ZKaccess Inbio460 User manual

www.ZKAccess.com

Safety Precautions
Product Contents
Product
PIN Diagram
LED
indicators
Product Dimensions
Installation of
Panel with Casing
Wire
Legend
Power
Wiring Diagram
FR1200 Connection
Weigand
Connection
Exit button Connection
Lock connection
Door
Sensor Connection
Aux. Input Connection
Aux. Output Connection
Ethernet Connection
RS485 Connection
DIP switch settings
Electrical
Specifications
Troubleshooting
Specifications
1
02
04
06
06
07
08
09
10
11
12
12
13
13
15
15
16
17
18
19
20
21

1
2
Safety Precautions
Do not install the device in an area
subject to direct sun light, Humidity
or dust
Do not place a magnet near the
product. Magnetic objects such as
magnet, CRT, TV, monitor or speaker
may damage the device.
Do not place the device next to
heating equipments
Be careful not to let liquid like
water, drinks or chemicals leak
inside the device.
Clean the device often to remove
dust on it
01 02 03
04 05 06
Do not let children touch the
device without supervision.
The list below is to keep user’s safety and prevent any loss. Please read carefully before installation.

3
Safety Precautions
The list below is to keep user’s safety and prevent any loss. Please read carefully before installation.
Do not drop the device. Do not use the device for any
other purpose than specified.
Do not disassemble, repair or
alter the device.
07 08
In cleaning, do not splash water
on the device but wipe it out with
smooth cloth or towel.
09
Contact your nearest dealer in
case of a trouble or problem.
Do not damage the device
10 11 12

4
Product Contents
Basic Contents
Inbio460
Wall Mounting Screws –2 pcs. Wall Plugs–2 pcs. Surge Suppressing Diode–4 pcs.
Screw Driver –2 pcs. Software CD InBio Installation Guide

5
Product Contents
Optional accessories
Weigand Card Reader Prox Card
Card Enroller
ZK4500 FP Enrollment reader
FR1200 FP Reader K1-1 Exit Button
Inbio Metal Case RS485 convertor

6
Product PIN Diagram
#4 Door Card
Reader
#4 Door Exit
Button
#3 Door Card
Reader
#3 Door Exit
Button
#2 Door Exit
Button
#2 Door Card
Reader
#1 Door Card
Reader
#1 Door Exit
Button
State Indictor
FR1200
Fingerprint
Reader
Aux Input 4
Aux Input 1
SD Card Slot
LINK LED
ACT LED
Ethernet Port
DIP Switch
PC RS485 Port
Aux Output 1
Aux Output 4
#1 Door Lock
#4 Door Sensor
Lock Power
Inbio Power
LED indicators
LINK
(Green)
LED solid green indicates
TCP/IP communication is
normal
ACT
(Yellow)
Flashing LED indicates data
communication is in progress
EXT RS485
(Yellow &
Green)
Flashing LED indicates data
communication in progress
PC RS485
(Yellow &
Green)
Flashing LED indicates data
communication is in progress
POWER
(Red)
Flashing LED indicates the
panel is powered on.
RUN
(Green)
Flashing LED indicates that
panel is in normal working
mode
CARD
(Yellow)
Flashing LED indicates that
the card is read by the panel.
#1 Door Sensor
#4 Door Lock

7
Inbio460
Product Dimension
Dimensions(L*W*H): 400 *90.5*330(mm)
InBio-Casing
226mm
(8.89in.)
106mm
(4.17in.)
106mm
(4.17in.) 36mm
(1.42in.)
Dimensions(L*W*H):226× 106× 36(mm)
8.89× 4.17× 1.42(inches)
400mm
(15.7in.)
330mm
(13.0in.)
330mm
(13.0in.) 90.5mm
(3.56in.)
15.7× 13.0× 3.56(inches)

8
Installation of Panel & Case
Metal Case

Wire Legend
9
Detector Infrared sensors FR1200 Inbio-Box #1Exit Button #1Card Reader #4 Exit Switch #4 Card Reader
12V
Power Supply
Normally Open LockNormally Close LockAlarm
Floodlight
RS485 Convertor
Network
12V DC
Power
DC

Power wiring diagram
10
With
Backup Battery
AC
AC
Switching power supply
Inbio460
AC
AC
Switching power supply
Inbio460
Backup Battery
+
-
110-220V
110-220V
Without
Backup Battery

FR1200 Connection
11
#1 FR1200 #2 FR1200 #3 FR1200 #8 FR1200
DIP Switch Setting For FR1200 Device ID
1. There are six DIP switches on the back of FR1200 , Switches 1-4 is for RS485
address , switch 5 is reserved , switch 6 is for reducing noise on long RS485 cable.
2. Set the odd number for IN reader, and the even number for OUT reader(for eg.
For two readers for one door- the RS485 address 1 is for IN reader, RS485 address
2 is for OUT reader )
3. If FR1200 is powered from Inbio460 panel ,the length of wire should be less
than 100 meters or 330 ft.
4. The External RS485 interface can supply maximum 500mA current , The
FR1200’s startup current is 240mA. So Inbio460 only can only power two FR1200s.
5. If the cable length is more than 200 meters or 600 ft , the number 6 switch
should be ON as below
Important Notes
12V DC
12V DC
Distance
More than 200 meters

Weigand Connection
12
Weigand Card Reader
Exit Button Connection
Beeper
Green LED
Weigand D1
Weigand D0
GND
DC+(6-14V)
BUT
GND
DV12V(+)
DV12V(-)
NO
COM
NC
separate power supply
Notice:
ZK ABK Exit Button
K1-1 Exit Switch
12V DC Power Supply

13
Lock Connection
12V DC
GND
Sensor
Sensor
12V DC
GND
GND
12V DC
Sensor
Sensor
GND
12V DC
FR107
FR107
For Normally Open -Lock powered from panel power supply
For Normally Closed -Lock powered from panel power supply

Lock Connection
14
Important Notes:
InBio is set to supply lock power by default from built-in
power supply , If you want to use external power supply ,
you must take the following steps
1. Take apart the cover of inbio460
2. Select the desired lock relay and find its jumpers
3. Take off the jumpers and change to
4. Connect the lock as shown in the diagram below.
Steps:
Inbio460 Detach from Rail Remove Top Cover Lock Relay
Terminals Default SettingChanged Setting Jumpers
FR107
GND
12V DC
SEN SEN GND 12V DC
5 1 15 5 1 15
Connecting a Lock with External Power supply
Switching Wet Contact to Dry Contact

15
Auxiliary Input/Output
Aux. Input Connection
Aux. output Connection
COM
NO
NC
GND
12V DC
COM
NO
NC
GND
12V DC
Smoke Detector
Alarm

16
Ethernet Connection
Direct connection
To connect Inbio460 with a PC directly, connect both devices with a straight network cable. As the Inbio460 supports auto MDI/MDIX ,
it is not necessary to use a crossover type cable.
Important Notes:
ZK4500 Enrollment
reader
CR10 Card Issuer
1. Both 10Base-T and 100Base-T
are supported
2. The cable length must be less
than 100 meters or 330 ft.
3. For more than 100 meters ,
please use HUB to amplify the
signal
TCP/IP
CR10 Card Issuer
ZK4500 Enrollment
reader
The CR10 and ZK4500 are connected to the server
using USB connection.

17
RS485 Connection
Important Notes
#1 Inbio460
#63 Inbio460
Do's and Dont's for RS 485 connection
RS485-
RS485+
GND
1. RS485 communication wires should be a shielded or twisted pair cable.
RS485 communication wires should be connected in a bus cascade instead
of a star form, to achieve a better shielding effect by reducing signal
reflection during communications.
2. A single 485 bus can be connected with 63 access control panels at the
most, but preferably less than 32 panels should be connected.
3. To eliminate signal attenuation in communication cables and suppress
interference, if the bus is longer than 200 meters, set the number 8 DIP
switch to the ON position. This is equivalent to a parallel connection of one
120ohm resistance between the 485+ and 485- lines.
Distance
More than 200 meters
#1 Inbio460 #* Inbio460

18
DIP Switch Setting
Introduction RS485 Address
1. Number 1-6 are reserved to set the device number for RS485
communication. The code is binary, and the numbering starts from left to
right. When the switch is set to ON position, it indicates 1 (on); when the
switch is set downwards, it indicates 0 (off). For example, to set a device
number 39=1+2+4+32, which corresponds to the binary code 111001, put
number 1, 2, 3, and 6 to ON position, as illustrated below.
2. For more details, please check the table at the end of this document
Restore factory setting
1. If you forget the inBio IP address or the device does not work
normally, you can use the number 7 terminal to restore inbio460 to
factory default settings. The parameters which gets reset are
device IP address, communication password ,gateway ,subnet mask.
2. The switch is OFF by default. When it is moved upwards and
downwards for three times within 10 seconds and finally returned
to OFF position, the factory settings will be restored after the
access control panel is restarted.
1 times 2 times 3 times OFF
Terminal Resistance
1. Number 8 is for setting the RS485 termination resistance. Putting the
switch to ON position is equivalent to parallel connection of a 120ohm
termination resistance between 485+ and 485-
2. As shown in diagram below, for more info please read RS485 connection
important notes
120ohm

Electrical Specification
19
Min. Typ. Max. Notes
Working power supply
Voltage(V) 9.6 12 14.4 Use regulated DC power adaptor only
Current(A) 2
Electronic lock relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 2
Auxiliary relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 1.25
Switch Aux. input
VIH (V) TBD
VIL (V) TBD
Pull-up resistance (Ω) 4.7k The input ports are pulled up with 4.7k resistors
WEIGAND Input
Voltage(V) 10.8 12 13.5
Current(mA) 500
ZK Electronic lock
Voltage(V) 10.8 12 13.2
Current(mA) 500
Other manuals for Inbio460
1
Table of contents
Other ZKaccess Control Panel manuals
Popular Control Panel manuals by other brands

NAPCO
NAPCO GEM-P800 installation instructions

Bosch
Bosch Solution 64 Installer's guide

Trox
Trox X-AIR-CP-2T operating instructions

Gira
Gira G1 Installation and operating instructions for the installer

Sartorius
Sartorius Arium Comfort I Quick start operating instructions

Fröling
Fröling RBG 3200 operating instructions