1. Technical specications
Enclosure and operating conditions
Enclosures Wall mouting
Dimensions (L x W x H) 280 x 242 x 42 (mm)
Weight 1360gr (with battery and GSM module)
Operating temperature 0°C ... +50°C
Storage temperature 0°C ... +85°C
Relative humidity 20% - 85% (non-condensing)
IP code IP42
Operating altitude Up to 2000 metres
Regulations
EMC EN 301 489-1 V2.1.1 / EN301 489-3 V1.6.1
LVD EN-IEC 62368-1:2014 + AC:2015 + A11:2017 + AC:2017
System properties
Contact inputs Voltage 30VDC Max
Vil <3V
Vih >4V
Note • 10k pull-up to 12VDC
• Input can be a contact to GND or a voltage
Relay contact Max load 30VDC / 2A, 30VAC / 1A (resistive load)
Open-drain output Max switch voltage 12V/300mA
Output voltage 12V/120mA
Protection Short-circuit, thermal
USB (master) Type 2.0
Load 5V/500mA
I/O bus Output voltage 12V/100mA
Driver ISL3152 met “external fail-save biasing”
PSTN Line RJ11
Phone RJ11
Ethernet Type 10Base-T/ 100Base-T
Auto MDIX Yes
Intended use Indoor
Mobile network (GSM) Bands LTE Cat. 4
3G HSPA+
FDD LTE: B1/B3/B5/B7/B8/B20
TDD LTE: B38/B40/B41
WCDMA: B1/B5/B8
GSM: 900/1800
Bandwidth 1.4/3/5/10/15/20 MHz
Power Class 3 (23dBm±2dB) for LTE FDD
Class 3 (23dBm±2dB) for LTE TDD
Class 3 (24dBm +1/-3dB) for TD-SCDMA
Class 3 (24dBm +1/-3dB) for UMTS
Class E2 (27dBm ±3dB) for EDGE 850/900MHz
Class E2 (26dBm +3/-4dB) for EDGE 1800/1900MHz
Class 4 (33dBm ±2dB) for GSM 850/900MHz
Class 1 (30dBm ±2dB) for GSM 1800/1900MHz
Power consumption Nominal 5 Watt
Maximal 20 Watt
Imax 0,22A
Input voltage range 100 ... 240VAC +/- 10%, 50/60 Hz
Tag Frequency 13.56MHz
Max range 10mm
Lifespan (Calculated MTBF) 10.64 years, according to parts count method

2. Installation
2.1. Mounting
The Octalarm-Touch housing is suitable for wall mounting:
• mount screws in the wall or panel;
• slide the device’s mounting holes over them.
Caution: keep in mind that the screws must be able to support
at least 1360 grams combined.
2.2. Connecting
The connection sticker shows how to connect the various cables.
power line phone usb eth battery
p
1
no nc
p
2
no
A B
12V
1 2 3 4 5 6 7 8out
+12V
nc
1 2
relais
IO bus
RS485
gnd
2.3. Stable internet connection
You should connect the Octalarm alarm dialler to a stable
internet connection. If a rewall is used in the corporate network,
please refer to the information What to do in case of a rewall in
the corporate network (https://docs.octalarm.com/link/rewall/
en-GB):
Connector description
1 Primary power (C5 connector)
2 PSTN line in (RJ11)
3 PSTN Phone (RJ11)
4 USB port for service purposes
5 Ethernet RJ45
6 Relay contacts
7 Open-drain outputs
8 Inputs
9 RS485 data connection
10 Connector for batterij
3. Components explained
3.1. Screen
Scherm pictogrammen
1 Touchscreen
2 RFID reader
(Keep the supplied RFID Tag within 10
mm of the RFID scanner.)
Caution: using sharp objects on the touchscreen may cause
damage.
3.2. Power
Insert the supplied power cable into the S-shaped holder; this
creates a strain relief.
Caution: the power supply cable must comply with
IEC 60227-1.
3.3. Battery
Battery compartiment
1 Velcro fastener
2 Battery connector location
Caution: only use the battery for the Octalarm-Touch (A-Batt-
6,4V) supplied by Adésys! This battery has been developed by
Adésys, has been fully tested and has a communication chip.

3.4. PSTN conguration
You can connect the dialler to PSTN in 2 ways:
1. via a private PSTN line;
2. via a shared PSTN line with other equipment, such as a fax
machine.
• In both situations, connect the PSTN line to the “Line” (RJ11)
socket.
• Connect any other equipment to the “Phone” (RJ11) socket.
In this way, the PSTN line is never busy for alarm calls. However,
due to a “Line-Seize” relay, all other PSTN devices temporarily
lose their connection during alarms.
Caution: check the operation of the “Line Seize” relay
immediately after installation and perform this test periodically.
3.5. Antenna
• Connect the desired antenna to the primary SMA connector
(upper). You can use the supplied antenna (AA-114) if
required.
• In case of poor reception conditions, a diversity antenna can
be connected to the lower SMA connector.
3.6. GSM module
Each dialler has a GSM module with an unactivated SIM card. You
can activate this SIM card during onboarding (conclusion of the
Octalarm Connect service).
Inserting your own SIM card
• Remove the GSM module from the device.
• Replace the SIM card on the back of the GSM module for your
own SIM card (4G with LTE Cat-M1 band).
• Slide the module back into the GSM compartment until it
clicks.
3.7. EM-8001 (external module): number of inputs increased
The EM-8001 can be used to extend the number of inputs on the
Octalarm-Touch to 16 or even 24 (max. 2 modules per alarm).
The EM-8001 is connected to the Octalarm-Touch via the I/O bus
(RS485).
4. Labels
Label enclosure, Europe (51x25mm)
Label packaging, Europe (71x36mm)
Battery label, Europe (40 x 25mm)

5. Accessories included
6. Legislation and regulations
6.1. Safety rules
• Mount the device on a solid panel or wall.
• Mount the dialler below a height of 2 metres.
• Protect the Octalarm-Touch against a surge by using a
grounded power connection.
• Do not use an outdoor ethernet connection directly, instead
use a surge protected switch or router.
• Use the Octalarm-Touch in an indoor setting, the device
needs to be protected from direct weather exposure.
• The device operates at temperatures from 0°C to +50°C.
Using the Octalarm-Touch outside this temperature range
may result in damage.
• This equipment is not suitable for use in locations where
children are likely to be present.
• When recycling and/or disposing, take into account the
regulations in force in your country.
Battery handling guide
• Only use the battery for the Octalarm-Touch (A-Batt-6.4V)
supplied by Adésys. This battery has been developed by
Adésys, has been fully tested and has a communication chip.
• Do not expose battery to temperature over +85°C or an open
ame.
• Do not damage the Octalarm-Touch battery, for example by
dropping, deforming, impacting, cutting or penetrating with a
sharp object.
• Do not charge or discharge damaged battery.
• Keep the battery away from direct contact with liquids. Do
not use if battery is wet or moist is visible.
• When recycling and/or disposing, take into account the
regulations in force in your country.
6.2. Maintenance
• Change the battery every 3 years.
• Keep the screen clean of grease, water and dust.
• The calculated lifespan is 10.64 years. Replace the Octalarm-
Touch after this period has elapsed.
Power cable
Length: 1,5 metres
Connector type: C5
Plug: EU-plug
Battery (A-Batt-6,4V)
Rechargeable LiFePO4 battery
LFR18650-2S
6.4 V/1500mAh
9.6Wh
GSM module
LTE Cat. 4 (sim card included)
Caution:
the SIM card is not activated by default. You
can activate it during installation and use it
to subscribe to Octalarm Connect.
Antenna (AA-114)
SMA connector
Tag
Number: 3 pieces
Type: RFID
13.56MHz
Quickstart
Installation manual in:
• English (EN)
• Dutch (NL)
• German (DE)
• French (FR)
6.3. Storage and transport
• Store and transport the product on a at surface.
• There must be no ammable or explosive materials nearby.
• The storage temperature is between 0°C and +85°C.
• Do not store this product in a place exposed to direct
sunlight.
• It is not recommended to have the dialler disconnected from
the mains for more than a year, because:
• the internal clock will then lose the correct time/date;
• this negatively aects the battery life.
6.4. Malfunctions and repairs
When a fault has occurred please contact Adésys service
helpdesk. By opening the Octalarm-Touch the warranty is
void. Repairing the Octalarm-Touch is only allowed by Adésys
appointed experts.
6.5. Recycling and disposal
If the Octalarm-Touch or the battery is at the end of its service
life, please observe the regulations in force in your country when
disposing of it.
6.6. Warranty and liability
Each product is subjected to a series of comprehensive tests by
Adésys before shipment. The warranty claim is void when:
• the defect has been caused by gross negligence or
incompetent installation;
• repairs and/or modications have been made to the
equipment without permission from Adésys;
• the serial number is removed or damaged.
Adésys products do not oer a 100% guarantee against damage,
but are only a tool to prevent damage. Therefore, please discuss
the remaining risk with your insurer.
All our transactions are subject to the Terms and Conditions of
the ‘Metaalunie’ 2019, led at the Registry of the District Court in
Rotterdam on 1 January 2019.
In accordance with article 13 of these Terms and Conditions of
the ‘Metaalunie’, Adésys accepts no liability for consequential
damage caused by inexpert use of, and/or faults in its products.
In addition to the applicable Terms and Conditions of the
‘Metaalunie’, both Clients and Contractor are obliged to comply
with the applicable laws and regulations relating to sanction
countries.
6.7. Fields of application | Certication
Adésys products are only provided with a CE quality mark,
which makes them exclusively suitable for application within the
European Economic Area (EEA).

Molenweer 4
2291 NR Wateringen
The Netherlands
+31 174 794022
www.adesys.nl
Complete manual available on website
How to optimally use your dialler
Create a free account at portal.octalarm.com
Remote setup and management
View current status alarms
Installer can provide remote support
Possible to use app “Adesys Alarm”
Download the free app “Adesys Alarm”
Access your dialler(s) literally from your pocket
High priority alarms always on your mind
Location alarm immediately visible via app alarm
Activate Octalarm Connect
Reliable VoIP / SIP and GSM calling connection set up
in one go
Fixed price per month (at fee)
24/7 secured duplicate servers
a
a
a
a
a
a
a
a
a
a
a
https://docs.octalarm.com/link/manual-octalarm/en-GB
Other manuals for Octalarm-Touch
3
This manual suits for next models
1
Table of contents
Other Adesys Security System manuals