3M 5458A-IJ User manual

3M™ Cold Shrink Integrated Splice
Kit QS-III 5458A-IJ
for Jacketed Concentric Neutral (JCN) Cable
Instructions
IEEE Std. 404
25/28 kV Class
200 kV BIL
CAUTION
Working around energized systems may cause serious injury or death. Installation should
be performed by personnel familiar with good safety practice in handling electrical
equipment. De-energize and ground all electrical systems before installing product.
KitSelectionTable
Kit Number Cable Insulation O.D. Range Conductor Size Range
5458A-IJ 1.24"–2.07"
(31,5–52,6 mm)
500–1000 kcmil*
(240–500 mm2)
* Splices (including size transitions) can be made to smaller or larger conductors (but larger conductors may require special neutral
handling), provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements
shownbelow.
ConnectorDimensionalRequirements
Minimum Inches (mm) Maximum Inches (mm)
Outside Diameter 1.05" (26,7 mm) 2.07" (52,6 mm)
Length
Aluminum (Al/Cu) Compression —7.50" (191 mm)
Length
Copper Compression and
3M™ Shearbolt Connector QCI 500-1000
—8.25" (210 mm)
September2010
78-8127-8872-3-B3

2 78-8127-8872-3-B
1.0 Kit Contents
a. 3M™ColdShrinkIntegratedSpliceBody5458A-IJ(1ea.)
b. ConstantForceSprings(4ea.)
c. RedCompoundTubes(non-siliconegrease)(2ea.)
d. Scotch®RubberMasticTape2228Rolls,2"x48"(2ea.)
e. Scotch®MasticSealingStrips2230,6"length(8ea.)
f. ColdShrinkAdapterTube(1ea.*)
g. 3M™CableCleaningPadsCC-3(1ea.)
h. Scotch®ElectricalShieldingTape24,1"x15'(1ea.)
i. 3M™AluminumFoilTapeStrips1115B,10"length(2ea.)
j. Cut-backTemplate(2ea.**)
k. InstructionBooklet(1ea.)
*Cold shrink adapter tube may not be included in all kits.
**Kits contain either 1 or 2 cut-back templates as needed per conductor size.
Note: Do not use knives to open plastic bags.
Note: Connector not shown, but if included, it is indicated on the packaging label.

78-8127-8872-3-B 3
2.0 Prepare Cables
2.1 Checktobesurethecablefitswithinthekitrangesasshownonthecoverpage.
2.2 Preparecablesaccordingtostandardprocedures.Refertotemplateprovidedorillustrationbelowforproper
dimensions(Figure1).
“A”
“B”
3 1/2"
(89 mm)
Insulation
Semi-Con
Neutral Wires
Cable Jacket
Typical Conductor Size*
kcmil (mm2)
Insulation OD Range
Inches (mm)
Jacket Cutback "A"
Inches (mm)
Semi-con Cutback "B"
Inches (mm)
500**-750
(240-400)
1.24–1.70
(31,5–43,2)
15 3/4
(400)
9 1/4
(235)
1000**
(500)
1.59–2.07
(40,4–52,6)
15 1/4
(387 mm)
8 3/4
(222)
*For 100% and 133% insulation levels, Insulation OD is the final determining factor.
**Cables must be within the Insulation OD Range of the splice kit and the connector must meet the dimensional requirements shown on the front page.
Figure1
2.3 Carefullybendthecutneutralwiresupandawayfromthecablesemi-conasshown.FoldoneScotch®Mastic
SealingStrip2230inhalflengthwiseandapplyonewraponlyatcablejacketedgeundertheneutralwires
(Figure2).
Insulation
Semi-Con
Neutral Wires
Scotch® Mastic Sealing Strip 2230
Fold mastic strip in half lengthwise
Figure2

4 78-8127-8872-3-B
2.4 Markthecablesemi-con4"(102mm)fromthecablejacketedge.Applytwohalf-lappedlayersofScotch®
ElectricalShieldingTape24overthecablesemi-con,startingfromthemasticedgeouttothemarkonthe
semi-conandback.Half-hitchtotieoff(Figure3).
Insulation
Semi-Con
Neutral Wires
Scotch® Mastic Sealing Strip 2230
4"
(102 mm)
Scotch® Electrical Shielding Tape 24
Figure3
2.5 Carefullylayneutralwiresbackdownontopoftheshieldingtapeandpressintomastic.Keepwireprofilelow
byfollowingtheconcentricturninthecable(Figure4).
2.6 Removethelinerfromone3M™AluminumFoilTapeStrip1115Bandsecuretheendsoftheneutralwires.
Wrapthealuminumtapeontopofitselfandtightlypressdownontheedgeofthetapetowardtheendofthe
electricalshieldingtape(Figure4).
Insulation
Semi-Con
Neutral Wires
3M™ Aluminum Foil Tape Strip 1115B
Scotch® Electrical Shielding Tape 24
Press down edge tightly
Figure4

78-8127-8872-3-B 5
2.7 ApplyaScotch®MasticSealingStrip2230overthepreviouslyappliedmasticstripandoverlappingontothe
cablejacket.Kneadmasticaroundneutralwires.Overwrapmasticwithvinyltape,takingcarenottoextend
tapealongneutralwires(Figure5).
Scotch® Mastic Sealing Strip 2230
Overwrap with vinyl tape
Cable Jacket
Figure5
2.8 Cleanorcovercablejacket30"(760mm)fromjacketedgeonsidewheresplicebodywillbeparked.
2.9 Slideintegratedsplicebodyontocleancablejacket,loosecoreendfirst(Figure6).
Loose core end
Integrated splice body
Cleaned cable jacket
Figure6
3.0 Install Connector
Note: If using a crimp-type connector, go to step (3.3).
3.1 Ifusinga3M™ShearboltConnectorQCI500-1000,refertotheinstructionsincludedwiththeconnectorfor
insulationcut-backdimension.Insulationremovallengthshallnotexceed33/4"(95mm)fromconductorend
(Figure7).
Refer to connector instructions for dimensions
Figure7

6 78-8127-8872-3-B
3.2 Install3M™ShearboltConnectorQCI500-1000accordingtotheinstructionsincludedwiththeconnector
(Figure8).
Connector
Shearbolt
Figure8
Go to section 4.0 “Install Splice.”
3.3 Ifusingacrimptypeconnector,removecableinsulationfor1/2connectorlengthplusanallowance*for
increasesinconnectorlengthduetocrimping.Insulationremovallengthshallnotexceed4-1/8"(105mm)from
conductorend.Donotinstallconnectornow(Figure9).
*Note: This assumes that the installer has determined the increased length of an aluminum connector crimped
with a specific tool and die.
Aluminum (Al/Cu) Crimp Connector Growth Chart
Conductor Size Typical growth allowance (per end)
500 kcmil 1/4" (6 mm)
750–1000 kcmil 3/8" (10 mm)
Note: 1) Copper connectors do not require a length change allowance.
2) Maximum aluminum connector crimped length allowed is 8.25" (210 mm).
One-half connector length
+ growth allowance*
Figure9

78-8127-8872-3-B 7
3.4 For500kcmilcopperconnectors,orconnectorswithanO.D.between1.05–1.24"(26,7–31,5mm):
Parkcoldshrinkadaptertubeoncableinsulation(Figure10).
Cold shrink adapter tube
Figure10
3.5 Installconnector.Seetable(oncover)forproperconnectordimensions.(Forstandard3M™Connectors,refer
totableattheendofthisinstructionforcrimpinginformation).Removeanyexcessoxidationinhibitorfrom
connectorendsifaluminumconnectorisused(Figure11).
Connector
Figure11
4.0 Install Splice
4.1 Applyatapemarkertosemi-coninsulationshieldoncablewhichdoesnotcontainsplice.Measure11-1/2"
(292mm)fromcenterofconnector(Figure12).
Tape Marker
Semi-con
11 1/2"
(292 mm)
Figure12

8 78-8127-8872-3-B
4.2 Ifusingcoldshrinkadaptertube:Positionadaptertubeovertheconnector.Shrinkadapternearcenterof
connectorbypullingandunwindingtheloosecoreendinacounter-clockwisedirection(Figure13).
Cold shrink adapter tube
Figure13
4.3 Cleancablesusingstandardpractice:
a.Donotallowsolventorabrasivetocontactthecablesemi-conductiveinsulationshield.
b.Donotreducecableinsulationdiameterbelow1.24"(31,5mm)specifiedforthesplice.
c.Theinsulationsurfacemustberound,smoothandfreeofcuts/voids.Sandingmaybenecessary,finish
sandingshouldbedonewitha300gritorhigherelectricalgradeabrasive.
d.Makecertainthatthecableinsulationissmooth,cleananddrybeforecontinuing.
4.4 Applyredcompoundoncableinsulations,makingcertaintofillinedgeofcablesemi-con.Donotuse
siliconegrease(Figure14).
Apply Red
Compound
Apply Red
Compound
Fill semi-con step Fill semi-con step
Figure14

78-8127-8872-3-B 9
4.5 Positionthesplicebodyoverconnectorarea,aligningendofthesplicebody(notthecore)atthecenter
ofthetapemarker.Slowlystarttoremovethesplicecorebypullingandunwindingtheloosecoreend
counterclockwise,allowingonly¼"(6mm)ofthesplicetoshrinkontothetapemarker.Carefullyslidethe
splicebodyoffthetapemarkerbypullingandtwistinguntiltheentiretapemarkerisexposed.Continue
removingthecoretocompletethesplicebodyinstallation(Figure15).
Note: The splice body ends must overlap onto the semi-con of each cable by at least 1/2" (13 mm).
Note: Do not push the splice body toward the tape marker as this may cause the end to roll under. If the end
does roll under, DO NOT use sharp-edged tools to pull it out as this could cut and damage the splice.
Unwind Counter-clockwise
Align splice body with tape marker
Figure15
5.0 Connect Shielding
5.1 Removethevinyltapeholdingtheshieldsleeveontherejacketingtube,andspreadtheshieldsleeveouttoward
thecablejacket.
Note: The 3M™ Cold Shrink Integrated Splice Body includes a pre-installed ground braid for external
grounding on either side of the splice body. If not using the ground braid, it may be tied into the ground
system with the shield sleeve using constant force springs as shown below.
5.2 Hand-tightentheshieldsleeveoutwardandsecureit(alongwiththegroundbraidifnotgroundingexternally)
totheneutralwiresoneithersideofthespliceusingtwoconstantforcespringsoneachendbetweenthe
vinlytapeatthejacketedgeandthealuminumfoiltapeasshown.Trimexcessgroundbraidifneeded.Cinch
(tighten)thespringafterwrappingthefinalwinding(Figure16).
Ground Braid
Aluminum Foil Tape beneath Shield Sleeve
Constant Force Springs
Cable Jacket
Rejacketing Tube
Vinyl Tape
Figure16

10 78-8127-8872-3-B
5.3 Wraptwohalf-lappedlayersofvinyltapeovertheconstantforcesprings(Figure17).
Vinyl Tape
Figure17
6.0 External Grounding (Optional)
Note: Use these instructions if circuit grounding is required at this location.
6.1 Connectagroundwiretothepre-installedgroundbraidontheintegratedspliceusinganappropriateconnector.
Keepconnectorprofileaslowaspossible.ForC-taporH-tapconnectors,positionflatagainstthecable.Crimp
connectorfollowingtheconnectormanufacturer’srecommendations(Figure18).
Ground Wire
Connector
Ground Braid
Figure18

78-8127-8872-3-B 11
6.2 Cutonemasticsealingstripintotwoequalpieces.Placeonepieceonthecablejacketcenteredunderthe
groundwirenearthejacketend.Rolltwomasticstripsintosmallrolls.Placeonerolloneithersideofthe
groundwire.(Figure19).
Ground Wire
Ground Wire Rolled Mastic
Half Mastic Strip
Cable Jacket
Rolled Mastic
Half Mastic Strip
Figure19
6.3 Placetheotherhalfmasticstripoverthepreviouslyappliedmasticandgroundwire.Pressthemasticaround
thegroundwireandtothecablejacket(Figure20).
Second Half Mastic Strip
Ground Wire
Figure20
6.4 Wraptwohalf-lappedlayersofvinyltapeoverthegroundconnector(Figure21).
Vinyl Tape
Ground Wire
Mastic Seal for Ground Wire
Figure21

12 78-8127-8872-3-B
7.0 Install Jacket
Note: Jacketing is not optional.
7.1 WraparollofslightlystretchedScotch®RubberMasticTape2228,2"x36"aroundcablejacketends(tacky
sidetowardcable)(Figure22).Stretchandtearofflast1–2"(25–50mm)ofmastic(Figure23).Ifgrounding
wasapplied,applytapeovermasticstrips.
2" rubber mastic 2" rubber mastic
Figure22
Stretch and tear off last 1–2"
(25–50 mm) of rubber mastic
Figure23
7.2 Installthelargerrejacketingtubebyslowlypullingandunwindingthecorecounterclockwise.Thetubemay
needaslightpushtokeepitfromfoldingbackonitself(Figure24).
Unwind Counter-clockwise
Figure24

78-8127-8872-3-B 13
7.3 Installthesmallerrejacketingtubebyslowlypullingandunwindingthecorecounterclockwise.Thetubemay
needaslightpushtokeepitfromfoldingbackonitself(Figure25).
Unwind Counter-clockwise
Figure25
7.4 Connectoptionalgrounding.
Note: In applications where the splice is regularly exposed to high levels of ultra-violet radiation
(i.e. direct sunlight), wrap two half-lapped layers of Scotch® Super 33+™ Vinyl Electrical Tape or Scotch
Vinyl Electrical Tape Super 88 over the re-jacketing tubes.

14 78-8127-8872-3-B
Crimping Tool - Die Sets (number of crimps/end)
™M3
rotcennoC
rebmuN
rotcudnoC
eziS
)limck(
ydnru .B proCstteB&samohT .oCDerauqS
.viDnosrednA
A43Y 93Y,53Y
*64Y,*54Y **0001Y 8MBT 21MBT 51MBT **3-6CV
**TF-6CV **C8CV
)uC(4100 01 05 )2(R43 )A 2(TR43U — )3(nworB — )3(H78 )2( —
)uC/lA(4100 02 05 — )4(TRA43 )U 1( — )3(H601 )4(H601 )2( )2(
)uC(4101 01 05 )4(R43 )A 3(TR43U — )4(nworB — )4(H78 )3( —
)uC/lA(005-I 0C 05 — )3(TRA43U — — — )3(H601 )3( —
)uC/lA(6100 02 06 — )4(TRA63 )U 1( — — )3(H511 )3( )3(
)uC(9100 01 57 — )3(TR93U — — — )3(H601 — —
)uC/lA(9100 02 57 — )4(TRA93U — — — )5(H521 )3( )3(
)uC(9101 01 57 — )5(TR93U — — — )4(H601 — —
)uC/lA(057-I 0C 57 — )3(TRA93S — — — )3(H041 )3( —
)uC(4200 01 00 )—1 4(TR44P,TR44 )———S 3(H521 — —
)uC/lA(4200 02 00 )—1 4(TRA44P,TRA44 )———S 4(H041 — —
)uC(4201 01 00 )—1 4(TR44P,TR44 )———S 4(H521 — —
*Y45 and Y46 accept all Y35 dies ("U Series"). For Y45, use PT6515 adapter. For Y46, use PUADP adapter.
**Anderson VC6-3, VC6-FT, VC8C and Burndy Y1000 require no die set.

78-8127-8872-3-B 15

3M and Super 33+ are trademarks of 3M Company. Scotch is a registered trademark of 3M Company.
All other trademarks are property of their respective owners.
Important Notice
All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy
or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume
all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary
statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M.
Warranty; Limited Remedy; Limited Liability.
This product will be free from defects in material and manufacture for a period of one (1) year from the time of purchase. 3M MAKES NO OTHER
WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or
refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or con-
sequential loss or damage arising from this 3M product, regardless of the legal theory asserted.
3
Electrical Markets Division
6801 River Place Blvd.
Austin, TX 78726-9000
800-245-3573
Fax 800-245-0329
www.3M.com/electrical
Please Recycle. Printed in USA.
© 3M 2010. All Rights Reserved.
78-8127-8872-3-B
Other 3M Cables And Connectors manuals