manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ABB
  6. •
  7. Relay
  8. •
  9. ABB 511 Series User manual

ABB 511 Series User manual

This manual suits for next models

7

Other ABB Relay manuals

ABB E45 DU User manual

ABB

ABB E45 DU User manual

ABB CM Series User manual

ABB

ABB CM Series User manual

ABB TF140DU User manual

ABB

ABB TF140DU User manual

ABB Relion REX610 User manual

ABB

ABB Relion REX610 User manual

ABB ITH Manual

ABB

ABB ITH Manual

ABB CA-16 User manual

ABB

ABB CA-16 User manual

ABB UAF User manual

ABB

ABB UAF User manual

ABB CM Series User manual

ABB

ABB CM Series User manual

ABB CWC Manual

ABB

ABB CWC Manual

ABB CM Series User manual

ABB

ABB CM Series User manual

ABB A140-H56 User manual

ABB

ABB A140-H56 User manual

ABB CV Series Manual

ABB

ABB CV Series Manual

ABB A135-H65 User manual

ABB

ABB A135-H65 User manual

ABB SGR-51 User manual

ABB

ABB SGR-51 User manual

ABB CR Series Manual

ABB

ABB CR Series Manual

ABB SPAU 331 C Parts list manual

ABB

ABB SPAU 331 C Parts list manual

ABB DB42 User manual

ABB

ABB DB42 User manual

ABB KLF Series Manual

ABB

ABB KLF Series Manual

ABB SRW Manual

ABB

ABB SRW Manual

ABB CM Series User manual

ABB

ABB CM Series User manual

ABB CW Series Manual

ABB

ABB CW Series Manual

ABB REM 610 Product manual

ABB

ABB REM 610 Product manual

ABB SC Manual

ABB

ABB SC Manual

ABB SPAU 130 C Parts list manual

ABB

ABB SPAU 130 C Parts list manual

Popular Relay manuals by other brands

Woodward BU1-DC2 manual

Woodward

Woodward BU1-DC2 manual

Siemens SIRIUS 3UG4633 operating instructions

Siemens

Siemens SIRIUS 3UG4633 operating instructions

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Siemens

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Shelly Pro Series user manual

Shelly

Shelly Pro Series user manual

GE MVAX 11 Technical manual

GE

GE MVAX 11 Technical manual

Kemo Electronic B197 quick guide

Kemo Electronic

Kemo Electronic B197 quick guide

Seg MRM3 manual

Seg

Seg MRM3 manual

Basler BE1-700C manual

Basler

Basler BE1-700C manual

CD Automation REVEX 2PH 280A user manual

CD Automation

CD Automation REVEX 2PH 280A user manual

Ruelco 1S04 Operation manual

Ruelco

Ruelco 1S04 Operation manual

Basler V3E Z1P B2C1F instruction manual

Basler

Basler V3E Z1P B2C1F instruction manual

GE DGP instruction manual

GE

GE DGP instruction manual

Kyongbo Electronics GDR-D01 user manual

Kyongbo Electronics

Kyongbo Electronics GDR-D01 user manual

Eaton easyE4 series Application note

Eaton

Eaton easyE4 series Application note

Siemens BD2-AK03X/FS Series installation instructions

Siemens

Siemens BD2-AK03X/FS Series installation instructions

Leuze MSI-SR5B Original operating instructions

Leuze

Leuze MSI-SR5B Original operating instructions

Littelfuse SE-330AU manual

Littelfuse

Littelfuse SE-330AU manual

EVA Logik ZW12 user manual

EVA Logik

EVA Logik ZW12 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

it
lilt
#
\
IPW
IB
7.2
.
1.7
-
1
Issue
C
Instructions
Overcurrent
Relays
CATALOG
SERIES
223
/
423
DRAWOUT
SEMI
-
FLUSH
MOUNTED
SINGLE
PHASE
,
TWO
PHASE
,AND
THREE
-
PHASE
RELAYS
INVERSE
VERY
INVERSE
EXTREMELY
INVERSE
DEFINITE
TIME
.
TYPE
511
TYPE
51
Y
TYPE
51
E
TYPE
51
D
SHORT
TIME
LONG
TIME
LONG
TIME
INVERSE
.
TYPE
51
S
.
.
TYPE
51
L
TYPE
51
IM
LONG
TIME
VERY
INVERSE
....
TYPE
51
YM
gown
-
,
rK
'
$
/
*
a
*
*
BBC
Brow
"
?
a
cuflvi
A i
!
»
SINGLE
PHASE
FOR
RESIDUAL
GROUND
PROTECTION
THREE
PHASE
FOR
PHASE
PROTECTION
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
2
SOLID
-
STATE
OVERCURRENT
RELAYS
INSTRUCTIONS
FOR
CIRCUIT
-
SHIELD
®
SOLID
-
STATE
RELAYS
DRAWOUT
SEMI
-
FLUSH
MOUNTED
SINGLE
PHASE
,
TWO
PHASE
,
AND
THREE
PHASE
TABLE
OF
CONTENTS
3
.
Be
sure
the
trip
circuit
is
interrupted
by
an
"
a
"
contact
to
remove
high
currents
from
solid
-
state
output
circuits
.
Solid
-
state
output
circuits
have
inherently
high
momentary
current
ratings
and
low
continuous
current
ratings
.
Never
exceed
the
ratings
.
4
.
When
applying
input
current
to
protective
relays
,
be
sure
to
interrupt
the
input
current
immediately
after
the
relay
operates
.
5
.
Load
(
trip
coils
or
auxiliary
relays
)
must
draw
at
least
0.10
amps
to
insure
operation
.
SCR
'
s
require
a
minimum
current
to
remain
conducting
after
triggering
.
Parallel
a
resistance
with
a
low
current
coil
to
guarantee
the
holding
current
,
if
necessary
.
6
.
Do
not
attempt
to
manually
operate
target
vanes
on
CIRCUIT
-
SHIELD
overcurrent
relays
.
Although
the
targets
return
their
indication
under
shock
,
they
can
be
damaged
by
manual
operation
with
a
pencil
or
pointed
object
.
7
.
Do
not
apply
high
voltage
tests
to
solid
-
staie
relays
.
If
a
control
wiring
insulation
test
is
required
,
bond
all
terminals
together
and
disconnect
ground
wire
before
applying
test
voltage
.
8
.
Besuretonotetheconnectionstoterminals
9
,
10
,
and
11
(
described
under
CONNECTIONS
on
page
3
)
required
for
the
proper
operation
of
the
TIME
and
INSTANTANEOUS
elements
.
Jumper
links
are
supplied
with
all
relays
.
9
.
Only
the
lower
circuit
ooard
of
the
CIRCUIT
-
SHIELD
overcurrent
relay
is
removable
.
This
board
should
insert
smoothly
.
Do
not
use
force
.
10
.
Note
that
removal
of
the
tap
block
pin
is
equivalent
to
setting
the
highest
tap
.
11
.
Follow
test
instructions
to
verify
that
the
relay
is
in
proper
working
order
.
CAUTtON
:
Since
troubleshooting
entails
working
with
energized
equipment
,
caution
should
be
taken
to
avoid
personal
shock
.
Only
competent
technicians
familiar
with
good
safety
practices
should
service
these
devices
.
Introduction
Precautions
Placing
Relay
into
Service
Testing
While
in
Service
Application
Data
Calibration
and
Acceptance
Testing
Pg
.
2
Pg
.
2
Pg
.
3
Pg
.
3
Pg
.
4
Pg
18
INTRODUCTION
These
instructions
contain
the
information
required
to
properly
install
,
operate
,
and
test
the
complete
line
of
Type
51
solid
-
state
overcurrent
relays
.
The
CIRCUIT
-
SHIELD
overcurrent
relay
is
housed
in
a
semi
-
flush
drawout
relay
suitable
for
conventional
panel
mounting
.
All
connections
to
the
relay
are
made
at
terminals
located
on
the
rear
of
the
case
and
clearly
numbered
,
one
(
1
)
through
twelve
(
12
)
.
CURRENT
,
TIME
,
and
INST
,
pickup
controls
are
lo
-
cated
on
the
front
panel
behind
a
removable
clear
plastic
cover
.
TIME
and
INST
,
target
indicators
are
also
mounted
on
the
front
panel
.
Both
targets
are
reset
by
means
of
a
pushbutton
extending
through
the
relay
cover
.
PRECAUTIONS
The
following
precautions
should
be
taken
when
applying
solid
-
state
relays
:
1
.
Incorrect
wiring
may
result
in
damage
to
solid
-
state
relays
,
Be
sure
wiring
agrees
with
the
connection
diagram
for
the
particular
relay
before
the
relay
is
energized
.
Be
sure
control
power
is
applied
in
the
correct
polarity
before
applying
control
power
.
2
.
Apply
only
the
rated
control
voltage
marked
on
the
relay
front
panel
.
Unlike
conventional
relay
contacts
,
solid
-
state
outputs
are
rated
for
a
particular
control
voltage
.
If
rectified
AC
voltage
is
used
in
place
of
a
battery
,
proper
filtering
will
be
required
to
insure
SCR
"
Holding
Current
"
.
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
3
SOLID
-
STATE
OVERCURRENT
RELAYS
PLACING
THE
RELAY
INTO
SERVICE
Time
Dial
One
of
ten
(
10
)
time
-
current
curves
is
selected
by
a
two
-
element
control
labeled
TIME
on
the
left
side
of
the
relay
front
panel
.
a
)
A
ten
position
SWITCH
giving
discrete
steps
1
through
10
.
b
)
A
screwdriver
adjusted
VERNIER
providing
continuous
time
adjustment
between
steps
.
When
the
vernier
,
marked
“
ADJ
”
,
is
turned
to
the
extreme
counterclockwise
position
,
the
time
-
current
curve
shown
on
the
switch
has
been
selected
.
The
vernier
provides
a
continuous
time
adjustment
between
the
switch
selected
curve
and
the
curve
indicated
by
the
next
higher
number
.
Intermediate
positions
can
be
verified
by
test
.
Instantanoous
Instantaneous
pickup
is
selected
by
the
potentiometer
dial
on
the
right
side
of
the
relay
front
panel
.
The
dial
is
labeled
"
INST
.
"
The
markings
indicate
multiples
of
the
pickup
tap
setting
.
1
.
RECEIVING
,
HANDLING
,
STORAGE
Upon
receipt
of
the
CIRCUIT
-
SHIELD
relay
(
when
not
included
as
part
of
a
switchboard
)
examine
for
shipping
damage
.
If
damage
or
loss
is
evident
,
file
a
claim
at
once
and
promptly
notify
the
nearest
Asea
Brown
Boveri
Of
-
fice
.
Use
normal
care
in
handling
to
avoid
mechanical
damage
.
The
CIRCUIT
-
SHIELD
system
has
no
vital
moving
parts
and
if
kept
reasonably
clean
and
dry
,
has
no
practical
limit
to
its
operating
life
.
2
.
INSTALLATION
Mounting
The
outline
dimensions
and
panel
drilling
and
cutout
information
is
given
in
Figure
2
.
Connections
External
connection
diagram
is
shown
in
Figure
1
.
For
the
instantaneous
function
to
be
operable
Terminals
9
and
10
must
be
externally
shorted
.
Instantaneous
relay
operation
can
be
cancelled
for
reclosing
applications
by
using
an
external
supervisory
contact
connected
to
these
terminals
.
For
example
,
if
the
phase
one
(
1
)
tap
is
set
at
six
(
6
)
amperes
and
the
INST
dial
is
set
at
eight
(
8
)
,
the
INST
,
setting
is
:
For
the
TIME
function
to
be
operable
terminals
10
and
11
must
be
externally
shorted
.
The
TIME
function
can
be
cancelled
for
directional
or
voltage
control
by
using
an
external
supervisory
contact
connected
to
these
terminals
.
6
amps
X
8
=
48
amps
Consequently
,
an
instantaneous
trip
will
occur
at
48
amps
in
phase
one
(
1
)
of
the
relay
.
TESTING
IN
SERVICE
In
general
,
it
is
not
necessary
to
schedule
periodic
maintenance
of
this
relay
.
However
,
if
a
trip
test
is
desired
to
confirm
the
proper
functioning
of
the
system
,
the
following
procedure
can
be
used
.
Mounted
in
Switchgear
Tests
should
be
made
on
a
de
-
energized
main
circuit
.
If
tests
are
to
be
made
on
an
energized
circuit
,
be
sure
to
take
all
necessary
precautions
.
It
is
customary
to
test
the
trip
circuit
of
electro
-
mechanical
overcurrent
relays
by
manually
closing
the
trip
contacts
to
trip
their
associated
circuit
breakers
.
If
the
contacts
are
allowed
to
part
before
the
seal
-
in
contact
closes
,
the
relay
contacts
are
eroded
by
the
arc
.
Also
,
high
transient
voltages
will
appear
from
trip
bus
to
positive
.
This
problem
is
avoided
in
the
CIRCUIT
-
SHIELD
overcurrent
relay
by
the
operatic
nal
test
feature
.
Separate
pushbuttons
labeled
"
TRIP
'
'
are
provided
for
the
TIME
and
INST
,
functions
.
The
pushbuttons
,
recessed
to
prevent
accidental
operations
,
will
cause
the
breaker
to
trip
.
All
CIRCUIT
-
SHIELD
relays
have
metal
front
panels
which
are
connected
through
printed
circuit
board
runs
and
connector
wiring
to
a
terminal
at
the
rear
of
the
relay
case
.
The
terminal
is
marked
"
G
"
and
is
located
as
shown
in
Fig
.
2
below
.
In
all
applications
this
terminal
should
be
wired
to
ground
.
Special
care
must
be
taken
to
connect
control
power
in
the
proper
polarity
.
Reversing
plus
(
+
)
and
minus
(
-
)
will
cause
SCR
A
and
SCR
Bto
block
the
flow
of
trip
current
and
the
relay
will
not
function
.
For
capacitor
trip
applications
,
the
plus
{
+
)
output
of
the
capacitor
trip
device
must
be
connected
to
terminal
7
of
the
relay
,
the
negative
(
-
)
to
terminal
8
.
3
.
SETTINGS
Current
Pickup
Taps
A
tap
block
for
each
phase
is
located
on
the
relay
front
panel
.
Each
tap
block
provides
for
seven
(
7
)
pickup
settings
which
are
marked
in
CT
secondary
amperes
.
When
a
pin
is
pulled
out
.
that
phase
switches
to
the
maximum
tap
setting
.
The
pin
may
be
moved
with
the
relay
in
service
.
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
4
SOLID
-
STATE
OVERCURRENT
RELAYS
A
portion
of
the
control
voltage
is
applied
to
the
time
circuit
when
the
TIME
pushbutton
is
depressed
.
The
time
del
$
y
circuit
then
produces
a
trip
signal
,
in
a
time
corresponding
to
approximately
two
(
2
)
multiples
of
current
tap
setting
,
(
at
nominal
control
voltage
)
,
and
the
TIME
target
operates
.
For
this
test
the
INST
,
pickup
must
be
set
above
(
2
)
multiples
or
the
INST
,
element
will
trip
first
.
Similarly
,
a
portion
of
the
control
voltage
is
applied
to
the
INST
,
circuit
when
the
INST
,
pushbutton
is
depressed
,
producing
a
trip
signal
and
operating
the
INST
,
target
.
On
special
three
phase
relays
with
individual
phase
targets
,
the
tests
described
will
cause
the
middle
phase
target
to
operate
in
addition
to
the
TIME
or
INST
,
target
.
Test
Accessory
A
test
accessory
which
can
be
used
to
quickly
check
the
primary
C
.
T
.
'
s
,
the
upper
non
-
drawout
input
section
of
the
relay
,
control
power
,
and
the
continuity
of
the
trip
circuit
is
available
from
the
factory
.
This
drawout
test
accessory
is
plugged
into
the
relay
in
place
of
the
drawout
element
to
make
the
checks
.
See
IB
-
7.2
.
1.7
-
2
for
details
.
These
overcurrent
relays
are
offered
with
the
follow
-
ing
pickup
ranges
:
Taps
$
Range
0.1
,
0.15
,
0.2
,
0.25
,
0.3
,
0.4
,
0.5
0.1
-
0.5
0.5
,
0.6
,
0.8
,
1.0
,
1.2
,
1.5
,
2.0
0.5
-
2.0
1.5
,
2.0
,
2.5
,
3
,
4
,
5
,
6
1.5
-
6.0
2
,
5
,
2.8
,
3.1
,
3.5
,
4.0
,
4.5
,
5.0
2.5
-
5
2.5
,
3.75
,
5
,
6.3
,
7.5
,
8.6
,
10
2.5
-
10
4
,
5
,
6
,
7
,
8
,
10
,
12
4
-
12
$
When
tap
plug
is
removed
,
affected
phase
reverts
to
the
maximum
pickup
.
TOLERANCES
TIME
PICKUP
TIME
DELAY
dial
#
10
(
2
-
20
multiples
)
dial
#
1
(
2
-
20
multiples
)
±
5
%
of
tap
setting
±
5
%
10
ms
or
±
10
%
(
whichever
is
larger
)
±
10
%
of
pickup
amps
(
tap
x
dial
setting
)
INST
.
PICKUP
RATINGS
APPLICATION
DATA
TEMPERATURE
The
Type
51
series
of
overcurrent
relays
provide
overcurrent
protection
phase
-
to
-
phase
or
phase
-
to
-
ground
.
They
are
designed
to
be
operated
by
standard
five
(
5
)
ampere
secondary
current
transformers
.
The
output
circuit
(
trip
circuit
)
will
operate
conventional
cir
-
cuit
breaker
trip
coils
at
the
DC
voltage
specified
on
the
relay
nameplate
.
These
relays
can
oe
used
for
all
applications
where
conventional
electromechanical
relays
are
used
.
They
come
in
seven
different
time
-
current
curve
families
,
INVERSE
(
511
)
,
VERY
INVERSE
(
51
Y
)
,
EXTREMELY
INVERSE
(
51
E
)
,
SHORT
TIME
(
51
S
)
,
LONG
TIME
(
51
L
)
,
DEFINITE
TIME
(
51
D
)
,
LONG
TIME
INVERSE
(
51
IM
)
,
and
LONG
TIME
VERY
INVERSE
(
51
YM
)
.
A
standard
INSTANTANEOUS
function
or
a
special
INVERSE
INSTANTANEOUS
function
can
be
furnished
as
an
option
with
any
of
the
time
families
.
.
..
25
°
C
ambient
-
15
CC
to
+
55
°
C
-
30
°
C
to
+
70
°
C
Nominal
Additional
±
5
%
tolerance
Must
operate
FREQUENCY
Nominal
Additional
±
5
%
tolerance
60
Hertz
.
+
1
to
-
3
Hertz
INPUT
CIRCUIT
Phase
one
(
1
)
current
—
terminals
1
and
2
.
Phase
two
(
2
)
current
—
terminals
3
and
4
.
Phase
three
(
3
)
current
—
terminals
5
and
6
.
The
current
input
for
single
-
phase
relays
is
made
at
terminals
3
and
4
.
Each
input
current
is
fed
to
a
tapped
transformer
primary
.
The
secondary
winding
produces
a
voltage
across
a
burden
resistor
.
This
voltage
is
rectified
and
supplied
to
the
static
circuitry
.
The
pickup
of
the
static
circuit
is
adjusted
to
the
desired
pickup
current
by
tap
selection
of
the
transformer
primary
turns
.
Any
one
of
seven
control
voltages
can
be
obtained
:
24
Vdc
,
32
Vdc
,
48
Vdc
,
125
Vdc
,
250
Vdc
,
175
Vdc
(
120
Vac
capacitor
trip
)
,
350
Vdc
(
240
Vac
capacitor
trip
)
.
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
5
SOLID
-
STATE
OVERCURRENT
RELAYS
OUTPUT
CIRCUIT
The
CIRCUIT
-
SHIELD
overcurrent
relay
energizes
the
breaker
trip
coil
by
means
of
an
output
SCR
.
Two
SCR
’
s
are
provided
,
one
for
the
time
delay
and
pne
for
the
instantaneous
circuit
as
indicated
in
the
wiring
diagram
shown
in
Figure
1
.
As
shown
,
relay
terminal
7
is
connected
to
the
control
power
positive
,
with
the
trip
coil
connected
to
relay
terminal
12
through
a
52
/
a
contact
.
SCR
A
is
gated
by
the
time
delay
circuit
,
while
SCR
B
is
gated
by
the
instantaneous
circuit
.
Note
that
once
an
SCR
is
gated
(
turned
on
)
,
it
will
remain
in
conduction
until
its
anode
current
falls
below
its
holding
current
which
typically
is
5
to
20
milliamperes
.
Consequently
,
the
trip
coil
current
must
be
interrupted
with
the
52
/
a
contact
.
INPUT
CURRENT
RATINGS
Input
Current
,
1
0
or
3
0
(
CT
Secondary
Amperes
)
Tap
Range
.
A
Time
0
1
-
0.5
0.5
-
2.0
1.5
-
6.0
2.5
-
5.0
2.5
-
10
300
multiples
of
pickup
tap
setting
or
235
A
rms
.
whichever
is
less
.
1
Second
390
A
rms
4
-
12
Continuous
All
Ranges
1.5
multiples
of
pickup
tap
setting
.
BURDEN
The
burden
of
the
Circuit
Shield
overcurrent
relay
is
very
low
,
allowing
the
use
of
current
transformers
which
would
give
unsatisfactory
performance
if
they
were
driving
electro
-
mechanical
relays
.
Because
the
input
characteristic
of
the
Circuit
Shield
relay
is
nonlinear
,
an
impedance
cannot
be
specified
,
however
,
the
burden
voltage
across
the
relay
current
inputterminals
can
be
readily
calculated
for
any
given
value
of
current
transformer
secondary
current
:
OUTPUT
TRIP
CIRCUIT
RATINGS
Max
.
Current
,
Amps
DC
Range
of
Operation
Nominal
Voltage
6
Cycles
1
Second
Continuous
24
Vdc
32
Vdc
48
Vdc
125
Vdc
250
Vdc
175
Vdc
350
Vdc
18
-
30
24
-
40
28
-
60
70
-
140
140
-
280
100
-
195
200
-
385
1.0
TAP
Roc
+
Is
x
R
V
=
IT
(
AMPS
)
OHMS
30
1
15
V
=
burden
voltage
(
volts
)
Is
=
current
transformer
secondary
current
(
amperes
)
IT
=
relay
pickup
current
tap
setting
(
amperes
)
R
=
D
C
.
resistance
of
relay
input
circuit
(
ohms
)
(
select
from
table
)
0
5
092
0.6
.
078
0
8
065
*
Capacitor
Trip
Applications
1.0
055
048
1 2
TARGET
CIRCUITS
The
target
indicators
for
the
TIME
and
INST
,
circuits
are
polarity
sensitive
devices
which
are
set
by
current
flow
through
the
corresponding
trip
SCR
.
Target
reset
is
accomplished
by
the
control
power
connection
(
terminals
7
and
8
of
Figure
1
)
through
the
TARGET
RESET
pushbutton
.
Standard
relays
have
2
targets
TIME
and
INST
.
Three
phase
relays
may
be
specially
ordered
with
5
targets
—
TIME
,
INST
,
and
PHASE
targets
.
These
3
additional
targets
wil
indicate
which
phase
currents
are
in
excess
of
tap
setting
when
the
relay
trips
the
breaker
.
.
040
1.5
2.0
032
NOTES
:
1.5
.
042
1
.
for
units
with
0.1
to
0.5
A
tap
range
,
the
Is
x
R
term
is
negligible
.
2.0
034
2
,
5
038
2
.
for
units
with
2
to
5
A
tap
range
,
use
values
shown
for
1.5
to
6
A
unit
.
3.0
.
026
4.0
.
022
5.0
020
6.0
.
0185
4
.
020
5
.
020
6
.
0185
7
.
0175
FREQUENCY
RATING
See
page
17
.
8
.
017
10
.
0165
12
.
0165
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
6
SOLID
-
STATE
OVERCURRENT
RELAYS
Internal
Connection
Diagrams
12
D
223
A
TIME
-
OVERCURRENT
RELAYS
Type
51
(
with
or
without
Instantaneous
)
Single
Phase
Relays
—
omit
coils
1
-
2
and
5
-
6
)
(
Two
Phase
Relays
—
omit
coil
3
-
4
)
°
~
Vo
4
*
3
?
V
?
rV
?
7
I
TEST
11
L
.
10
L
.
9
o
o
u
£
E
1
0 8
O
’
TIME
12
30
£
LIT
-
10
o
'
*
J
>
TEST
(
-
)
(
)
I
T
TARGET
Vw
'
l
TT
«
U
»
towm
Ce
*
wc
«
»
<
•
»
UMdl
1
MST
.
Not
*
:
User
to
remove
links
Ly
or
L
|
only
if
torque
-
control
contacts
are
to
be
used
:
1
.
Remove
only
Lx
for
torque
-
control
of
51
.
(
Time
element
)
2
.
Remove
only
L
|
for
torque
control
of
50
.
(
Instantaneous
element
)
$
2
*
3
in
Three
-
phase
and
ground
with
instantaneous
52
—
i
1
i
-
i
i
i
i
i
6
5
4
3
2
1
12
M
10
9
0
7
1
u
O
O
*
o
o
6
5
4
3
2
FIGURE
1
Internal
Connections
and
Typical
External
Connection
Diagram
i
I
2
H
I
0
9
0
HB
*
—
O
TRIPPING
BUS
RELIABLE
O
.
C
.
SUPPLY
52
5
«
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
7
SOLID
-
STATE
OVERCURRENT
RELAYS
I
l
I
TIME
-
CURRENT
CHARACTERISTICS
6
.
1
.
09
U
5
.
08
.
07
-
4
CIRCUIT
©
SHIELD
®
.
06
3
.
05
Type
50
§
8
.
04
§
-
2
fc
S
03
1
AJ
.
02
1
»
.
01
o
o
ooooo
*
3
*
LT
3
CD
h
>
QOO
)
0
o
Tf
LO
CO
r
»
oocno
o
o
LO
co
r
^
ooo
»
*
—
co
CM
o
ro
CM
CM
MULTIPLES
OF
INST
.
SETTING
(
TAP
X
INST
.
DIAL
)
TYPE
50
INSTANTANEOUS
Oct
.
19
,
1971
TCC
605807
6
5
4
3
3
C
2
1
TYPE
501
INVERSE
INSTANTANEOUS
Aug
29
,
1972
TCC
605812
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
8
SOLID
-
STATE
OVERCURRENT
RELAYS
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
*
SOLID
-
STATE
OVERCURRENT
RELAYS
Courtesy of NationalSwitchgear.com
IB
-
7.2
.
1.7
-
1
PAGE
10
SOLID
-
STATE
OVERCURRENT
RELAYS
Courtesy of NationalSwitchgear.com