Selection and Installation Manual 6
GB
Description of the unit
The rooftop units of the RTE range have
been designed taking into account the
precise needs of the plant engineering
sector, that deals with large structures for
the “large-scale retail trade“ (supermarkets
and hypermarkets), and areas dedicated to
exhibitions, trade fairs, and industrial use
in general.
These units, usually positioned on roof-
tops or anyway out of doors, offer the
following main advantages:
• their installation on the roof does not
reduce the effective space available;
• they offer the maximum modularity,
therefore allowing you to distinguish
the treatment in different volumes with
different usage characteristics (food sec-
tion, clothing department, etc.);
• they offer high levels of environmental
comfort, controlling not only the tem-
perature but also the exchange, filtering
and humidification or dehumidification
of the air;
• the environmental noise level is kept
down thanks to the careful soundproo-
fing of the machine.
Components
The RTE rooftop units are all available in
the cooling-only version (RTE F) or coo-
ling + heat pump (RTE H).
The RTE rooftop units are supplied com-
plete with:
• condensing unit with helicoidal fans and
scroll compressors;
• cooling circuit with thermostatic valves,
filters, liquid indicator lights;
• corrugated synthetic filter, class G4
(EN779);
• direct expansion coil with condensate
collection tank in aluminium alloy;
• centrifugal supply fan, with blades for-
wards or backwards blades depending
on the model and the pressure levels
required, with belt transmission and
variable pulley;
• adjustment by means of microproces-
sor;
• electric panel.
Sizes
The units of the RTE range are available
in 5 sizes (480-560-600-700-800), with
the possibility of standard, low noise L
or high temperature A operation (exclu-
ding sizes 200 and 255). With a suita-
ble combination of the numerous options
available, it is possible to configure each
model to satisfy the most demanding plant
requirements.
Available configurations
Note: the figures shown refer to the
dimensional diagrams on pages 23-26
Standard configuration: a single-block
rooftop unit with flat G4 filters (efficiency
level in compliance with EN779), evapo-
rator coil (optional hot water coil) (fig.1)
SMP: rooftop unit with 2-ways mixing
box, rear intake (1) (fig.2)
FT7: rooftop unit with flat G3 pre-filters
and F7 rigid bag filters (EN779) (fig.3)
SM2: rooftop unit with 2-ways mixing
box, side/lower intake (1) (fig.4)
SM3: rooftop unit with 3-ways mixing box
with actuators and free-cooling for the
temperature (fig.7)
REC: rooftop unit with plate heat recove-
ry unit (with recirculation damper) and
intake fan. The air/air heat recovery unit is
of the static plate type with cross flows. It
allows the recovery of sensitive heat from
the expelled air with an efficiency level
higher than 50% during winter operation.
The two air flows (expulsion and intake)
are completely separate, thereby avoiding
any form of contamination. Modulating
actuators included as standard (fig.13)
Gxxx: rooftop unit with condensing hot
air generator. The condensing hot air
generator is powered by natural gas. The
air is heated as it passes over the surfa-
ce of the combustion chamber and the
exchange pipes. The combustion chamber
is built entirely of AISI 430 stainless steel,
while the surfaces in contact with the
condensate (heat exchanger, flue gases
collection hood) are made of AISI 304 L
steel to be particularly resistant to corro-
sion. It is fitted with a safety thermostat
with automatic reset (fig.6).
The cooling circuit will be switched off
when the hot air generator is working.
It is not possible to combine the hot air
generator with the electric heating ele-
ment.
Configuration combina-
tions
SM2-FT7: rooftop unit with 2-ways mixing
box, side/lower intake and F7 bag filters
(1) (fig.5)
Gxx-SMP: rooftop unit with heat gene-
rator and 2-ways mixing box, rear intake
(fig.8) (1)
Gxxx-FT7: rooftop unit with heat genera-
tor and F7 bag filters (fig.9)
SM3-FT7: rooftop unit with 3-ways mixing
box and F7 bag filters (fig.10)
SM2-Gxxx:
rooftop unit with 2-ways mixing
box and hot air generator (fig.11) (1)
SM2-Gxxx-FT7: rooftop unit with 2-ways
mixing box, hot air generator and F7 bag
filters (fig.12) (1)
REC-FT7: rooftop unit with static heat
recovery unit and F7 bag filters (fig.14)
SM3-Gxxx: rooftop unit with 3-ways
mixing box and hot air generator (fig.15)
SM3-Gxxx-FT7: rooftop unit with 3-ways
mixing box, hot air generator and F7 bag
filters (fig.16)
REC-Gxxx: rooftop unit with static heat
recovery unit and hot air generator
(fig.17)
REC-Gxxx-FT7: rooftop unit with sec-
tion with static heat recovery unit, hot air
generator and F7 bag filters (fig.18)
NOTE:
(1) dampers without actuators and recir-
culation damper upon request
RTE size Heating capacity
Gxxx [kW]
480/530/600 150 / 200
700/800 150 / 200 / 150+92