Afriso EURO-INDEX 43790 User manual

Mess-, Regel- und
Überwachungsgeräte
für Haustechnik,
Industrie und Umweltschutz
Lindenstraße 20
74363 Güglingen
Telefon +49 7135-102-0
Service +49 7135-102-211
Telefax +49 7135-102-147
www.afriso.de
Read instructions before using device!
Observe all safety information!
Keep instructions for future use!
01.2011 0
854.001.0512
Operating Instructions
Leak Detector Pressure Type
Europress
Europress # 43790
... in protective housing # 43795
... in protective housing
with heating # 43796
Leckanzeiger
Z-65.23-3

2 Europress
Contents
1This instruction manual............................................................................................4
1.1 Precautions ..................................................................................................4
1.2 Explanation of symbols and typeface ..........................................................4
2Safety ......................................................................................................................5
2.1 Intended use ................................................................................................5
2.2 Predictable incorrect application ..................................................................6
2.3 Safe handling ...............................................................................................6
2.4 Staff qualification..........................................................................................6
2.5 Modifications to the product .........................................................................7
2.6 Usage of spare parts and accessories.........................................................7
2.7 Liability information ......................................................................................7
3Product description..................................................................................................8
3.1 Function........................................................................................................9
3.2 Operating modes..........................................................................................9
3.3 Application examples .................................................................................10
4Technical specifications.........................................................................................11
4.1 Approvals, tests and conformities ..............................................................12
5Transport and storage ...........................................................................................13
6Mounting and commissioning................................................................................13
6.1 Safety information on mounting .................................................................13
6.2 Installation site ...........................................................................................13
6.3 Installing the leak detector .........................................................................14
6.4 Electrical connection ..................................................................................15
6.5 Connection line ..........................................................................................17
6.6 Drying filter .................................................................................................21
6.7 Valve settings .............................................................................................22
6.8 Commissioning the device .........................................................................23
7Operation...............................................................................................................23
7.1 Alarm condition ..........................................................................................23
7.2 Function test...............................................................................................24
8Maintenance ..........................................................................................................27
8.1 Service indication .......................................................................................27
8.2 Maintenance activities................................................................................28
9Troubleshooting.....................................................................................................29
9.1 Evaluation of the pump operating time ......................................................30
10 Shutting down, disposal ........................................................................................31
11 Spare parts and accessories.................................................................................31

Europress 3
12 Warranty ................................................................................................................32
13 Copyright ...............................................................................................................32
14 Customer satisfaction ............................................................................................32
15 Addresses..............................................................................................................32
16 Appendix................................................................................................................33
16.1 Certificate of expert ....................................................................................33
16.2 Approval documents...................................................................................34

This instruction manual
4 Europress
1 This instruction manual
This instruction manual is part of the product.
Read this manual before using the product.
Keep this manual during the entire service life of the product
and always have it readily available for reference.
Always hand this manual over to future owners or users of the
product.
1.1 Precautions
WARNING TERM
Type and source of the danger are shown here.
Precautions to take in order to avoid the danger are shown
here.
There are three different levels of warnings:
Warning Term Meaning
DANGER Immediately imminent danger!
Failure to observe the information will result in
death or severe injuries.
WARNING Possibly imminent danger!
Failure to observe the information may result in
death or severe injuries.
CAUTION Dangerous situation!
Failure to observe the information may result in
minor or severe injuries as well as damage to
property.
1.2 Explanation of symbols and typeface
Symbol Meaning
Prerequisite for an activity
Activity consisting of a single step
1. Activity consisting of a several steps
Result of an activity
• Bulleted list
Text Indication on display
Highlighting Highlighting

Safety
Europress 5
2 Safety
2.1 Intended use
The Europress leak detector for pressurised systems is a class 1
leak detector according to EN 13160-1.
The Europress leak detector may only be used to detect leaks in the
tanks listed below which are not pressurised (i.e. operated under at-
mospheric conditions) and which are used for aboveground or un-
derground storage of the liquids described below.
Tanks
• Double-walled steel or plastic tanks with approval of use of the
German Institute for Building Technology (Deutschen Institut für
Bautechnik) and which are suitable for water-polluting liquids.
The interstitial spaces of the tanks must be resistant to the liquid and
its vapours and must not contain leak detection fluid.
A leak detector may be connected to a single aboveground tank or
to several underground tanks with a total interstitial space volume of
4 m³.
Liquids
• Steel tanks: Water-polluting liquids
• Plastic tanks: Water-polluting liquids with a flash point of more
than 55 °C
• AdBlue® (urea solution 32.5 %) according to DIN 70070
The leak detector must be resistant to the liquid and its vapours. The
materials used are: PVC, silicone, ABS, NBR, PA6, EPP, EPDM.
The permissible density of the liquid depends on the tank height / the
tank diameter.
Tank height/tank Ø Permissible density
≤2.00 m ≤1900 kg/m³
≤2.50 m ≤1740 kg/m³
≤2.60 m ≤1670 kg/m³
≤2.76 m ≤1580 kg/m³
≤2.84 m ≤1530 kg/m³
≤2.90 m ≤1500 kg/m³
Any use other than the application explicitly permitted in this instruc-
tion manual is not permitted.

Safety
6 Europress
2.2 Predictable incorrect application
The Europress leak detector must never be used in the following
cases:
• Hazardous area (Ex)
If the device is operated in hazardous areas, sparks may cause
deflagrations, fires or explosions.
• Mounting in access chambers of underground tanks
• Use with aggressive liquids which attack the connection hoses
and the leak detector.
2.3 Safe handling
This product represents state-of-the-art technology and is made ac-
cording to the pertinent safety regulations. Each device is subjected
to a function and safety test prior to shipping.
Operate the product only when it is in perfect condition. Always
observe the operating instructions, all pertinent local and na-
tional directives and guidelines as well as the applicable safety
regulations and directives concerning the prevention of acci-
dents.
WARNING
Severe burns or death caused by mains voltage in the control
unit.
Do not expose the leak detector to water.
Interrupt the mains voltage supply before opening the leak de-
tector or before performing maintenance and cleaning work and
make sure it cannot be switched on by accident.
Do not tamper with the leak detector in any way whatsoever.
2.4 Staff qualification
Mounting, commissioning, maintenance and cleaning may only be
performed by specialised companies as per § 3 of the German Ordi-
nance on Installations for Handling Water-Polluting Substances
(VAwS of March 31, 2010) unless such activities do not have to be
performed by specialised companies according to the applicable lo-
cal directives or unless the manufacturer of the device has such ac-
tivities performed by his own, trained staff.
Electrical work may only be performed by trained electricians and in
compliance with all applicable local and national directives.

Safety
Europress 7
2.5 Modifications to the product
Changes or modifications made to the product by unauthorised per-
sons may lead to malfunctions and are prohibited for safety reasons.
2.6 Usage of spare parts and accessories
Usage of unsuitable spare parts and accessories may cause dam-
age to the product.
Use only genuine spare parts and accessories of the manufac-
turer (refer to chapter 11, page 31).
2.7 Liability information
The manufacturer shall not be liable in any form whatsoever for di-
rect or consequential damage resulting from failure to observe the
technical instructions, guidelines and recommendations.
The manufacturer or the sales company shall not be liable for costs
or damages incurred by the user or by third parties in the usage or
application of this device, in particular in case of improper use of the
device, misuse or malfunction of the connection, malfunction of the
device or of connected devices. The manufacturer or the sales com-
pany shall not be liable for damage whatsoever resulting from any
use other than the use explicitly permitted in this instruction manual.
The manufacturer shall not be liable for misprints.

Product description
8 Europress
3 Product description
1 Rubber grommet
2 Green LED “Supply
ON”
3 Button “Test”
4 Red LED “Alarm”
5 Button “Mute”
6 Yellow LED “Service”
7 Button “Set”
8 Measurement valve
9 Measurement line
connection
10 Pressure gauge con-
nection
11 Cover for hose con-
nections
12 Suction line connection
13 Test valve
14 Pressure line connec-
tion
15 Condensate trap with
filter
16 Cable gland
Fig. 1: Exterior view and dimensions
The leak detector Europress generates a constant overpressure in
the interstitial space of the tank and triggers an alarm in the case of a
pressure drop.
Europress contains the following elements in an impact-resistant
plastic housing: display elements and controls, a pressure pump, a
pressure switch, a safety valve, a printed circuit board with the elec-
tronic components for processing the output signal, a filter and three
hose connections for the pneumatic connection to the interstitial
space of the tank.
The green LED “Supply ON” lights up when mains voltage is avail-
able. The alarm is indicated visually and audibly and is made avail-
able via a voltage-free relay contact (1 changeover contact).

Product description
Europress 9
Drying filters (not included) are used to dry the air compressed for
the operating pressure to a residual humidity level of approx. 10 %
and a filter is used to remove the dust particles. The dried and fil-
tered air is pumped into the interstitial space of the tank. Pressure
fluctuations in the interstitial space are compensated for by the pump
and the safety valve.
3.1 Function
The green LED “Supply ON” lights up when mains voltage is avail-
able and the device is ready for operation.. The pump integrated into
the leak detector draws in air via the drying filter and pumps it via the
pressure line to the tank's interstitial space until a constant overpres-
sure has been built up.
The pressure switch measures the pressure in the interstitial space
via the measurement line and keeps it at a constant level together
with the pump. The safety valve at the pump opens if the pressure is
too high in order to prevent the interstitial space test pressure (0.6
bar) from being reached.
If a leak occurs in the tank's inner or outer wall either above or below
the level of the stored liquid or the ground water, and if this leak is
greater than the pump's pumping capacity, the overpressure will
drop. When the alarm threshold is reached, the red LED “Alarm” and
the audible alarm are activated and the relay is energised.
The audible alarm can be muted with the button “Mute”. The switch-
ing point for "Alarm on" is at least 30 mbar higher than the static
pressure of the stored liquid or the ground water.
3.2 Operating modes
Europress is equipped with an output relay to transmit the alarm sig-
nal to additional external devices. If no error condition is present, the
relay is de-energised. In the case of an alarm, the relay is energised.
Europress can be operated with or without additional external de-
vices. The following types of additional devices can be used: visual
and audible alarm units, telecommunication devices, building control
systems, building automation systems, etc.

Product description
10 Europress
3.3 Application examples
1 Red: Measurement
line
2 Drying filter
3 Transparent: Pres-
sure line
4 Green: Suction line
5 Electrical connection
6 Outer wall
7 Interstitial space
8 Inner wall
Fig. 2: Application example
1 Europress
2 AFRISO event
reporting system
3 Internet
4 E-mail
5 Cell phone
6 Fax
7 Phone
Fig. 3: AFRISO event reporting system for remote reporting of leaks

Technical specifications
Europress 11
Fig. 4: Europress in protective housing,
without (A) or with heating (B),
pre-assembled and ready to be connected. The horn is connected to
the output relay. Protection IP 55.
1 Horn HPW 2 5 Red: Measurement line
2 Mute button for horn HPW 2 6 Green: Exhaust line
3 Europress 7 Transparent: Suction line
4 Protective housing 8 Heating controller
9 Heating
4 Technical specifications
Table 1: Technical specifications
Parameter Value
General specifications
Weight 1.2 kg
Emissions The A-evaluated sound level of the
audible alarm is at least 70 dB(A) at a
distance of one metre.
Output relay 1 changeover contact
Breaking capacity output
relay
max. 250 V, 2A, resistive load

Technical specifications
12 Europress
Parameter Value
Relay fuse T 2 A
Operating pressure in
interstitial space
Approx. 530 mbar
Switch point Alarm On 465 to 485 mbar
Switch point Alarm Off 510 mbar (point of reference, results
from switching hysteresis)
Switch point Pump On 500 mbar (point of reference, results
from switching hysteresis)
Switch point Pump Off 520 to 540 mbar
Safety valve opens ≥570 mbar
Connecting hose PVC hose 6 x 2 mm
Length of connection lines Max. 50 m
Temperature range
Ambient -5 °C to +50 °C
Storage -10 °C to +60 °C
Voltage supply
Nominal voltage AC 100-240 V ± 10 %
Rated power < 10 VA
Electrical safety
Degree of protection II
Protection IP 30
Mode of operation and
additional mode of opera-
tion
Type 1.B
Electromagnetic compatibility (EMC)
Interference According to CISPR 22
Noise immunity According to EN 61000
4.1 Approvals, tests and conformities
Europress HV complies with the EMC Directive (2004/108/EC), the
Low Voltage Directive (2006/95/EC), the Construction Products Di-

Transport and storage
Europress 13
rective (89/106/EEC) and has the Technical Approval of the German
Institute for Building Technology Z-65.23-3.
5 Transport and storage
CAUTION
Damage to the device due to improper transport.
Do not throw or drop the device.
Protect from wetness, humidity, dirt and dust.
CAUTION
Damage to the device due to improper storage.
Protect the device from shock when storing it.
Protect from wetness, humidity, dirt and dust.
Only store the device within the permissible temperature range.
6 Mounting and commissioning
The leak detector may only be installed and commissioned by a spe-
cialised company, see chapter 2.4, page 6.
6.1 Safety information on mounting
In the case of underground tanks, the hydrostatic pressure of the
ground water acting on the tank bottom must not exceed 435 mbar.
The hydrostatic pressure of the stored liquid including any overlay
pressure must not exceed 435 mbar.
Install the leak detector in such a way that it cannot cool down
to temperatures of –5 °C, e.g. Mount the leak detector in a pro-
tective housing with a heating. See chapter 11, page 31 for ac-
cessories.
6.2 Installation site
Choose an installation site that is as close as possible to the
tank to be monitored. The ambient temperature specified must
not be exceeded.
Mount the leak detector to an even, rigid and dry wall at eye
level.
The leak detector must be accessible and easy to oversee at all
times.
The leak detector must not be exposed to water or splash water.
Do not mount the leak detector in damp rooms.

Mounting and commissioning
14 Europress
The leak detector must not be installed in hazardous areas or in
access chambers of underground tanks.
If the case of outdoor applications, the leak detector must be
mounted in a protective housing with IP 55 protection. If the leak
detector is installed in a protective housing, an additional
weather-proof audible alarm must be installed outside of the
protective housing. See chapter 11, page 31 for accessories.
If the leak detector is installed below rooftops or in rooms that
are only partially closed, protect it against direct atmospheric in-
fluences or use a protective housing as mentioned above.
6.3 Installing the leak detector
1. Fasten the leak detector the wall (use Aor B),
a drilling template is included.
2. Open the leak detector.
3. Connect the unit electrically as described in chapter 6.4 on
page 15.

Mounting and commissioning
Europress 15
4. Close the leak detector.
6.4 Electrical connection
Mains voltage is interrupted and cannot be switched on by acci-
dent.
1 Pressure switch
2 Pump
3 Cable routed through
upper cable gland
4 Cable routed through
bottom cable gland
5 Relay fuse
6 Relay connection
7 Mains connection
Fig. 5: Electrical connection
Connect the leak detector directly to the supply network without
a switch and without a plug!
If you want to route the mains or relay cable trough the top of
the housing, replace the rubber grommet at the top of the hous-
ing by the enclosed cable gland.
Close any cable glands at the bottom of the housing that are not
used by means of the enclosed plugs.

Mounting and commissioning
16 Europress
Power supply
Connect the leak detector to mains by means of a permanently in-
stalled cable such as NYM-J 2 x 1.5 mm².
1. Route the mains cable through the upper or bottom cable gland
into the leak detector.
2. The phase must be connected to terminal L1, the neutral con-
ductor to terminal N. The leak detector supply cable must have
a separate fuse (max. 16 A). Do not connect it to the circuit of
other electrical devices.
Output
The output signal of the leak detector is made available via a volt-
age-free relay contact (1 changeover contact).
Permanently install the relay cable, route it through the upper or
bottom cable gland into the leak detector and connect it to the
terminals with the corresponding designations.
Safely isolate the relay cable. The isolation characteristics of the
relay cable must at least comply with IEC 60227 or IEC 60245.
If no error condition is present, the relay is de-energised. In the case
of an alarm, the relay is energised.
CAUTION
Destruction of the switching contact and adverse effects on the
function of electrical systems due to voltage peaks when induc-
tive consumers are switched off.
Use commercially available standard RC combinations such as
0.1 µF/100 Ohm for inductive consumers.

Mounting and commissioning
Europress 17
9 V battery for alarm in the case of power failure
If a standard 9 V battery is connected, an alarm sound is activated in
the case of a power failure. The alarm sound cannot be muted; it re-
mains on until mains power is available again. When mains power is
available again, the device immediately resumes operation. If a leak
has occurred in the meantime, this is indicated.
6.5 Connection line
Hoses from the leak detector to the tank to be monitored, see also
fig. 6 and fig. 7, page 19.
1. Use pressure-proof (at least PN10 for tanks containing inflam-
mable liquids), oil- and water-resistant plastic hoses 6 x 2 mm
for the measurement hose (red), the suction hose (green) and
the pressure hose (transparent. The hoses must be resistant to
the stored liquid and its vapours.
2. Protect the plastic hoses by means of rigid, weather-proof pro-
tective pipes. According to the German TRbF 20 No. 4.1.4 sec-
tion 8, the protective pipes must be resistant to the permeation
of inflammable liquids and their vapours.
3. The connection lines must have the full cross section over the
entire length, there must be no bends and indentations.
4. Do not fit any shut-off elements.
5. Hose connections must be secured by means of hose clamps
which fit over the entire circumference.
Under the following conditions, you may also use quick-action cou-
plings (shutting off at one end, nominal diameter 7.2, Rectu Base

Mounting and commissioning
18 Europress
type 26) at the tank side of the pressure line and the measurement
line of the interstitial space:
• The coupling part with the shut-off element is directly and per-
manently mounted to the tank.
• The connection piece for the pressure line and the measure-
ment line is secured by means of one hose clamp for each
hose.
• The pressure line and measurement line must be mounted and
connected in such a way as to prevent twisting.
Quick-action couplings enable factory-filling of the interstitial space
with dried air which considerably reduces the time required on site
for commissioning. The following must ensured:
• There is only dried air (or nitrogen) in the interstitial space.
• The coupling part at the tank end must not get dirty during
mounting in order to prevent damage to the seal.
6. Slide the cover over the connections to protect hose connec-
tions.

Mounting and commissioning
Europress 19
1 Measurement line, red
hose
2 Suction line, green
hose
3 Pressure line, white or
transparent hose
4 Drying filter
5 Interstitial space
Fig. 6: Connecting an aboveground tank
1 Measurement
line, red hose
2 Pressure line,
white or
transparent
hose
3 Distributors
Fig. 7: Connecting several underground tanks

Mounting and commissioning
20 Europress
Leak test
1. Check the connection lines for leaks prior to connection to the
interstitial space. To do so, perform a leak test with 600 mbar.
CAUTION
Damage to or destruction of the measurement system if the test
pressure at the connected Europress exceeds 600 mbar.
Make sure the test pressure does not exceed 600 mbar.
The connection lines can be considered to be tight if the pres-
sure drop within a period of 30 minutes is less than 20 mbar.
2. Connect the connection lines to the interstitial space of the tank
after a successful leak test.
Basic filling
The pump of the leak detector must not exceed the pump capacity of
100 l/h.
1. Fill the interstitial space to obtain a pressure of approx. 500
mbar. Use an installation pump with a greater capacity for this
purpose.
2. The intake air must be dried by means of a sufficiently large dry-
ing filter.
3. Once a pressure of 500 mbar has been built up, disconnect the
installation pump and connect the leak detector.
This manual suits for next models
2
Table of contents
Other Afriso EURO-INDEX Security Sensor manuals
Popular Security Sensor manuals by other brands

U-Prox
U-Prox Smoke quick start guide

Bosch
Bosch DS820 Manual and installation

Theben
Theben theRonda P360-100 WH GST quick start guide

Elk Products
Elk Products ELK-SWB28 installation manual

PCB Piezotronics
PCB Piezotronics ICP RHM240A01 Installation and operating manual

Digital Watchdog
Digital Watchdog SiteWatch DW-DTMWIPW user manual

PCB Piezotronics
PCB Piezotronics 138A25 Installation and operating manual

B.E.G.
B.E.G. LUXOMAT PD1-M-DIM Installation and operating instruction

Levenhuk
Levenhuk ERMENRICH PING SA20 user manual

Silverline
Silverline 140878 manual

LAHTI PRO
LAHTI PRO L2011300 user manual

Starport
Starport Cellphone Detector Plus 610 user manual