SACE Tmax XT
XT1-XT2-XT3-XT4
FC CuAl e t. - Terminali esterni per cavi x XT1-XT2-XT3-XT4.
FC CuAl ext. - External terminals for cables XT1-XT2-XT3-XT4.
FC CuAl ext. - Externe Anschlusse fur Kabel XT1-XT2-XT3-XT4.
FC CuAl ext. - Prises extèrieures pour càbles XT1-XT2-XT3-XT4.
FC CuAl ext. - Terminales exteriores para cables XT1-XT2-XT3-XT4.
Doc. N.° 1SDH000719R0816 - B1247
1
XT1 XT3 XT2 XT4
1
F-P-W
2 2
XT2 - 70 mm ...185 mm
III IV
1(2)
3(6)
3(6)
1(2)
4(8)
4(8)
2 2
XT2 - 2x35 mm ...70mm
III IV
1(2)
3(6)
3(6)
3(6)
1(2)
4(8)
4(8)
4(8)
2 2
XT1 - 35 mm ...95 mm
III IV
3(6) 4(8)
1(2)
1(2)
XT3 - 2 2
2x35 mm ...120 mm
III IV
1(2)
3(6)
1(2)
3(6)
1(2)
4(8)
1(2)
4(8)
XT4 - 2 2
2x35 mm ...120 mm
III IV
1(2)
3(6)
3(6)
3(6)
1(2)
4(8)
4(8)
4(8)
1(2) 1(2) 1(2) 1(2)
1(2) 1(2) 1(2) 1(2) 1(2) 1(2)
XT2 - 2x2 AWG...2/0 AWG XT3 - 2x2 AWG...250 Kcmil
XT2 - 2/0 AWG...350 Kcmil XT4 - 2x2 AWG...250 Kcmil
XT1 - 2 AWG...4/0 AWG
SACE Tmax XT | ABB
3
5
12
XT1 - XT2 - XT3 - XT4 2 2
XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)
4
62 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
ONLY FOR XT1F - XT3F ONLY FOR XT2 F- XT4 F
2 2
XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)
2
1
FOR XT1F UL ONLY
FOR UL ONLY
2
1
FOR UL ONLY
FOR UL ONLY
6 Nm
2
13
4
53 lb in
16 MIN
0.63" MIN
13.5 Nm
2
1
120 lb in
2
MAX 95 mm
2
MIN 35 mm
CuAl
Stranded
CuAl
Flexible
MAX 4/0 AWG
MIN 2 AWG
1
3
4
2
6 Nm
53 lb in
5
SACE | ABBTmax XT
9
11
78
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil) 2 2
XT3 - FC-CuAl EXT- 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
10
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2
XT3 - FC-CuAl EXT- 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
100 (3.94")
42 MIN
1.65" MIN
22 MIN
0.87" MIN
16 Nm
142 lb in
31 Nm
274 lb in
1
3
2
20 MIN
0.79" MIN
2
MAX 185 mm
2
MIN 70 mm
CuAl
Stranded
CuAl
Flexible
MAX 350 Kcmil
MIN 2/0 AWG
- Attenzione: fissare i cavi
al quadro prima di serrare i
morsetti; Setti di ancoraggio
a cura del cliente.
- Important note: fit the
cables to the switchboard
before tightening the
terminals; Anchor plates to
be supplied by the
customer.
- Achtung: vor dem
Festziehen der Klemmen
die Kabel an der
Schaltanlage befestigen;
Verankerungswände vom
Kunden beizustellen.
- Attention: fixer les
câbles au tableau avant
de serrer les bornes;
Secteurs d’ancrage à
la charge du client.
- Atención: sujetar los
cables al cuadro antes
de apretar los bornes;
Placas de anclaje a cargo
del cliente.
2
MAX 150 mm
2
MIN 35 mm
CuAl
Stranded
CuAl
Flexible
MAX 300 Kcmil
MIN 2 AWG
1
L 18 mm
L 0.71"
3
4
2
L 20 mm
L 0.79"
8 Nm
71 lb in
5
SACE Tmax XT | ABB
13 14
12
15
2
XT3 - FC-CuAl EXT- 2x120 mm (2x250 Kcmil)
2 2
XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG)
2 2
XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG)
2. 2
XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
3 POLES
81,5 (3.21")
81,5 (3.21")
A
B
4 POLES
64 (2.52")
99 (3.90") Ø 2,6
Ø 0.10"
AB
17,5
0.69"
17,5
0.69"
X
122 (4.80")
70 (2.76") (IV POLES ONLY)
X
155 (6.10")
Ø 4,5
Ø 0.18"
1,1 Nm
9.7 lb in
5
1
3
2
3
1
3
3
4
XT2
18/33 (0.71"/1.30")
A
XT4
22/42 (0.87"/1.65") XT2 12 Nm/106 lb in
XT4 16 Nm/142 lb in
1
A MIN
2
MAX 70 mm
2
MIN 35 mm
CuAl
Stranded
CuAl
Flexible
MAX 2/0 AWG
MIN 2 AWG
MAX 250 Kcmil
MIN 2 AWG
2
MAX 120 mm
2
MIN 35 mm
XT2
XT4
2. 2
XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
53 lb in
3
4
2
1
6 Nm
571 lb in
3
4
2
L 18 mm
L 0.71"
L 20 mm
L 0.79"
1
8 Nm
5
SACE | ABBTmax XT
17
19
16
2 2
XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)
18
20
XT1 - XT2 - XT3 - XT4
1
3
2
1
2
2
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
P-W
XT2
III IV
1(2)
XT3
III IV
1(2)
XT1
III IV
1(2)
XT4
III IV
1(2)
2(4) 2(4) 2(4) 2(4)
2(4) 2(4) 2(4) 2(4)
1(2) 1(2)1(2) 1(2)
XT1 - XT2 - XT3 - XT4
2 2
XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)
2
3
1
4
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
SACE Tmax XT | ABB
26
25
23 24
2 2
XT3 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
2 2
XT3 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
23 24 2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
23 24 2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
21 22 2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil) 2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil) 22 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2
XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
100
31 Nm
274 lb in
1
3
2
- Attenzione: fissare i cavi
al quadro prima di serrare
i morsetti;
Setti di ancoraggio a cura
del cliente.
- Important note: fit the
cables to the switchboard
before tightening the
terminals; Anchor plates
to be supplied by the
customer.
- Achtung: vor dem
Festziehen der Klemmen
die Kabel an der
Schaltanlage befestigen;
Verankerungswände vom
Kunden beizustellen.
- Attention: fixer les câbles
au tableau avant de serrer les
bornes; Secteurs d’ancrage
à la charge du client.
- Atención: sujetar los cables
al cuadro antes de apretar los
bornes; Placas de anclaje a
cargo del cliente.
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
1
3
4
2
5
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
1
L 20 mm
L 0.79"
3
4
2
5
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
L 18 mm
L 0.71"
27
© Copyright 2011-2017 ABB. All rights reserved.
www.abb.com
2 2
XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
2 2
XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG)
2 2
XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
28
30
29
2 2
XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG)
2 2
XT3 - FC-CuAl EXT - 2x35 mm ...150 mm (2x2 AWG...250 Kcmil)
For more information please contact:
ABB S.p.A.
ABB SACE Division
Via Pescaria, 5
24123 Bergamo - Italy
Phone: +39 035 395 111
1
3
2
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
Ø 2,6
Ø 0.10"
CB
43,5
1.71"
X
50
1.97"
X
225
8.85"
Ø 4,5
Ø 1.78"
A
Y
Y
3 POLES
43,5 (1.71")
81,5 (3.21")
A
B
4 POLES
78,5 (3.09")
64 (2.52")
81,5 (3.21")
C99 (3.90")
2,5 Nm
22 lb in
5
1
3
2
1
3
4
1
3
4
2
5
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
3
4
2
5
Per l’installazione fare
riferimento a interruttore
fisso
For installation refer to
fixed circuit-breaker
Für die Installation zu
festen Leistungsschlater
beziehen
Pour l'installation reporter
à le disjoncteur fixe
Para la instalación
consulte el interruptor fijo
L 18 mm
L 0.71"
1
L 20 mm
L 0.79"

Other manuals for SACE Tmax XT

12

Other ABB Touch Terminal manuals

ABB REL 551 2.5 User manual

ABB

ABB REL 551 2.5 User manual

ABB REL 561*2.5 User manual

ABB

ABB REL 561*2.5 User manual

ABB REF 541 User manual

ABB

ABB REF 541 User manual

ABB SACE Tmax T7D/PV User manual

ABB

ABB SACE Tmax T7D/PV User manual

ABB REF 541 User manual

ABB

ABB REF 541 User manual

ABB REB 551-C4 2.5 Series User manual

ABB

ABB REB 551-C4 2.5 Series User manual

ABB SPAC 536 C User manual

ABB

ABB SPAC 536 C User manual

ABB Symphony Harmony Series User manual

ABB

ABB Symphony Harmony Series User manual

ABB RE 54 User manual

ABB

ABB RE 54 User manual

ABB Welcome M25102 C Series User manual

ABB

ABB Welcome M25102 C Series User manual

ABB REL 551-C1 2.3 Series Guide

ABB

ABB REL 551-C1 2.3 Series Guide

ABB REL 505-C1 2.3 Series Guide

ABB

ABB REL 505-C1 2.3 Series Guide

ABB REL 551-C1*2.5 Product manual

ABB

ABB REL 551-C1*2.5 Product manual

ABB REM 54 Series Product manual

ABB

ABB REM 54 Series Product manual

ABB CP410 User manual

ABB

ABB CP410 User manual

ABB REF 54 Series Use and care manual

ABB

ABB REF 54 Series Use and care manual

ABB RET 54 Series Use and care manual

ABB

ABB RET 54 Series Use and care manual

ABB SPAC 315 C Parts list manual

ABB

ABB SPAC 315 C Parts list manual

ABB REB 551-C3*2.5 Guide

ABB

ABB REB 551-C3*2.5 Guide

ABB REO 517 Instructions for use

ABB

ABB REO 517 Instructions for use

ABB Unifix AD 1STQ004320B0000 manual 

ABB

ABB Unifix AD 1STQ004320B0000 manual 

ABB SPAC 310 C Parts list manual

ABB

ABB SPAC 310 C Parts list manual

ABB SPAC 531 C Parts list manual

ABB

ABB SPAC 531 C Parts list manual

ABB REF 54 Series Product manual

ABB

ABB REF 54 Series Product manual

Popular Touch Terminal manuals by other brands

Varian 969-9860 instruction manual

Varian

Varian 969-9860 instruction manual

FlyTech POS455 user manual

FlyTech

FlyTech POS455 user manual

Allen-Bradley PanelView Plus 2711P user manual

Allen-Bradley

Allen-Bradley PanelView Plus 2711P user manual

Festo CPV10-GE-ASI-4E3A-Z M8 Brief description

Festo

Festo CPV10-GE-ASI-4E3A-Z M8 Brief description

Sharp RZ-X650 user guide

Sharp

Sharp RZ-X650 user guide

CDVI ievo IFACE manual

CDVI

CDVI ievo IFACE manual

HP Rp5000 - Point of Sale System Getting started

HP

HP Rp5000 - Point of Sale System Getting started

VeriFone V400c instructions

VeriFone

VeriFone V400c instructions

Sagem Securite MorphoAccess J-Bio user guide

Sagem Securite

Sagem Securite MorphoAccess J-Bio user guide

Casio DT-X8 Series user guide

Casio

Casio DT-X8 Series user guide

Festo CPV-GE-DN3-8 Series manual

Festo

Festo CPV-GE-DN3-8 Series manual

VeriFone PinPad VX520 instructions

VeriFone

VeriFone PinPad VX520 instructions

C-Data FD704GW user manual

C-Data

C-Data FD704GW user manual

Omron WT30 Specification sheet

Omron

Omron WT30 Specification sheet

POSIFLEX HT-3200 SERIES Technical manual

POSIFLEX

POSIFLEX HT-3200 SERIES Technical manual

First Data FD130 Quick reference guide

First Data

First Data FD130 Quick reference guide

Festo CPX-FB33 manual

Festo

Festo CPX-FB33 manual

BIXOLON BCD-3000 Installation Guide & Safety Guide

BIXOLON

BIXOLON BCD-3000 Installation Guide & Safety Guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.