

Riello CPD 30 quick start guide

Riello

Riello CPD 30 quick start guide

ESAB A2 PEK instruction manual

ESAB

ESAB A2 PEK instruction manual

Sony RCP-3100 operating instructions

Sony

Sony RCP-3100 operating instructions

DMP Electronics XT Series Installation & quick start guide

DMP Electronics

DMP Electronics XT Series Installation & quick start guide

Honeywell MB-Secure 1000 installation instructions

Honeywell

Honeywell MB-Secure 1000 installation instructions

CAME ZE5 V.7 installation manual

CAME

CAME ZE5 V.7 installation manual

Risco LightSYS Quick user guide

Risco

Risco LightSYS Quick user guide

SILENTRON 4001 Centrale Sil-Bus 4A instruction manual

SILENTRON

SILENTRON 4001 Centrale Sil-Bus 4A instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.