Related documents
3AXD50000622467 Rev A EN 2020-04-21
© Copyright 2020 ABB. All rights reserved.
ACS355 user’s manual
3AUA0000066143
ACS355 manual list
9AKK107680A5563
Configure fieldbus communication (optional)
See the drive user’s manual.
ENTRY OF START-UP DATA (parameter group 99)
If you have an assistant control panel, select the
language. See parameter
9901
for the values of
the available language alternatives.
Select the motor type (
9903
).
1(
AM
): Asynchronous motor
2(
PMSM
): Permanent magnet synchronous
motor.
Setting of parameter
9903
is shown below as an
example of parameter setting with the basic
control panel.
1. To go to the Main menu, press if the
bottom line shows OUTPUT; otherwise press
repeatedly until you see MENU at the
bottom.
2.Press keys / until you see “PAr”.
3.Press . Panel changes to Parameter
mode.The display shows the number of one of
the parameter groups.
4.Find the appropriate parameter group (
99
)
with keys / .
5.Press . The display shows one of the
parameters in the selected group. Find the
appropriate parameter (
9903
) with keys
/.
6.Press and hold for about two seconds
until parameter value is shown with SET under
the value. If necessary, change the value with
keys / .
7. Save the parameter value by pressing .
Select the application macro (
9902
) according
to how the control cables are connected.
The default value 1 (
ABB STANDARD
) is suitable
in most cases.
Select the motor control mode (
9904
).
1(
VECTOR: SPEED
) suits most cases
2(
VECTOR: TORQ
) suits torque control
3(
SCALAR: FREQ
) suits if control accuracy is not
important, and for certain special cases. See
user’s manual. Not for permanent magnet
synchronous motors.
Enter the motor data from the motor
nameplate: motor nominal voltage (
9905
),
nominal motor current (
9906
), motor nominal
frequency (
9907
), motor nominal speed (
9908
),
motor nominal power (
9909
)
…
Select the motor identification method (
9910
).
The default value 0 (
OFF/IDMAGN
) using the
identification magnetization is suitable for
most applications. It is applied here. (Requires
also that
9904
is set to 1 (
VECTOR: SPEED
) or
2(
VECTOR: TORQ
)).
IDENTIFICATION MAGNETIZATION WITH ID RUN SELECTION 0 (
OFF/IDMAGN
)
Press key to switch to local control (LOC
shown on the left).
Press to start the drive. The motor model
is now calculated by magnetizing the motor for
10 to 15 s at zero speed.
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
1. If the drive is in remote control (REM shown
on the left), switch to local control by pressing
.
2. To go to the Main menu, press if the
bottom line shows OUTPUT; otherwise press
repeatedly until you see MENU at the
bottom.
3.Press keys / until you see “rEF”
and press .
4.Increase the frequency reference from zero to
a small value with key .
5.Press to start the motor.
6.Check that the actual direction of the motor is
the same as indicated on the display (FWD
means forward and REV reverse).
7. Press to stop the motor.
To change the forward and reverse rotation
directions (with a parameter):
Invert the phases by changing the value of
parameter
9914
to the opposite, ie, from 0 (
NO
)
to 1 (
YES
), or vice versa.
Verify your work by repeating the rotation
direction check as described above.
SPEED LIMITS AND ACCELERATION/DECELERATION TIMES
Set the minimum speed (
2001
), maximum speed
(
2002
), acceleration time 1 (
2202
), and
deceleration time 1 (
2203
)
SAVING A USER MACRO AND FINAL CHECK
The start-up is now completed. If you want to
save your setting as a user macro, scroll to
Parameter 9902 and select value USER S1 SAVE.
Check that there are no faults or alarms shown
on the display.
The drive is now ready for use.
Fault codes
This is a short list of fault messages.
Ratings
Fuses and typical power cable sizes
The table list the fuses for protection against short-circuits in the input power
cable or drive. The table also shows typical power cable sizes.
Ambient conditions
Fault Description
0001 OVERCURRENT - Output current has exceeded trip level.
0002 DC OVERVOLT - Excessive intermediate circuit DC voltage.
0003 DEV OVERTEMP - Drive IGBT temperature is excessive.
0004 SHORT CIRC - Short-circuit in motor cable(s) or motor.
0006 DC UNDERVOLT - Intermediate circuit DC voltage is not sufficient.
0009 MOT OVERTEMP - Motor temperature estimation is too high.
0016 EARTH FAULT - Drive has detected earth (ground) fault in motor or motor cable.
0022 SUPPLY PHASE - Intermediate circuit DC voltage is oscillating due to missing
input power line phase or blown fuse.
0044 SAFE TORQUE OFF - STO (Safe torque off) requested via STO terminal and it
functions correctly. Parameter 3025 STO OPERATION is set to react with fault.
ACS355-…
x = E/U
Input Input with
choke
Output Frame
size
I
1N
I
1N
(480 V)
I
1N
I
1N
(480 V)
I
2N
I
2,1/10
I
2max
P
N
AAAAA A AkWhp
1-phase
U
N= 230 V (200…240 V)
01x-02A4-2 6.1 - 4.5 - 2.4 3.6 4.2 0.37 0.5 R0
01x-04A7-2 11 - 8.1 - 4.7 7.1 8.2 0.75 1 R1
01x-06A7-2 16 - 11 - 6.7 10.1 11.7 1.1 1.5 R1
01x-07A5-2 17 - 12 - 7.5 11.3 13.1 1.5 2 R2
01x-09A8-2 21 - 15 - 9.8 14.7 17.2 2.2 3 R2
3-phase
U
N= 230 V (200…240 V)
03x-02A4-2 4.3 - 2.2 - 2.4 3.6 4.2 0.37 0.5 R0
03x-03A5-2 6.1 - 3.5 - 3.5 5.3 6.1 0.55 0.75 R0
03x-04A7-2 7.6 - 4.2 - 4.7 7.1 8.2 0.75 1 R1
03x-06A7-2 12 - 6.1 - 6.7 10.1 11.7 1.1 1.5 R1
03x-07A5-2 12 - 6.9 - 7.5 11.3 13.1 1.5 2 R1
03x-09A8-2 14 - 9.2 - 9.8 14.7 17.2 2.2 3 R2
03x-13A3-2 22 - 13 - 13.3 20.0 23.3 3 3 R2
03x-17A6-2 25 - 14 - 17.6 26.4 30.8 4 5 R2
03x-24A4-2 41 - 21 - 24.4 36.6 42.7 5.5 7.5 R3
03x-31A0-2 50 - 26 - 31 46.5 54.3 7.5 10 R4
03x-46A2-2 69 - 41 - 46.2 69.3 80.9 11.0 15 R4
3-phase
U
N= 400/480 V (380…480 V)
03x-01A2-4 2.2 1.8 1.1 0.9 1.2 1.8 2.1 0.37 0.5 R0
03x-01A9-4 3.6 3.0 1.8 1.5 1.9 2.9 3.3 0.55 0.75 R0
03x-02A4-4 4.1 3.4 2.3 1.9 2.4 3.6 4.2 0.75 1 R1
03x-03A3-4 6.0 5.0 3.1 2.6 3.3 5.0 5.8 1.1 1.5 R1
03x-04A1-4 6.9 5.8 3.5 2.9 4.1 6.2 7.2 1.5 2 R1
03x-05A6-4 9.6 8.0 4.8 4.0 5.6 8.4 9.8 2.2 3 R1
03x-07A3-4 12 9.7 6.1 5.1 7.3 11.0 12.8 3 3 R1
03x-08A8-4 14 11 7.7 6.4 8.8 13.2 15.4 4 5 R1
03x-12A5-4 19 16 11 9.5 12.5 18.8 21.9 5.5 7.5 R3
03x-15A6-4 22 18 12 10 15.6 23.4 27.3 7.5 10 R3
03x-23A1-4 31 26 18 15 23.1 34.7 40.4 11 15 R3
03x-31A0-4 52 43 25 20 31 46.5 54.3 15 20 R4
03x-38A0-4 61 51 32 26 38 57 66.5 18.5 25 R4
03x-44A0-4 67 56 38 32 44 66 77.0 22.0 30 R4
3AXD00000353783 L
I
1N continuous rms input current (for dimensioning cables and fuses)
I
1N (480 V) continuous rms input current (for dimensioning cables and fuses) for drives with
480 V input voltage
I
2N continuous rms current. 50% overload is allowed for one minute every ten
minutes.
I
2,1/10 maximum (50% overload) current allowed for one minute every ten minutes
I
2max maximum output current. Available for two seconds at start, otherwise as long
as allowed by the drive temperature.
P
Ntypical motor power. The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
ACS355-…
x = E/U
Fuses Size of copper conductor
gG UL
Class T
or CC
(600 V)
Supply
(U1, V1, W1)
Motor
(U2, V2, W2)
PE Brake
(BRK+, BRK-)
AAmm
2AWG mm2AWG mm2AWG mm2AWG
1-phase
U
N= 230 V (200…240 V)
01x-02A4-2 10 10 2.5 14 0.75 18 2.5 14 2.5 14
01x-04A7-2 16 20 2.5 14 0.75 18 2.5 14 2.5 14
01x-06A7-2 16/201) 25 2.5 10 1.5 14 2.5 10 2.5 12
01x-07A5-2 20/251) 30 2.5 10 1.5 14 2.5 10 2.5 12
01x-09A8-2 25/351) 35 6102.512610612
3-phase
U
N= 230 V (200…240 V)
03x-02A4-2 10 10 2.5 14 0.75 18 2.5 14 2.5 14
03x-03A5-2 10 10 2.5 14 0.75 18 2.5 14 2.5 14
03x-04A7-2 10 15 2.5 14 0.75 18 2.5 14 2.5 14
03x-06A7-2 16 15 2.5 12 1.5 14 2.5 12 2.5 12
03x-07A5-2 16 15 2.5 12 1.5 14 2.5 12 2.5 12
03x-09A8-2 16 20 2.5 12 2.5 12 2.5 12 2.5 12
03x-13A3-2 25 30 6106106102.512
03x-17A6-2 25 35 6106106102.512
03x-24A4-2 63 60 10 8 10 8 10 8 6 10
03x-31A0-2 80 80 16 6 16 6 16 6 10 8
03x-46A2-2 100 100 25 2 25 2 16 4 10 8
3-phase
U
N= 400/480 V (380…480 V)
03x-01A2-4 10 10 2.5 14 0.75 18 2.5 14 2.5 14
03x-01A9-4 10 10 2.5 14 0.75 18 2.5 14 2.5 14
03x-02A4-4 10 10 2.5 14 0.75 18 2.5 14 2.5 14
03x-03A3-4 10 10 2.5 12 0.75 18 2.5 12 2.5 12
03x-04A1-4 16 15 2.5 12 0.75 18 2.5 12 2.5 12
03x-05A6-4 16 15 2.5 12 1.5 14 2.5 12 2.5 12
03x-07A3-4 16 20 2.5 12 1.5 14 2.5 12 2.5 12
03x-08A8-4 20 25 2.5 12 2.5 12 2.5 12 2.5 12
03x-12A5-4 25 30 6106106102.512
03x-15A6-4 35 35 6868682.512
03x-23A1-4 50 50 10 8 10 8 10 8 6 10
03x-31A0-4 80 80 16 6 16 6 16 6 10 8
03x-38A0-4 100 100 16 4 16 4 16 4 10 8
03x-44A0-4100100254254164108
3AXD00000353783 L
1) If 50% overload capacity is needed, use the larger fuse alternative.
Requirement During operation (installed for stationary use)
Installation altitude 0…2000 m (0…6562 ft) above sea level (with output derating
above 1000 m [3281 ft])
Surrounding air
temperature
-10…+50 °C (14…122 °F). If the temperature is more than 40 °C
(104 °F), output derating is necessary. No frost permitted.
Relative humidity 0…95% without condensation
Dimensions and weights
Free space requirements
Markings
The applicable markings are shown on the type designation label.
Declaration of conformity
The drive is equipped with a Safe torque off function (STO). If you implement,
start up, use or maintain a system that uses the STO, read and obey the STO
instructions in the drive user’s manual.
Contamination levels
(IEC 60721-3-3: 2002)
No conductive dust permitted
Shock (IEC 60068-2-27,
ISTA 1A)
Not permitted
Free fall Not permitted
IP20 (cabinet) / UL open
Frame
size
H1 H2 H3 W D Weight
mm in mm in mm in mm in mm in kg lb
R0 169 6.65 202 7.95 239 9.41 70 2.76 161 6.34 1.2 2.6
R1 169 6.65 202 7.95 239 9.41 70 2.76 161 6.34 1.4 3.0
R2 169 6.65 202 7.95 239 9.41 105 4.13 165 6.50 1.8 3.9
R3 169 6.65 202 7.95 236 9.29 169 6.65 169 6.65 3.1 6.9
R4 181 7.13 202 7.95 244 9.61 260 10.24 169 6.65 5.2 11.5
IP20 / NEMA 1
Frame
size
H4 H5 W D - Weight
mm in mm in mm in mm in - - kg lb
R0 257 10.12 280 11.02 70 2.76 169 6.65 -- 1.6 3.5
R1 257 10.12 280 11.02 70 2.76 169 6.65 -- 1.8 3.9
R2 257 10.12 282 11.10 105 4.13 169 6.65 -- 2.2 4.8
R3 260 10.24 299 11.77 169 6.65 177 6.97 -- 3.7 8.2
R4 27010.6332012.6026010.24 177 6.97 -- 5.8 12.9
3AXD00000353783 L
IP20 (cabinet) / UL open
H1 height without fastenings or clamping plate
H2 height with fastening and without clamping plate
H3 height with fastenings and clamping plate
Wwidth
Ddepth
IP20 / NEMA 1 (drive with optional MUL-xx kit installed)
H4 height with fastenings and connection box
H5 height with fastenings, connection box and hood
Above Below Sides
mm in mm in mm in
75 3 75 3 0 0
3AXD00000353783 L
CE UL RCM EAC WEEE EIP TÜV Nord
Requirement During operation (installed for stationary use)