ABB ED83368-30 User manual

Page 1
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Micro-BDCBB DC Battery Distribution Circuit
Breaker Bay ED83368-30
600 A, −48V / +24V, 19” or 23”
Notes:
1. Group 1 – Field conversion to Dual buses is not supported.
19” 14 1 or 2 1 or 2 108992070 3
19” 14 221VIM1 CC109145455 4
19” 14 211VIM1 CC109145447 8
23” 22 - 1 or 2 1108991056 1
23” 22 221 or 2 VIM1 CC109145463 2
1
1 Shunts, when provided, are two 600A shunts, one on each side - A Bus (left) and B bus (right). The VIM1 meter sums the two shunts for one battery bus
configurations.
QUICK START GUIDE

Page 2
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Figure 1 Group 1 23" Panel with 477D Alarm Card
Figure 2 Group 8 19” Panel with VIM1 Meter
QUICK START GUIDE
Front Panel Screw Alarm LED

Page 3
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Figure 3 Wall Mounting Bracket CC848786401
Figure 4 Accessory Items
QUICK START GUIDE

Page 4
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Installation Notes
1. Follow all Installation Notes. Read before installing, maintaining, or repairing the equipment.
2. Follow all site specific installation notes and instructions.
3. Mount to grounded frame using 12-24 screws provided.
Grounding for the equipment is through this connection to the frame. Make sure frame is properly grounded.
4. Do not install this equipment over combustible surfaces.
5. Follow NEC, and local and national codes and rules.
6. Use a personal ESD strap when accessing or removing electronic components.
7. Use only protectors and holders specified in the equipment Ordering Guide.
8. Size protectors (fuses or circuit breakers) as required by the National Electric Code (NEC) and/or local codes. Refer to the
equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 64% of protector rating
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
9. Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations when making field
connections.
• Size field-wired conductors based on listed recommendations, National Electric Code (NEC) and/or local codes based
on 70°C ampacity.
• Insulation rating: 90°Cminimum; 105°C (minimum) if internal to enclosed equipment cabinets.
10. Bonding Network - Suitable for installation as part of either
• Common Bonding Network (CBN)
• Isolated Bonding Network (IBN)
11. Facilities - Suitable for installation in
• Network Telecommunication Facilities
• Locations where the NEC applies
12. DC Return - Isolated DC Return (DC-I) or Common DC Return (DC-C)
13. Intra-building ports - Equipment and subassembly ports are suitable for connection to intra-building or unexposed wiring
or cabling. The equipment and subassembly ports can be connected to shielded intra -building cabling grounded at both
ends.
Note: If a panel using the VIM1 meter shows a “Shunt Mis-Wired” alarm message when being used in a +24VDC
system, it will be necessary to swap/reverse the polarity of the monitored shunt pairs(s):
• For Shunt 1, the shunt pair is S and S/W. Cust this pair in the vicinity of J1 at the VIM1 meter and butt-splice S to S/W and
S/W to S to reverse the input signal polarity.
• For Shunt 2, the shunt pair is BL and BL/W. Cut this pair in the vicinity of J1 at the VIM1 meter and butt-splice BL to BL/W
and BL/W to BL to reverse the input signal polarity.
QUICK START GUIDE

Page 5
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Convert Battery and Return from 1 bus to 2 buses – Group 3
only
Notes: 1. Not applicable to panels with VIM1 meter which must be factory configured for single or dual bus.
2. Not applicable to Group 1which is single bus only.
Battery and return buses may be converted in configurations bridging bus bars.
1. Remove nuts and washers securing bridging Bus Bar.
2. Remove bridging Bus Bar.
3. Replace nuts and washers.
4. Torque to 120 in-lb
Alarm Card 477 Alarm Jumper
Not applicable to panels with VIM1 meter.
Position the jumper on HDR1 for Open on Alarm or Close on Alarm.
Return Bridging Bus Bar Battery Bridging Bus Bar
Figure 5 Bridging Bus Bars
J2 & J3 Alarm Out
J1
Alarm Jumper HDR1
Close on Alarm
Open on Alarm
Figure 6 Alarm Card
QUICK START GUIDE

Page 6
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Battery Connections – Loads - Figure 7
For single load configurations, A and B sections are bridged: Battery, Battery Return, Breaker Loads, and Load
Returns.
1. Connect battery feeds and returns.
2. Connect Breaker loads and returns.
Breakers and Fuse Holders
1. Open Breaker Access Covers by loosening front panel screws.
2. Install protectors and protector holders
3. Close Breaker Access Covers and tighten Breaker Access Screws.
4. Install fuses into fuse holders.
5. Install multi-pole bus kits included with each protector and protector holder occupying 2 or 3 positions.
Load Connections - Figure 7
1. Connect breaker load wires to Breaker Load Connections.
2. Connect breaker load return wires to the Return Bus.
Figure 7 DC Connections
2 Load configuration shown
Alarm Jumper HDR1
Battery Return Connections
Load B
Return Connections
Load A
Return Connections
Load B
Battery Connections
Load A
Battery Connections
B Breakers
Load Connections
A Breakers
Load Connections
Battery Lug Landings 3/8” on 1” centers torque 16 ft lb (22 Nm)
Breaker Load Lug Landings 5 mm (#10) on 5/8” centers torque 30 in lb (3.4 Nm)
QUICK START GUIDE

Page 7
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Alarm Wiring
20 AWG recommended.
1. Butt-splice office alarm wires to the provided alarm cable.
2. Connect the alarm cable connector to the VIM1 meter or alarm card.
Alarm2
Fuse NO Blue J2-1Fuse Brown
Fuse NC White/Blue J2-2Yellow
Fuse C3Slate J3-1Fuse Brown
10 OVLNO White/Slate J3-2Fuse C Yellow
OVLNC Orange
OVLC White/Orange
12 PLNO Yellow
PLNC White/Yellow
11 PLC White
2 NO signals Open on Alarm. NC signals Close on Alarm.
3 C signals, such as “Fuse C” are common or return signals for the similarly named signals, such as “Fuse NO”.
QUICK START GUIDE

Page 8
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
VIM1 Meter
The VIM1 can be configured to display the voltage, current, and panel identifier of each monitored load bus.
The VIM1 display normally blinks at regular intervals.
Notes specific to application in this equipment 5067:
1. Lamp Test does not activate 5067 Alarm LED - Figure 1.
Alarm Indication
When an alarm occurs, LCD backlight on the display changes color from green (normal) to red (alarm active). The
front panel text also changes from “No Alarms” to “Alarms”
Navigation Keys
Left and Right Keys are used for menu navigation. Up and Down keys are used to change the parameter values of
the meter. They also allow screen contrast adjustment at:
Menu System Parameters Display Contrast
Display
Previous Menu
Display Menus
Save Changes
Refresh
Arrows Keys
Navigate Menus
Adjust Values in Con
Figure 8 VIM1 Meter
Alarm and Monitoring
Visual, Audible and Remote Alarms
The VIM1 monitor includes an audible alarm with a user configurable on/off feature. There is a form-C relay for
each of the three alarms for remote monitoring.
All alarms are active when the VIM1 is unpowered. Alarms are asserted when their relay coils are not powered.
Power Loss/Under Voltage
Generates an alarm when power is lost to a load bus or when a user configurable low voltage threshold is reached.
Overload
Generates an alarm when a user configurable current threshold is reached. A configurable time delay may also be
set to avoid nuisance alarms due to bus transients.
Breaker/Fuse
Generates an alarm when either a circuit breaker trips or a fuse blows.
Network Connectivity
There are two RJ45 type connectors on the board for future use.
QUICK START GUIDE

Page 9
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Menu Map
The VIM1 front panel is structured such there are three main menu items: System Parameters, Load Parameters,
and Control/Operations. Each key menu item has sub items as shown in the menu map below.
QUICK START GUIDE

Page 10
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Programming the Meter
VIM1 parameters like shunt size and number of load buses are preconfigured when it is factory installed in a BDFB/
BDCBB or Micro-BDFB. Only customer specific preferences need to be adjusted in the field. As a replacement or
mete upgrade, the factory default settings may need to be adjusted for the application. Listed below are the
configurable parameters and their associated factory defaults available through the front panel. Following the
table are the typical items that need to be configured or verified in a retrofit or replacement application.
48V.
Allows the integrated audible alarm to be Enabled or Disabled. Factory default is Disabled.
Used by system controller to uniquely identify VIM1 device when connected for remote management. Device canbe
configured from 1-16.
Allows the display contrast to be adjusted for the local ambient lighting. Adjustable from 0-100% in 1% increments.
Factory default is 50%.
Displays the version of the application code running in the meter in the format (vX.Y). Version 1.5 is the latest as of this
printing.
Number Of Loads configurable from 1-8. Factory
default is 6.
(volt_curr).
Load ID Format
First Load (location)
Shunt Rating The factory default is 800A.
Overload Latch
Combined Load
Load Available
(A1-A4;B1- B4)
Indicates if the load is available or in use. Allowable configurations are “installed” and “not installed”. “Installed” loads
imply that the load is in use. “Not Installed” loads imply that the load may be present, but it is not in use. Information
obtained from the load should not be relevant. Factor default is set to be “installed”.
Load Power Loss
The Power Loss (PL) alarm is triggered upon loss of the primary DC or when the individual’s panels’ DC input has
reached the configured low voltage threshold. This Power Loss voltage threshold is configurable between 40.00-
60.00V for 48V systems and 20.00-30.00V for 24V systems. Factory defaults for these thresholds are 40.00V and
20.00V, respectively.
QUICK START GUIDE

Page 11
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Configuring the VIM1 For Controller Connectivity
The VIM1 has two shielded RJ45 connectors (figure 9) located on its top-rear that allow connecting the meter to a
ABB Galaxy Pulsar Plus or Galaxy Millennium 2 system controller through a cat-5 style communication cable. These
two system controllers can be part of a standard DC system where the controller is managing ABB rectifiers or in a
Standalone monitoring arrangement where there are no ABB system rectifiers but only ED83368 distribution
panels with VIM1s. The communication bus utilized is an internal RS485 operating with ABB’s proprietary Galaxy
Protocol. Providing VIM1 connectivity to a system controller allows VIM information and alarms is to be managed
remotely.
Delay
and Green
Clear Latched Events enabled to have a latched alarm.
Figure 9 VIM1 Meter RS485 Connection
QUICK START GUIDE

Page 12
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Configuring/Verifying Reference Jumper Settings
To utilize this connectivity, there are two jumper settings on the VIM1 that must be set properly before connecting
the VIM meters to the controller’s communication bus. These jumpers reside behind the back cover of the VIM1 and
are used to provide a physical reference for the RS485 communication link. Setting the jumper position is based on
the system rectifiers and DC bus potential. Note: Improper settings of these jumpers can result in damage of the
RS485 communication circuitry on the VIM, controller, or both when connected.
Remove the three Philipps screws and cover to gain access to the 3-pin J10 and J11 headers on the VIM1 circuit
pack. Note: a future enhancement will allow the cover to remain intact and while making the jumpers accessible.
Figure 10 shows the two jumpers with pin 1 identified.
• The factory default position of the jumpers for VIM1 J10 and J11 header is positions 1/2. This setting coincides with the
correct settings for Power Plants with Millennium 2 or Pulsar Plus DC controllers managing 595 (GPS), NE (Infinity), or
GP100 rectifiers.
• For VIM1s in Power Plants with system controllers managing EP (SPS), QS (CPS), or CP (CPL) family of rectifiers the
jumpers shall be placed in position 2/3 on J10 and J11.
• For systems where there are no ABB rectifiers and/or a ABB controller is dedicated to operate as a “Standalone”
distribution monitor that is connected only to the system VIM1s set the jumpers to position 2/3 on J10 and J11.
Figure 10 VIM1 J10 And J11 Settings
The following table summarizes the required jumper settings.
2 / 3 2 / 3
1 / 2 1 / 2
Setting The VIM1 Device ID
In order to connect the VIM1 to a system controller RS485 GP bus the VIM1 must be able to be uniquely identified by
the controller. To configure a unique ID for the VIM1 go to the front panel Menu►System Parameters►Device ID #.
Enter the menu and set the ID to a unique value between 1-16 (generally start with 1) and save the configuration.
Repeat the configuration to each VIM1 in the system.
QUICK START GUIDE

Page 13
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
Connecting The RS485 (GP) Communication Bus
For Standalone controller to VIM1 operation, make sure the controller’s appropriate RS485 GP communication
reference lead is properly connected to the correct DC bus potential prior to making the communication cable
connections. As with the jumper settings, this reference lead (Part of the power cable connection) either connects
to the DC- or DC+ bus based upon rectifier connectivity or Standalone operation. The RS485 GP Communication
reference lead is found on pin 2 of J9 on the Pulsar Plus NE843 controller or pin 3 of P6 on the Millennium 2
controller. Connect/Verify reference lead connection per table below. Consult appropriate controller manuals or
technical field support for additional information as required.
Figure 12 Standalone Pulsar Plus Monitoring VIM1 ED83368 Panels
With the system controller connections verified, VIM1 jumpers and ID properly set, and both units powered, the
VIM1 is ready to be connected to the controller’s system communication bus. For Standalone Controller
configurations, the communication connection can be made by simply using straight-thru cat-5 style cable to
connect between one of the RS485 ports on the VIM1 to port J10 on the Pulsar Plus (Figure 12) or on P9 for the
Millennium 2. Use the second VIM1 RS485 port to connect additional VIM1 in a daisy-chain fashion. Note: Although
not needed in many cases, it is recommended for long cable runs (>50’) with multiple VIM1s (>5) that the last VIM1
connected have a RS485 bus termination resistor 450050642 installed in the unused RS485 port. In power systems
with ABB rectifiers managed by a system controller, the communication connection may not be directly to the
controller and will have the be looked at on a per systems basis.
QUICK START GUIDE

Page 14
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
QUICK START GUIDE

Page 15
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
QUICK START GUIDE
* Maximum of 3 125A fuses per side. A space must be left between each fuse.

Page 16
© 2021 ABB. All rights reserved. Micro-BDCBB_QSG Rev. 04
We reserve the right to make technical changes or modify the
contents of this document without prior notice. With regard
to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this
document.
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole or in parts – is
forbidden without prior written consent of ABB.
Copyright© 2021 ABB
All rights reserved
ABB
601 Shiloh Rd.
Plano, TX USA
abbpowerconversion.com
Table of contents
Other ABB Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Magikist
Magikist MagikMinder MM100 operating manual

Blastrac
Blastrac 1-10DPS75 MKII operating instructions

Festo
Festo EGC FA Series operating instructions

Graco
Graco 253479 Instructions-parts list

SCHUNK
SCHUNK SRM 16 - 40 Repair instructions

Siemens
Siemens Compact PLUS 6SE7024-1EP85-0AA0 operating instructions

American Lubrication Equipment
American Lubrication Equipment TIM-390-A1 manual

Smartgen
Smartgen AIN16-M01 user manual

RINGFEDER
RINGFEDER TNM G Installation and operation manual

Fastbind
Fastbind C400 user manual

York
York AHS8 UH Series User's information, maintenance and service manual

GE
GE GEI-44233 F instructions