Advanced Air AIR CONTROL 0400FME User manual

0400_IOM_1.1_Mar21_1
1
AIR CONTROL
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
MODEL 0400
FIRE DAMPER

0400_IOM_1.1_Mar21_2
2
Page
Introduction and Health & Safety 3
Circular fire damper – Model 0400MAN
Two hour flexible wall 4
Two hour rigid wall 5
Circular fire damper – Model 0400FME
Two hour flexible wall 6
Two hour rigid wall 7
Operation and Maintenance
Model 0400MAN 8
Model 0400FME 9
Wiring information
Model 0400FME 10
DW145 Fire Damper Certificate 11
Index

0400_IOM_1.1_Mar21_3
3
Introduction
Advanced Air (UK) Ltd have been manufacturing a comprehensive range of fire dampers and fire smoke
dampers since 1975. We have always taken pride in our products and tested to the highest standards,
originally to BS476 and now more stringent testing to CE labelling under the Construction Product Regulation
which was introduced 1st July 2013.
All our fire, fire smoke and smoke control dampers have been tested to BS EN 1366-2 and BS EN 1366-10.
This is to cover a variety of installations used on sites today. Under CE labelling all dampers must follow the
Product Standards BS EN 15650 and BS EN 12101-8 which ensures the product is consistent and supplied to
the same specification and standard as tested. Any deviation or changes from the installations in this manual
would require the dampers to be subject to a new test or approval sought from Local Building Control.
In line with product standards we are pleased to oer this installation manual covering installation, operation
and maintenance instructions together with Health and Safety information. We have also included within this
manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to
be completed by the installer. A separate certificate is required per damper.
The installation contained in this manual cover most installation on site. However, there are still installation
which Advanced Air (UK) Ltd have not yet tested. We are continually reviewing requirements and continuously
developing the products. As additional installation tests are carried out and classified, installations will be
added to this manual, and the Declaration of Performance (DoP) updated accordingly.
Health and Safety
Any instruction contained within this manual must be undertaken by competent trained personnel. When
completing the installation standard PPE should be used, steel toe cap boots, hard hat, gloves, protective
eyewear along with any other specific site or material instructions.
The size and weight of dampers vary, and it may require two or more persons to safely handle and move
them. Do not lift the dampers by the blades or the actuator.
For the installation of dampers at high level, the correct lifting equipment shall be used in accordance with
the Work at Height Regulations 2005 and specific site rules.
All waste materials should be collected and disposed of defined by the suppliers.

0400_IOM_1.1_Mar21_4
4
PRODUCT 0400MAN APPLICATION FLEXIBLE SUPPORTING CONSTRUCTION
CLASSIFICATION REPORT NO. P1054241003 CLASSIFICATION E120 VE I O
TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING.
FIRE 0400MAN CIRCULAR FIRE DAMPER IN FLEXIBLE SUPPORTING CONSTRUCTION
OPEN
CLOSE
Access door
Fire batt
Two hour rated flexible supporting
construction to BS EN 1363-1:2020
15mm thick gypsum boards
Steel stud depth – 71 to 100mm
Installation sequence
3 The drywall will consist of two layers of 15mm plasterboard on each side of steel studwork with an
optional 50mm mineral wool insulation. The opening will be a letterbox construction with overlapping
layers of plasterboard.
4 The damper should be mounted in the opening with the fixing flange (access side) flush with the wall.
5 Confirm that the blade is horizontal, and the handle is on the RH or LH. The flange can then be secured
to the wall using M3.5 x 38mm drywall screws which are to pierce the steel channel. Ensure that all the
pre-drilled holes are populated.
6 The gap between the damper and the wall opening will need filling with two layers of 50mm thick
140kg/m3fire batt cut to interference fit and pushed into place. All cut edges must be sealed with a
fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied to
each joint.
7 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm,
leaving a 10mm clearance for any duct expansion in a fire situation.
8 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild
steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at
high temperature allowing the duct to break away without aecting the integrity of the installation.
9 The connecting galvanised mild steel ductwork must be independently supported within one metre of
the connections and have been installed in accordance with DW144.
10 An access door should be fitted on the access side of the damper for inspection and maintenance.
11 When the damper installation is complete the operation of the damper should be checked.
12 Complete DW145 Fire Damper Certificate.
Preparation
1 Ensure the that damper is kept in a clean dry
environment and that there is no damage to the
damper.
2 Work out the opening size to be cut by adding
55mm to the duct diameter and cut a square hole to
that size, see adjacent table.
Nom. duct diameter Opening size
100mm 155 x 155mm
125mm 180 x 180mm
150mm 205 x 205mm
160mm 215 x 215mm
200mm 255 x 255mm
250mm 305 x 305mm
300mm 355 x 355mm
315mm 370 x 370mm

0400_IOM_1.1_Mar21_5
5
PRODUCT 0400MAN APPLICATION RIGID SUPPORTING CONSTRUCTION
CLASSIFICATION REPORT NO. P1054241003 CLASSIFICATION E120 VE I O
TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING.
FIRE 0400MAN CIRCULAR FIRE DAMPER IN RIGID SUPPORTING CONSTRUCTION
Fire batt
Access door
135mm minimum thickness
two hour rated rigid supporting
construction to BS EN 1363-1:2020
OPEN
CLOSE
Installation sequence
3 The damper should be mounted in the opening with the fixing flange (access side) flush with the wall.
4 Confirm that the blade is horizontal, and the handle is on the RH or LH. The flange can then be secured
to the wall using fire resistant steel fixings. Ensure that all the pre-drilled holes are populated.
5 The gap between the damper and the wall opening will need filling with two layers of 50mm thick
140kg/m3fire batt cut to interference fit and pushed into place. All cut edges must be sealed with a
fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied to
each joint.
6 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm,
leaving a 10mm clearance for any duct expansion in a fire situation.
7 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild
steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at
high temperature allowing the duct to break away without aecting the integrity of the installation.
8 The connecting galvanised mild steel ductwork must be independently supported within one metre of
the connections and have been installed in accordance with DW144.
9 An access door should be fitted on the access side of the damper for inspection and maintenance.
10 When the damper installation is complete the operation of the damper should be checked.
11 Complete DW145 Fire Damper Certificate.
Preparation
1 Ensure the that damper is kept in a clean dry
environment and that there is no damage to the
damper.
2 Work out the opening size to be cut by adding
55mm to the duct diameter and cut a square hole to
that size, see adjacent table.
Nom. duct diameter Opening size
100mm 155 x 155mm
125mm 180 x 180mm
150mm 205 x 205mm
160mm 215 x 215mm
200mm 255 x 255mm
250mm 305 x 305mm
300mm 355 x 355mm
315mm 370 x 370mm

0400_IOM_1.1_Mar21_6
6
PRODUCT 0400FME APPLICATION FLEXIBLE SUPPORTING CONSTRUCTION
CLASSIFICATION REPORT NO. TBA CLASSIFICATION E120 VE I O S
TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING.
FIRE & SMOKE 0400FME CIRCULAR DAMPER IN FLEXIBLE SUPPORTING CONSTRUCTION
Thermal probe
Access door
Fire batt
Two hour rated flexible supporting
construction to BS EN 1363-1:2020
15mm thick gypsum boards
Steel stud depth – 71 to 100mm
Installation sequence
3 The drywall will consist of two layers of 15mm plasterboard each side of steel studwork with an optional
50mm mineral wool insulation. The opening will be a letterbox construction with overlapping layers of
plasterboard.
4 The damper should be mounted in the opening with the fixing flange (access side) flush with the wall.
5 Confirm that the blade is horizontal, and the actuator is on the RH or LH. The flange can then be
secured to the wall using M3.5 x 38mm drywall screws which are to pierce the steel channel.
Ensure that all the pre-drilled holes are populated.
6 The gap between the damper and the wall opening will need filling with two layers of 50mm thick
140kg/m3fire batt cut to interference fit and pushed into place. All cut edges must be sealed with a
fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied to
each joint.
7 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm,
leaving a 10mm clearance for any duct expansion in a fire situation.
8 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild
steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at
high temperature allowing the duct to break away without aecting the integrity of the installation.
9 The thermal probe should be fitted in the connecting galvanised mild steel ductwork, up to 400mm
away from the wall. Drill a 11mm hole, insert the thermal probe and secure with two pro points. Template
and screws supplied.
10 The connecting galvanised mild steel ductwork must be independently supported within one metre of
the connections and have been installed in accordance with DW144.
11 An access door should be fitted on the access side of the damper for inspection and maintenance.
12 When the damper installation is complete the operation of the damper should be checked.
13 Complete DW145 Fire Damper Certificate.
Preparation
1 Ensure that the damper is kept in a clean dry
environment and that there is no damage to the
damper.
2 Work out the opening size to be cut by adding
55mm to the duct diameter and cut a square hole to
that size, see adjacent table.
Nom. duct diameter Opening size
100mm 155 x 155mm
125mm 180 x 180mm
150mm 205 x 205mm
160mm 215 x 215mm
200mm 255 x 255mm
250mm 305 x 305mm
300mm 355 x 355mm
315mm 370 x 370mm

0400_IOM_1.1_Mar21_7
7
PRODUCT 0400FME APPLICATION RIGID SUPPORTING CONSTRUCTION
CLASSIFICATION REPORT NO. TBA CLASSIFICATION E120 VE I O S
TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING.
FIRE & SMOKE 0400FME CIRCULAR DAMPER IN RIGID SUPPORTING CONSTRUCTION
Access door
Thermal probe
Fire batt
135mm minimum thickness
two hour rated rigid supporting
construction to BS EN 1363-1:2020
Installation sequence
3 The damper should be mounted in the opening with the fixing flange (access side) flush with the wall.
4 Confirm that the blade is horizontal, and the actuator is on the RH or LH. The flange can then be
secured to the wall using fire resistant steel fixings. Ensure that all the pre-drilled holes are populated.
5 The gap between the damper and the wall opening will need filling with two layers of 50mm thick
140kg/m3fire batt cut to interference fit and pushed into place. All cut edges must be sealed with a
fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied to
each joint.
6 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm,
leaving a 10mm clearance for any duct expansion in a fire situation.
7 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild
steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at
high temperature allowing the duct to break away without aecting the integrity of the installation.
8 The thermal probe should be fitted in the connecting galvanised mild steel ductwork, up to 400mm
away from the wall. Drill a 11mm hole, insert the thermal probe and secure with two pro points. Template
and screws supplied.
9 The connecting galvanised mild steel ductwork must be independently supported within one metre of
the connections and have been installed in accordance with DW144.
10 An access door should be fitted on the access side of the damper for inspection and maintenance.
11 When the damper installation is complete the operation of the damper should be checked.
12 Complete DW145 Fire Damper Certificate.
Preparation
1 Ensure that the damper is kept in a clean dry
environment and that there is no damage to the
damper.
2 Work out the opening size to be cut by adding
55mm to the duct diameter and cut a square hole to
that size, see adjacent table.
Nom. duct diameter Opening size
100mm 155 x 155mm
125mm 180 x 180mm
150mm 205 x 205mm
160mm 215 x 215mm
200mm 255 x 255mm
250mm 305 x 305mm
300mm 355 x 355mm
315mm 370 x 370mm

0400_IOM_1.1_Mar21_8
8
Initial operating check
The 0400MAN damper should only be commissioned once the installation has been completed.
The damper should be inspected thoroughly to ensure that it is clean and free of any internal debris before
the damper actuation is tested as per the following instructions;
• Remove the access door.
• To operate the damper the thermal fuse must be unscrewed, then turn the handle anticlockwise until
it is in the open position, as shown on the label.
• The damper blade is under tension from a spring so the handle must be held in position whilst the
thermal fuse is re-tightened, the blade will hold in the open position.
• To ensure the damper is operating correctly the damper should be tested by first checking that there
are no obstructions to the handle and that it is free to move. Then unscrew the thermal fuse quickly,
this will release the blade to its closed position.
• Check that the blade is in the closed position by checking that the handle is in line with the close
position on the label.
• If everything is satisfactory then reset the damper to its correct position, either fully open or if it is to
balance air then this can be done so long as the damper remains at least 50% open.
• Re-fit the access door.
• If the damper has not closed, the blade may have been incorrectly positioned, or the damper may be
faulty. Please contact Advanced Air for advice.
Maintenance
0400MAN dampers are installed as a life safety product and it is essential that they are always maintained in
good, clean working condition. In accordance with BS9999 Annex W.1 maintenance and inspection should
be undertaken annually.
Maintain the dampers as follows;
• Mark the handle position on the label so that it can be reset to the same position after testing.
• Remove the access door.
• Visually inspect all damper components for signs of corrosion, obstructions and build-up of dirt/dust.
• Remove any obstructions, wipe away all dirt/dust from the damper blades and duct surfaces.
• After internal inspections are complete a functional check of the damper should be made.
• Test the damper by unscrewing the thermal fuse quickly, check that the reaches its closed position.
• Reset the damper to its original position and re-tighten the fusible link.
• If there is a requirement to change the thermal fuse this can be done simply by unscrewing it fully from
the case and replacing with a new one. The thermal fuse should be replaced if it has been activated,
damaged or part of a regular service plan.
• Refit the access door and complete inspection reports as appropriate.
0400MAN OPERATION AND MAINTENANCE
The damper is fully closed
when the handle is rotated
to the ‘Close’ position.
Thermal fuse The damper is fully open
when the handle is rotated
to the ‘Open’ position.

0400_IOM_1.1_Mar21_9
9
Initial operating check
The 0400FME damper should only be commissioned once it is fully installed and connected to electrical
power. The damper should be inspected thoroughly to ensure that it is clean and free of any internal debris
before the damper actuation is tested as per the following instructions:
• Isolate the power.
• Remove the access door.
• Test the damper manually by using the Allen key provided and
turning it clockwise until the damper is fully opened, mechanically
lock the actuator by using a screwdriver to turn the STOP SHAFT 5.
• Visually inspect the damper checking that the damper is in its fully
opened position.
• Close the damper by turning the Allen key clockwise and releasing
it, the spring action of the actuator will wind the damper to its fully
closed position.
• Visually inspect the damper checking that the damper is in its fully
closed position.
• Reapply power to the actuator. The actuator will start to travel, and
a GREEN light will be lit on the Thermal Release housing, it will take
90 seconds to fully open.
• The switch on the Thermal Release housing can be pressed to
simulate activation of the thermal release, the LED light will turn
RED and the actuator will spring return to its unpowered position,
it should take 15 seconds to complete this cycle.
• Release the switch and the damper will return to its fully opened
position.
• Visually inspect through the access door that the blades are fully
open and then re-fit the access door.
• Damper not fully opening or closing?
• Obstruction to the blades – remove the obstruction.
• Incorrect set up of the actuator – the actuator has been adjusted by others from the Factory Set
position.
• For other faults contact Advanced Air Sales Oce.
• Complete any relevant reports.
Maintenance
0400FME dampers are installed as a life safety product and it is essential that they are always maintained
so they are in a clean working condition. In accordance with BS9999 Annex W.1 maintenance and inspection
should be undertaken annually.
Maintain the dampers as follows;
• Remove the access door to internally inspect the damper.
• Visually inspect all damper components for signs of corrosion, obstructions and build-up of dirt/dust.
• Remove any obstructions, wipe away all dirt and dust from the damper blades and duct surfaces.
• Check that the thermal release probe is intact and does not show signs of damage.
• After internal inspections are complete a functional check of the damper should be made.
• The 0400FME damper is fitted with an electrical thermal release probe and its housing has a LED light
and an On/O toggle switch.
• A GREEN light indicates that there is a power supply and that the thermo sensor is OK.
• A RED light indicates a power supply but there is a fault.
• No light indicates that there is no power supply.
• Push and hold the toggle switch to simulate over-temperature. This simulates the response of the
thermal release, enabling the proper functioning test of the actuator and damper. It will take 15 seconds
for the damper to close and during the test the LED light will turn RED.
• After checking that the blades on the damper are fully closed, release the switch and the actuator will
power to its open position and the light will turn GREEN, check the blades are in the open position.
• Refit the access door and complete maintenance reports as appropriate.
0400FME OPERATION AND MAINTENANCE
LED Light
RED
Operating voltage OK. Thermo sensor defect.
GREEN
Operating voltage OK. Thermo sensor OK.
DARK
No operating voltage.
STOP SHAFT
– turn 5º
Allen key slot
Switch

0400_IOM_1.1_Mar21_10
10
WIRING INSTRUCTIONS 0400FME
12345678
G:\PRODUCTS\DMP - 0400 Series\02 Drawings\D0400 - ES - Electrical Schematics\D0400 ES001 Wiring diagram fire smoke damper actuator\D0400 ES001 rev B Wiring diagram 0400 FME.dwg
Wiring detail for dampers fitted with spring return actuators AA230TS4 or AA24TS4.

0400_IOM_1.1_Mar21_11
11
Fire Damper Certificate
CE-020
CE Certification
Rev 01
June 2019
S Manning
DW 145 Inspection & Handover Check Sheet to be completed by the installer with a separate
certificate for each damper.
No.
Question
Guidelines
Tick
1 Are the dampers the correct type?
Fire Damper Model 0160, 0400MAN
Fire Damper Model 2550, 2530, 26SCD
and 0400FME
2 Are the dampers correctly identified?
Identification label clearly shows the
damper individual reference number
3 Are the dampers located correctly?
The damper position matches the
position as detailed on the
manufactures installation instructions
4
Have supports for both the damper and
the adjacent ductwork been installed in
accordance with the approved method?
5
Are the dampers fitted in the correct
orientations?
The dampers are installed the correct
way up relative to airflow and access
6 Is access, through the ductwork to the
damper unobstructed?
There is unobstructed space to allow
safe access to damper, also through
ceiling void and adjacent services
7
Confirm the space around the damper has
not been used for the passage of other
services
The presence of other services will
invalidate the installation method
8
Using the access opening provided,
confirm that the damper has been left in
the open position
9
Release the damper catch to simulate the
thermal release mechanism (damper drop
test)
Ensure the blade operation is free from
interference
10 Check damper blades for damage
With the damper in the closed position
inspect for damage
11 Re-set damper and replace access panel
After resetting check that if supplied
the visual position indicator is correct
12 Is the fire barrier and penetration seal
complete?
Confirm at handover if installation is
complete and if no then other trades
will be required to finish
13 Handover damper installation for
commissioning
Obtain relevant acceptance of the
damper installation from the
nominated person responsible
Project
Installer Name
Damper ID No:
Company
Location
Date
Type
I hereby confirm the damper detailed has been installed and
tested according to the manufactures recommendations
Model No:
Signature
This manual suits for next models
1
Table of contents
Other Advanced Air Fire And Smoke Damper manuals