ABB eVM1 Quick guide

eVM1
Installation and service instructions
12 ... 17.5 kV - 630 ... 1250 A - 16 ... 31.5 kA

1

1
For your safety!
Make sure that the installation room (spaces, divisions and ambi-
ent) is suitable for the electrical apparatus.
Check that all the installation, putting into service and maintenance
operations are carried out by qualified personnel with suitable
knowledge of the apparatus.
Make sure that the standard and legal prescriptions are complied
with during installation, putting into service and maintenance, so
that installations according to the rules of good working practice
and safety in the workplace are constructed.
Strictly follow the information given in this instruction manual.
Check that the rated performance of the apparatus is not exceeded
during service.
Check that the personnel operating the apparatus have this
instruction manual to hand as well as the necessary information
for correct intervention.
Pay special attention to the notes indicated in the manual. A note
contains additional information worth noting in the specific
context, and looks like the following:
Safety warning.The safety warnings should always be observed.
Non-observance can result in death, personal injury or substantial
damages to property. Guarantee claims might not be accepted
when safety warnings are not respected. They look like the
following:
Note
Warning!
Responsible behaviour
safeguards your own and others’ safety!
For any requests, please contact the
ABB Assistance Service.

2
Index
I. Introduction 4
II. Environmental protection programme 4
1. Packing and transport 5
2. Checking on receipt 5
3. Storage 6
4. Handling 6
5. Description 7
5.1. Standards and regulations 7
5.2. Service conditions 8
6. Structure 9
6.1. Drive structure 9
6.2. Structure of the circuit-breaker poles 11
6.3. Basic structure of the withdrawable circuit-breaker 12
7. Operation 12
7.1. Operation of the circuit-breaker drive 12
7.2. Principle of extinction of the vacuum interrupter 14
7.3. Interlocks 15
8. Circuit-breaker characteristics 16
8.1. General characteristics of fixed circuit-breakers 17
8.2. General characteristics of circuit-breakers
for UniGear type ZS1 switchgear and PowerCube modules 18
8.3. Control circuit power supply 19
8.4. Standard fittings 20
8.5. Optional accessories 21
9. Installation 23
9.1. General 23
9.2. Trip curves 23
9.3. Preliminary operations 24
9.4. Installation of fixed circuit-breaker 24
9.5. Installation of withdrawable circuit-breaker 24
9.6. Auxiliary circuits 24
9.7. Overall dimensions 25
10. Putting into service 28
10.1. General procedures 28
10.2. Operation of the circuit-breaker 28
10.3. Operations before putting into service 29
11. Maintenance 30
11.1. General 30
11.2. Inspections and functional tests 31
11.3. Servicing 32
11.4. Repairs 33
12. Application of the X-ray emission Standards 34
13. Spare parts and accessories 34
13.1. List of spare parts 34

3
14. Multifunction Protection and Switchgear Control Unit 35
14.1. About this section 35
14.2. Safety Information 35
14.3. Acronyms and definitions 35
14.4. Menu, Toolbar and Tabs 36
14.5. General settings 41
14.6. Logic Configuration 58
14.7. Protection Parameters 62
14.8. Input / Output Mapping 88
14.9. Monitoring 94
14.10. Communication 96
14.11. Password 102
14.12. LCD Panel HMI 102
14.13. Local CB HMI 104
14.14. Anomaly list 105
14.15. Procedure for discharging the capacitor 106
14.16. Insulation Test on CB secondary wiring 107

4
I. Introduction
This publication contains the information needed to install medium voltage eVM1 (withdrawable
version for UniGear ZS1 type switchgear and PowerCube modules) and put them into service.
For correct use of the product, please read it carefully.
Like all the apparatus we manufacture, the eVM1 circuit-breakers are designed for different instal-
lation configurations.
However, they do allow further technical and construction modifications (at the customer’s re-
quest) to adapt to special installation requirements.
For this reason, the information given below may sometimes not contain instructions concerning
special configurations.
Apart from this manual, it is therefore always necessary to consult the latest technical documen-
tation (circuit and wiring diagrams, assembly and installation drawings, any protection coordina-
tion studies, etc.), especially regarding any variants requested in relation to the standardised
configurations.
Only use original spare parts for maintenance operations.
For further information, please also see the technical catalogue of the circuit-breaker.
All the installation, putting into service, running and maintenance operations must be car-
ried out by skilled personnel with in-depth knowledge of the apparatus.
II. Environmental protection programme
The eVM1 circuit-breakers are manufactured in accordance with the ISO 14000 Standards (Guide-
lines for environmental management).
The production processes are carried out in compliance with the Standards for environmental
protection in terms of reduction in energy consumption as well as in raw materials and production
of waste materials. All this is thanks to the medium voltage apparatus manufacturing facility envi-
ronmental management system.
Warning!

5
Fig. 1
1. Packing and transport
The circuit-breaker is shipped in special packing, in the open position.
Each piece of apparatus is protected by a plastic cover to prevent any infiltration of water during
the loading and unloading stages and to keep the dust off during storage.
2. Checking on receipt
Before carrying out any operation, always make sure that the capacitors are discharged
and that the apparatus is in the open position.
On receipt, check the state of the apparatus, integrity of the packing and correspondence with the
nameplate data (see fig. 1) with what is specified in the order confirmation and in the accompany-
ing shipping notes.
Also make sure that all the materials described in the shipping notes are included in the supply.
Should any damage or irregularity be noted in the supply on unpacking, notify ABB (directly or
through the agent or supplier) as soon as possible and in any case within five days of receipt.
The apparatus is only supplied with the accessories specified at the time of ordering and vali-
dated in the order confirmation sent by ABB.
Caption
A Circuit-breaker rating plate.
B Drive rating plate.
1 Type of apparatus.
2 Symbols of compliance with Standards.
3 Serial number.
4 Circuit-breaker characteristics.
5 Characteristics of the drive auxiliaries.
Warning!
A
B
3
4
2
CIRCUIT-BREAKER IEC 62271-100
eVM1 ... ... ... CEI 17-1
CLASSIFICATIONSN ... ... ...
SN ... ... ... PR. YEAR ......
M MASS ... kV
Ur VOLTAGE ... A
Up LIGHTING IMPULSE WITHSTAND VOLTAGE ... kV
Ud CORRENTE TERMICA NOMINALE ... A
fr FREQUENCY ... Hz
Ir NORMAL CURRENT
WITH FORCED VENTILATION BY ABB DESIGN
Ik SHORT TIME WITHSTAND CURRENT
tk DURATION OF SHORT CIRCUIT
Isc SHORT CIRCUIT BREAKING CURRENT
MAKING CAPACITY (PEAK VALUE)
AT THE VOLTAGE OF
D.C. COMPONENT ... A
Ic CABLE CHARGIMG BREAKING CURRENT ... A
Prn SF6 FILLING PRESSURE AT 20 °C ... kV
m SF6 MASS FOR CIRCUIT-BREAKER ... Kg
OPERATING SEQUENCE O-0,3S-C0-15S-CO
ELECTRICAL DIAGRAM ... ... ... ...
FIG. ... ...
.. ... ... ... OPERATING MECHANISM
-MO1 ... ... ... V
Made by ABB
1
5
The accompanying documents inserted in the
shipping packing are:
– instruction manual (this document)
– test certification
– identification label
– copy of the shipping documents
– electric wiring diagram.
Other documents which are sent prior to
shipment of the apparatus are:
– order confirmation
– original shipping advice notes
– any drawings or documents referring to special
configurations/conditions.

6
A
132
3
D
Fig. 2
3. Storage
When a period of storage is foreseen, our workshops can (on request) provide suitable packing
for the specified storage conditions.
On receipt the apparatus must be carefully unpacked and checked as described in Checking on
receipt (chap. 2).
If immediate installation is not possible, the packing must be replaced, using the original material
supplied.
Insert special hygroscopic substances inside the packing, using at least one standard packet per
piece of apparatus.
Should the original packing not be available and immediate installation is not possible, store in a
covered, well-ventilated, dry, dust-free, non-corrosive ambient, away from any flammable materi-
als and at a temperature between –5 °C and +45 °C.
In any case, avoid any accidental impacts or positioning which stresses the structure of the appa-
ratus.
4. Handling
Before carrying out any operations, always make sure that the capacitors are discharged.
To lift and handle the circuit-breaker, proceed as follows (fig. 2):
– use a special lifting tool (1) (not supplied) fitted with ropes with safety hooks (2);
– insert the hooks (2) in the supports (3) fixed to the frame of the circuit-breaker and lift. Latch the
hooks (2) into the support holes (3) according to the type of apparatus (see table);
– on completion of the operation (and in any case before putting into service) unhook the lifting
tool (1) and dismantle the supports (3) from the frame.
During handling, take great care not to stress the insulating parts and the terminals of the circuit-
breaker.
Version Pole centre Rated Hole
distance current
Fixed 150 mm up to 1250 A A
Fixed 210 mm up to 1250 A A
Fixed 275 mm up to 1250 A A
Withdrawable 150 mm up to 1250 A A

7
Warning!
Fig. 3
5. Description
The eVM1/P type vacuum circuit-breakers are designed for indoor installation in air-insulated
switchgear.
In respect of the technical characteristics, eVM1/P circuit-breakers are suitable for operation of
electric circuits under normal and fault service conditions.
The vacuum circuit-breakers have particular advantages when used in systems with a high fre-
quency of operations and/or which lead to a certain number of short-circuit trips.
The eVM1/P type vacuum circuit-breakers stand out for their particularly high operating reliability,
extremely long useful life expectancy and for being completely maintenance-free.
The eVM1/P type vacuum circuit-breakers are available in the withdrawable version. Their basic
structure is shown in the “Technical data” section.
5.1. Standards and regulations
5.1.1. Fabrication
The eVM1 circuit-breakers conform to the following Standards:
• VDE 0670, part 1000, and IEC 60694
• DIN VDE 0670, part 104, and IEC 62271-100
• DIN VDE 0847, part 4, and IEC 61000-4.
The apparatus must not be handled by putting lifting devices directly under the apparatus
itself. Should it be necessary to use this technique, put the circuit-breaker onto a pallet or
a sturdy supporting surface (see fig. 3).
In any case, it is always advisable to carry out lifting using the supports (3). Hole “D” must
never be used.

8
5.1.2. Installation and operation
For assembly and operation, please refer to the relative regulations, and in particular to:
• DIN VDE 0101, AC electrical plants with voltage higher than 1 kV
• DIN VDE 0100-410, Installation of electrical plants up to 1000 V, protective measures
• VDE 0105, Operation of electrical plants
• DIN VDE 0141, Earthing systems for special electrical plants with rated voltages higher than 1 kV
• Accident prevention regulations of insurance institutes against accidents at the workplace or of
comparable organisations
• Safety directives for auxiliary and operating materials.
5.2. Service conditions
5.2.1. Normal service conditions
Follow the recommendations in the IEC 60694 and 62271-100 Standards. In more detail:
Ambient temperature
Maximum + 40 °C
Average maximum over 24 hours + 35 °C
Minimum (according to class – 5), apparatus for indoor installation – 5°
Humidity
The average value of the relative humidity, measured for a period longer than 24 hours, must not
exceed 95 %.
The average value of the pressure of the water vapour without condensation, measured for a
period longer than 24 hours, must not exceed 2.2 kPa.
The average value of the relative humidity, measured for a period longer than 1 month, must not
exceed 90 %.
The average value of the pressure of the water vapour, measured for a period longer than 1
month, must not exceed 1.8 kPa.
Altitude
< 1000 m above sea level.
5.2.2. Special service conditions
Installations over 1000 m a.s.l.
Possible within the limits permitted by reduction of the dielectric resistance of the air.
Increase in the ambient temperature
Reduction in the rated current.
Encourage heat dissipation with appropriate additional ventilation.
Climate
To avoid the risk of corrosion or other damage in areas with a high level of humidity, and/or rapid
and large temperature variations, take appropriate steps (for example, by using suitable electric
heaters) to prevent condensation phenomena.
For special installation requirements or other operating conditions, please contact ABB.

9
10
7
5
11
13
12
8
2
9
6
3
4
1
14
6. Structure
6.1. Drive structure
The drive is of the magnetic type and basically consists of the magnetic actuator (8) (fig. 4), the
control module (10), the current sensors (3), the capacitor/s (2) and the kinematics which transmit
the movement to the circuit-breaker poles.
The actuator (8) acts on the circuit-breaker poles by means of special kinematics. The capacitor/
s (2) provides/provide the energy required for the operation.
The mechanical operating positions of the circuit-breaker are detected by two due sensors (14).
The basic version of the circuit-breaker is fitted with the following controls and instruments:
• coupling for manual emergency operation (9)
• mechanical state indicator (6)
• mechanical operation counter (5)
• control panel (7) with opening and closing pushbuttons.
6.1.1. Structure of the control module
The control module (10) of the circuit-breaker consists of:
• a microprocessor
• opto-electrical input couplers
• output relay
• electronic power system for controlling the actuator coils.
1Pole: vacuum interrupter
embedded in epoxy resin
2Capacitor
3Current sensor (Rogowski
coil)
4Truck of withdrawable circuit-
breaker
5Operation counter
6Mechanical Open/Closed
signalling device
7Control panel
8Magnetic drive
9Coupling for emergency
manual operating lever
10 Protection and control unit
11 Binary inputs/outputs
12 Communication
13 Socket for auxiliary circuits
14 Position Open/Closed
sensors
Fig. 4

10
6.1.2. Capacitor
The energy for operating the circuit-breaker is stored in one or two capacitors according to the
circuit-breaker model (fig. 5).
The capacitors are designed so that the energy for an O-C-O operating cycle is supplied without
the need for recharging.
The energy stored by the capacitor is constantly monitored by means of measuring the relevant
voltage.
The “UNIT READY” indication signals application of the power supply voltage and the “ready” state
of the circuit-breaker for the next operation.
The energy stored in the capacitors determines the position of the READY/NOT READY contacts
and lighting up of the luminous “UNIT READY” signal according to the following criteria:
• Case 1: circuit-breaker in the open position.
- The energy available is sufficient for one closing and opening operation.
• Case 2: circuit-breaker in the closed position.
- The energy available is sufficient for one opening operation.
- The energy available is sufficient for one opening operation within about 30 seconds from
interruption of the auxiliary power supply.
If the energy stored is not sufficient, the luminous “UNIT READY” signal is off, the “READY” contact
is open and the “NOT READY” contact is closed to indicate that the circuit-breaker is not ready for
the operation.
6.1.3. Position sensors
The use of two inductive position sensors (fig. 6) allows the state of the circuit-breaker (open -
closed - anomalous intermediate position) to be determined without the use of auxiliary contacts,
allowing continual monitoring of the system.
Fig. 5 Fig. 6

11
1
2
5
4
3
6
7
8
9
10
11
12
13
14
15
16
17
1a
2a
6.2. Structure of the circuit-breaker poles
The poles are installed in the rear part of the circuit-breaker frame (fig. 7).
The active parts of the poles (vacuum interrupters) are embedded in epoxy resin and protected
against shocks and other external agents.
With the circuit-breaker closed, the current flows from the top terminal (1) to the fixed contact (1a)
in the vacuum interrupter (4), and then through the moving contact (2a) and the flexible connector
(6) as far as the bottom terminal of the circuit-breaker (2).
The movement of the moving contact are ensured by the insulating tie-rod (8) and by the kinemat-
ics (9).
Fig. 7
1Top terminal
1a Fixed contact
2Bottom terminal
2a Moving contact
3Pole in resin
4Vacuum interrupter
5Current sensor
6Flexible connector
7Contact pressure spring
8Insulating tie-rod
9Drive shaft
10 Run regulator
11 Position sensors
12 Closing coil
13 Permanent magnets
14 Moving armature
15 Opening coil
16 Device for manual emergency opening
17 Supporting structure

12
4
3
1
2
Fig. 8
6.3. Basic structure of the withdrawable circuit-breaker
The withdrawable truck (4) (fig. 8), either manual or motorised, consists of a steel sheet structure
with wheels (3), on which the circuit-breaker with the relative auxiliary components, the isolating
contacts (2) for electrical connection with the switchgear and the multi-pole connector (1) for
connection of the circuit-breaker auxiliary circuits are installed.
After having been racked into the switchgear and hooked up, the withdrawable circuit-breaker
can take up the following positions: racked-out, isolated for test (with connector inserted) and
racked-in. The racked-in circuit-breaker is automatically earthed by means of the truck wheels.
The magnetic actuator of the circuit-breaker and the relative controls and indicators, are accessi-
ble from the front.
Withdrawable circuit-breakers of the same type and characteristics are interchangeable. How-
ever, the code of the connector prevents incorrect combinations between the circuit-breaker and
switchgear.
7. Operation
7.1. Operation of the circuit-breaker drive
7.1.1. Magnetic actuator
The magnetic actuator used in the eVM1 circuit-breakers generates the run required to operate
the moving contacts of the interrupters and integrates all the functions of a traditional operating
mechanism.
The magnetic actuator is a bistable system where end-of-run positions of the moving armature
are reached by means of magnetic fields generated by two coils (one for closing and one for
opening).
The moving armature is kept in position by permanent magnets.
The circuit-breaker operations are obtained by means of energisation of the opening or closing
coil respectively. The magnetic field generated by each coil attracts the moving armature and
thereby moves it from one of the latching points of the permanent magnets to the other.

13
The capacitors which allow circuit-breaker operation, for a maximum time of about 30 seconds (with
closed circuit-breaker), even in the case of a drop in the auxiliary voltage, are provided in the control
circuit. In case of emergency, the circuit-breaker can in any case be opened by means of a special
crank handle which acts directly on the moving armature of the drive.
Compared to a traditional operating mechanism, the magnetic actuator has few moving parts and
greatly reduced wear even after a high number of closing and opening cycles.
These characteristics therefore make it practically maintenance-free.
7.1.2. Opening and closing operations
The opening and closing operations can either be remotely controlled by means of the special
inputs provided in the control module, or locally by pressing the pushbuttons on the control panel (7)
(fig. 4).
During the operations, the moving armature of the actuator acts directly on the moving contact by
means of the kinematics (8-9-10) (fig. 7).
7.1.3. Reclosing function
Thanks to the short duration of capacitor recharging, the drive is suitable for multiple reclosing
operations with O-0.3s-CO-15s-CO cycle.
7.1.4. Control module functions
All the conditions for controlling the opening and closing commands given to the magnetic actua-
tor are managed by a microprocessor:
• The power supply voltage must be applied to the AC/DC converter.
• The capacitor must be sufficiently charged for the next operation:
Circuit-breaker position Operations
Open Closes and Opens
Closed Opens
Magnetic latching in end-of-run position.
Magnetic latching and action of the magnetic field of a coil.
Moving armature in opposing position and magnetic end-of-run latching.
• The closing coil can only be activated when the circuit-breaker is open
• The opening coil can only be activated when the circuit-breaker is closed
• Closing is disabled when an opening command is active at the same time
• De-activation of the opening or closing coil takes place when the relative limit position has been
reached.
• WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is not reached
within 70 ms during a closing (or opening) operation, an opening operation is immediately started
to guarantee reaching a defined safe position in any case.
• The anti-pumping function ensures that only one closing-opening cycle is carried out when a
closing command followed by an opening command is active. The active closing command must
be cancelled and reset for the next closing operation.
• Activation of the input for the closing command can be locked by means of an external locking
signal.
• The input for the “lock on closing” command must be energised to be able to close the circuit-
breaker (without power it inhibits closing).

14
Magnetic latching in end-of-run posi-
tion.
Magnetic latching and action of the
magnetic field of a coil.
Moving armature in opposing position
and magnetic end-of-run latching.
Fig. 9
• Undervoltage function: controls circuit-breaker opening if the applied voltage drops below the
tolerance limit (established by the Standards).
To prevent the function intervening when the voltage drops below the specified level (e.g. in the
case of motor starting), it is possible to set a trip time.
The undervoltage function is normally disabled. In this case, it is possible to open and close the
circuit-breaker without applying voltage to the input of the function.
• Monitoring function of the actuator closing and opening coil. This function serves to monitor the
continuity of the closing and opening coils of the magnetic actuator to detect any faults.
If a fault is detected, the luminous “COILS OK” signal on front of the circuit-breaker turns off and
the “READY/NOT READY” signalling contacts are commutated.
• Additional safety opening command function. The second input of the control module for the
opening function is designed so that an opening command is carried out directly even in the case
of a fault in the microprocessor.
7.1.5. Truck locking magnet
The locking magnet is inserted in withdrawable circuit-breakers with manual movement and pre-
vents traverse of the withdrawable truck when there is no power supply voltage. It is also linked to
the interlock between circuit-breaker closed and truck: it guarantees that even in a situation with
main welded contacts, the circuit-breaker cannot be isolated.
7.2. Principle of extinction of the vacuum interrupter
Given the relatively low static pressure of the interruption chamber (between 10-4 and 10-8 hPa), a
relatively limited distance between the contacts is required to obtain high dielectric strength. The
vacuum arc is extinguished on the first passage of the current through natural zero.
Considering the limited distance between the contacts, the high conductivity of the plasma of
metallic vapours, the drop in voltage of the arc and, moreover, the short arcing time, the energy
associated with the arc is extremely limited, therefore producing benefits for the useful life of the
contacts obtained and, consequently, for the useful life of the vacuum interrupters.

15
2
1
7.3. Interlocks
7.3.1. Interlocks / protection against malfunction (for withdrawable circuit-breakers for UniGear
ZS1 type switchgear and PowerCube modules)
A series of interlocks is provided to prevent incorrect operations and/or malfunctions. The inter-
locks are the following:
• the withdrawable truck can only be moved from the test/isolated position to the service position
(and vice versa) if the circuit-breaker is open (this means that first of all the circuit-breaker must
be opened).
• the circuit-breaker can be closed if the withdrawable truck is exactly in the defined test position
or in the service position (electric interlock).
• the circuit-breaker can be opened manually in the service or test position when it is not pow-
ered, but it cannot be closed.
• the switchgear is provided with devices which only allow connection and disconnection of the
plug connector (1) (fig. 10) in the test/isolation position.
Any detailed information regarding additional interlocks, e.g. with the earthing switch operating
mechanism, is given in the specific order documentation.
7.3.2. Interlocks in the case where withdrawable trucks are used UniGear ZS1 type switch-
gear and PowerCube modules
1) There is the possibility of configuring a binary input and relative function to allow the lock on
circuit-breaker closing when a voltage of 24 V - 240 V a.c./d.c. is applied to the input (electric
closing lock).
2) The eVM1/P circuit-breaker can only be closed when the withdrawable truck is in the test or
service position. In intermediate positions the closing lock voltage is cut off by the auxiliary
contacts of the truck.
3) A mechanical interlock positioned on the withdrawable truck prevents a closed circuit-breaker
being moved from the test position to the service position.
Fig. 10

16
8. Circuit-breaker characteristics
8.1. General characteristics of fixed circuit-breakers
eVM1 12
12
12
28
75
50-60
630 1250
16 16
20 20
25 25
31,5 31,5
16 16
20 20
25 25
31,5 31,5
40 40
50 50
63 63
80 80
33
10...15
43...48
50
... 100.000
... 30.000
... 30.000
... 100
461 461 461
450 570 700
464 464 464
150 210 275
205 205 205
106 ... 117
< 15
< 110
– 5 ... + 40
eVM1 17
17
17
38
95
50-60
630 1250
16 16
20 20
25 25
31,5 31,5
16 16
20 20
25 25
31,5 31,5
40 40
50 50
63 63
80 80
33
10...15
43...48
50
... 100.000
... 30.000
... 30.000
... 100
461 461 461
450 570 700
464 464 464
150 210 275
205 205 205
106 ... 117
< 15
< 110
– 5 ... + 40
IEC 60694 - 62271-100
CEI 17-1 (File 1375)
Ur [kV]
Us [kV]
Ud (1 min) [kV]
Up [kV]
fr [Hz]
(1) Ir [A]
Isc [kA]
Ik [kA]
Ip [kA]
[O-0,3s-CO-15s-CO]
[ms]
[ms]
[ms]
[ms]
Actuator [No.]
Interrupters [No.]
At rated current [No.]
Under short-circuit [No.]
H[mm]
W[mm]
D[mm]
I[mm]
A[mm]
[kg]
[W]
[W]
[°C]
IEC 61000
IEC 60255
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated symmetrical short-circuit current)
Rated short-time withstand current (3 s)
Making capacity
Operation sequence
Opening time
Arcing time
Total interruption time
Closing time
Mechanical operations (cycles)
Electrical operations (cycles)
Maximum overall dimensions
Pole centre distance
Bottom/top terminal distance
Weight
Consumption on stand-by
Consumption after a self-closing cycle
Standardised table of dimensions
Operating temperature
Electromagnetic compatibility
Fig. 11a
A
II
D
W
H

17
8.1.1. Types of circuit-breakers
Ur Ir (40°C) Isc Dimensions Type of circuit-breaker
[kV] [A] [kA] L [mm] I [mm] A [mm]
12 630 16 450 150 205 eVM1 12.06.16 p150
630 20 450 150 205 eVM1 12.06.20 p150
630 25 450 150 205 eVM1 12.06.25 p150
630 31,5 450 150 205 eVM1 12.06.32 p150
1250 16 450 150 205 eVM1 12.12.16 p150
1250 20 450 150 205 eVM1 12.12.20 p150
1250 25 450 150 205 eVM1 12.12.25 p150
1250 31,5 450 150 205 eVM1 12.12.32 p150
12 630 16 570 210 205 eVM1 12.06.16 p210
630 20 570 210 205 eVM1 12.06.20 p210
630 25 570 210 205 eVM1 12.06.25 p210
630 31,5 570 210 205 eVM1 12.06.32 p210
1250 16 570 210 205 eVM1 12.12.16 p210
1250 20 570 210 205 eVM1 12.12.20 p210
1250 25 570 210 205 eVM1 12.12.25 p210
1250 31,5 570 210 205 eVM1 12.12.32 p210
12 630 16 700 275 205 eVM1 12.06.16 p275
630 20 700 275 205 eVM1 12.06.20 p275
630 25 700 275 205 eVM1 12.06.25 p275
630 31,5 700 275 205 eVM1 12.06.32 p275
1250 16 700 275 205 eVM1 12.12.16 p275
1250 20 700 275 205 eVM1 12.12.20 p275
1250 25 700 275 205 eVM1 12.12.25 p275
1250 31,5 700 275 205 eVM1 12.12.32 p275
17,5 630 16 450 150 205 eVM1 17.06.16 p150
630 20 450 150 205 eVM1 17.06.20 p150
630 25 450 150 205 eVM1 17.06.25 p150
630 31,5 450 150 205 eVM1 17.06.32 p150
1250 16 450 150 205 eVM1 17.12.16 p150
1250 20 450 150 205 eVM1 17.12.20 p150
1250 25 450 150 205 eVM1 17.12.25 p150
1250 31,5 450 150 205 eVM1 17.12.32 p150
17,5 630 16 570 210 205 eVM1 17.06.16 p210
630 20 570 210 205 eVM1 17.06.20 p210
630 25 570 210 205 eVM1 17.06.25 p210
630 31,5 570 210 205 eVM1 17.06.32 p210
1250 16 570 210 205 eVM1 17.12.16 p210
1250 20 570 210 205 eVM1 17.12.20 p210
1250 25 570 210 205 eVM1 17.12.25 p210
1250 31,5 570 210 205 eVM1 17.12.32 p210
17,5 630 16 700 275 205 eVM1 17.06.16 p275
630 20 700 275 205 eVM1 17.06.20 p275
630 25 700 275 205 eVM1 17.06.25 p275
630 31,5 700 275 205 eVM1 17.06.32 p275
1250 16 700 275 205 eVM1 17.12.16 p275
1250 20 700 275 205 eVM1 17.12.20 p275
1250 25 700 275 205 eVM1 17.12.25 p275
1250 31,5 700 275 205 eVM1 17.12.32 p275
Note
L = Width of circuit-breaker.
I = Horizontal poles center lines.
A = Upper and lower distance.

18
8.2. General characteristics of circuit-breakers for UniGear type ZS1 switchgear
and PowerCube modules
A
II
PL
H
eVM1/P 12
12
12
28
75
50-60
630 1250
16 16
20 20
25 25
31,5 31,5
16 16
20 20
25 25
31,5 31,5
40 40
50 50
63 63
80 80
33
10...15
43...48
50
... 100.000
... 30.000
... 30.000
... 100
628 628
503 503
662 662
150 150
205 205
126 ... 137
< 15
< 110
– 5 ... + 40
eVM1/P 17
17
17
38
95
50-60
630 1250
16 16
20 20
25 25
31,5 31,5
16 16
20 20
25 25
31,5 31,5
40 40
50 50
63 63
80 80
33
10...15
43...48
50
... 100.000
... 30.000
... 30.000
... 100
628 628
503 503
662 662
150 150
205 205
126 ... 137
< 15
< 110
– 5 ... + 40
IEC 60694 - 62271-100
CEI 17-1 (Fasc. 1375)
Ur [kV]
Us [kV]
Ud (1 min) [kV]
Up [kV]
fr [Hz]
(1) Ir [A]
Isc [kA]
Ik [kA]
Ip [kA]
[O-0,3s-CO-15s-CO]
[ms]
[ms]
[ms]
[ms]
Actuator [No.]
Interrupters [No.]
At rated current [No.]
Under short-circuit [No.]
H[mm]
L[mm]
P[mm]
I[mm]
A[mm]
[kg]
[W]
[W]
[°C]
IEC 61000
IEC 60255
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated symmetrical short-circuit current)
Rated short-time withstand current (3 s)
Making capacity
Operation sequence
Opening time
Arcing time
Total interruption time
Closing time
Mechanical operations (cycles)
Electrical operations (cycles)
Maximum overall dimensions
Pole centre distance
Bottom/top terminal distance
Weight
Consumption on stand-by
Consumption after a self-closing cycle
Standardised table of dimensions
Operating temperature
Electromagnetic compatibility
(1)Rated uninterrupted
currents guaranteed
with withdrawable cir-
cuit-breaker installed in
UniGear ZS1 type
switchgear with air tem-
perature of 40 °C.
Fig. 11b
This manual suits for next models
2
Table of contents
Other ABB Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Skov
Skov DA 820 Mounting guide

HARTING
HARTING Han 24 HPR VarioShell Assembly instructions

Tormach
Tormach ATC owner's guide

Regulus
Regulus HSK PV Installation and operation instruction

ITOH DENKI
ITOH DENKI PM605KT Technical documentation

Fayat Group
Fayat Group BOMAG BT 65 Operating Instruction, Maintenance Instruction