Agrowtek GrowControl GC-Pro User manual

GrowControlTM GC-Pro
Cultivation Control System
Installation &
User Operation Manual
REV02-13
WARNING
Read these requirements, installation and operating instructions very carefully.
Failure to follow the instructions could result in a controller malfunction.
A malfunction could result in serious equipment damage, property damage, bodily injury or death.
Install in accordance with the installation manual (provided separately.)

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com
1
Table of Contents
Getting Started
GC-Pro Platform 2
Overview, Applications & Terminology 3
AgrowTouchTM Touch Screen 4
Setting up the Software 5
Connecting Software to Controller 6
Basic Controller Operation
Run/StopMode 8
Inputs & Outputs, Manual Operation 9
Output Settings 10
InputSettings 10
Controls Functions
Overview 11
Day & Night Modes 12
Lighting Timers, 24-Hour on/off 13
Light Flip Box Control 13
Temperature Controls 15
Humidity Controls 18
Carbon Dioxide
CO
2 Injection 20
CO
2 Ventilation 21
Timers
Overview 23
24-Hour Timers 24
24-Hour Cancel Timers 25
CycleTimers 26
24-Hour Cycle Timers 27
Off-Delay Timers 28
Re-Start Delay Timers 29
VSC Vent, Shade & Curtain Controls
VSC Settings 30
VSC Manual Operation 31
Nutrient Dosing
General 33
Batch Dosing 33
Demand Dosing 35
DosingPumpSettings 36
Advanced Settings 37
Nutrient Scheduler 38
pH Dosing
Settings 39
Dead-band/Reverse-band 40
Alarms
AlarmSettings 41
Additional Software Alarms 41
Email / Text Alerts 42
System Settings
General 43
SystemUnits 43
SystemTimers 44
Zones, Multi-Zone Mode 45
System and User Passwords
Setting the Passwords 46
Logging into the Controller 47
Log-InHistory 48
RemoteLock-out 48
SystemName 49
Time&Date 49
Sensor Calibration
General 50
Temperature/Humidity Calibration 51
pH Calibration 52
Conductivity Calibration 53
Light Irradiance Calibration 54
Software Features
Sensor Display Groups 54
Monitoring & Graphing 55
DataLogging 56
Cameras 57
Controller Settings File Up/Download
Download from Controller 58
Uploading to Controller 59
Connecting to Multiple Controllers
Saving Program Settings Files 61
Multiple Connections 62
Network Settings
Controller IP Address 63
Port Forwarding 64
Dynamic DNS Forwarding 64
Software Updates 65

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com 2
GrowControlTM GC-Pro Platform
GrowControlTM GC-Pro is a modular control system designed to be fully customizable to nearly any growing
control requirements. The core of the system is the GC-Pro controller itself where all of the settings are
stored and control operations take place. The GC-Pro obtains information about the environment from
climate sensors, hydroponics sensors, switch sensors and more. The controller uses this information and,
based on the settings you enter into the controls functions, turns equipment on or off via the controller’s
“outputs.” The controller and its outputs are low-voltage wet contacts (24Vdc) designed to be connected to
Agrowtek’s RX/CX relays to switch AC mains power to equipment. Outputs can also be wired to custom
contactor panels with 24Vdc pilot relays to switch equipment power.
Included 24Vdc power
supply operates controller,
sensors and relays.
~AC Mains Power
Auxiliary 24Vdc power supply
can be added if included
power supply is not sufficient
for all peripherals.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com
3
Overview
The GC-Pro cultivation controller is an advanced micro-processor based controller utilizing precision
electronic climate sensors to offer intricate control of your environment. GrowControlTM is equipped with a
broad array of flexible features, modes and options to suit nearly any climate controlled environment.
Settings can be entered easily on the controller screen or with the GrowControlTM PC software.
The GC-Pro is capable of monitoring and controlling up to two different environments (zones) from one
control unit.
Most controls settings have separate day and night set points which allow you to operate equipment
differently during these respective periods to obtain optimal crop response.
The PC software can be used to completely control and monitor the controller locally or from afar. Data can be
logged indefinitely to standard .csv files and live charting displays historical graphical data for up to two days.
Typical Applications
GrowControlTM controllers are designed for the discerning horticulturalist and can be tailored to any use from
hobby applications to mid and large-sized commercial environments.
GrowControlTM contains many features for use in both greenhouses with sun-light as well as indoor
environments that do not have the benefit of natural sun light.
Terminology
GrowControlTM takes information from its sensors and clock, and compares the readings with the settings
entered by the operator. The controller then decides whether to turn equipment (outputs) on or off.
Analog sensors are those that have a variable value such
as temperature, humidity, etc.
Digital Input sensors are those that act like a switch and
are either on or off such as a float switch.
Controls Functions are the functions built into the
controller such as timers, thermostats, humiditats, CO2
injection, nutrient dosing, etc.
Outputs are what equipment is connected to on the
controller such as lights, fans, pumps, etc.
Zones are separate environments that are independently monitored and controlled with sensors in each zone.
FlexnologyTM
Multiple controls functions can be assigned to a single output for maximum control flexibility.
For example: a ventilation fan can be controlled by a cooling thermostat and a de-humidify humidistat at the
same time. A timer could also be setup on the same fan output during the night, for example, to bring in fresh
air on a time schedule.
Sensor Inputs
(temp, humidity, etc.)
Control Functions
(thermostats, timers, etc.)
Outputs
(fans, heaters, etc.)
Cooling Thermostat
Output
#
(ventilation fan, etc.)
De-Humidify Stat
Cycle Timer

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com 4
AgrowTouchTM Touch Screen
Home Screen
The home screen displays the
sensor readings, time and date,
controller run status, and several
menu buttons.
If the controller is in multi-zone
mode, the bottom right corner will
display a button to toggle between
zone displays.
Screen Saver
The touch screen has a built-in screen
saver which turns off the back light after 30
minutes. To re-activate the screen, simply
touch any where on the screen.
Key Pads
Indoor climate sensor display. Hydroponics sensor display.
Outdoor weather sensor display.
Time & Date
Press here to activate
screen saver
Reading Heading
Press here to view
graphing history
Sensor reading value
Change display to
next zone
Controller Run
Mode status and
start/stop menu
Inputs & Outputs
Status / controls
Main Menu
Change display between
climate, hydro, weather and
other sensor displays.
Graphical meter display
Decimal Values
There is no decimal point key on the touch screen. For fields that have
a decimal place, enter the number as follows:
72.5 would be entered as: 7 2 5 Enter
75.0 would be entered as:
7 5 0 Enter
Acceptable
range
Current
Setting
Numeric Keypad Alpha-numeric Keypad
Press the ‘CAP’ key to change
between upper and lower case, and
to display special characters.
Space
When entering a name, an alpha-numeric
key-pad will be displayed.
Enter
Cancel
Clear
Delete /
Backspace
When entering a number, a numeric key-pad will
be displayed.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com
5
Setting up the Software
The controller can be ordered with or without a touch-screen interface. The PC software can connect to the controller whether
there is a touch screen or not and can take the place of a touch screen if the controller will never be accessed locally or to
save cost and use a PC as the sole interface.
Communication Connection
GrowControlTM can be linked to a PC for complete remote control, monitoring, setup and data logging.
The GC-Pro is equipped standard with a RS-232 serial port for local connection to a PC via the PC’s serial port (or a USB port
with USB converter.) Optionally, the GC-Pro can be equipped with an Ethernet port for connection to your local area network.
When connected to a LAN, the controller can be accessed via IP address locally or remotely via the internet (with proper port
forwarding; see Port Forwarding.)
Simultaneous Connections
When equipped with an Ethernet port, the controller may be accessed simultaneously by multiple PC’s locally or remotely. The
controller can also connect via its serial port and Ethernet port simultaneously.
Notes:
1. Serial communication cables can be extended up to 50ft with a male-female extension cable available from Agrowtek.
2. A USB-to-Serial converter is available from Agrowtek to connect the controller’s serial port to a USB port on your PC.
3. A “Wireless Bridge” (or a router in bridge mode) can be used to connect the Ethernet port to a wireless router.
Minimum PC Requirements
Windows® XP, Vista, 7, 8 (32 or 64 bit)
Microsoft .Net 4.0 Client Run Time Environment (installer provides download link from Microsoft if not installed)
RS-232 DB-9 Serial Com Port, or USB port (with USB-Serial converter)
1 GHz processor
1 GB Ram
6Mb HDD space for program
Additional HDD space for data logging files or camera images
Installing the Software
Download the installer file from the Agrowtek website:
Http://www.agrowtek.com/download/GrowControlSetup.msi
Open the installer and follow the prompts to install the
program.
Running the Software
A short-cut to the program should automatically be placed on your desktop and in your start-menu.
Double-click the desktop icon or navigate to “Agrowtek > GrowControl(TM)” in the start-menu to open the
program.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com 6
Connecting to the controller
1. Press the “Monitor” button OR from the top menu, select “Connection -> Connect…”
2. The connection dialog appears; select a COM port, or enter the controller’s IP or Remote address.
TCP Port: If using port forwarding on a port other than the controller’s standard port 502, enter it in the TCP port text
box.
3. Press the “Connect” button in the box with the connection you want to use.
1
1
Disconnected
Com Port
for Serial
connection
Connect to
Com Port
Connect to
Ethernet via
Internet
Connect to
Ethernet via
local network
Connect to
Ethernet Port
Change Ethernet
IP Settings

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com
7
4. If the controller has an operator password set, you will be prompted to enter your operator (or system) password.
5. The software will perform an initial read of the settings in the controller.
6. If you connected via the “Connection” menu, you will be asked if you want to start monitoring; press yes to begin
monitoring the controller or press no to remain connected but not monitoring.
7. The connection indicator in the lower right corner will change to show the connection status.
8. If monitoring, the sensor readings, I/O status and control functions status will be updated.
Disconnected Connected to
Serial Port Connected to
Ethernet Port
(Local Network)
Connected to
Ethernet Port
(Remote Address)
Enter 4-digit pin
password to
connect.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | agrowtek@agrowtek.com 8
Run / Stop
The controller will automatically turn the equipment outputs on and off depending on how they are programmed to operate
when the system is in “Run” mode. All of the outputs can be stopped simultaneously by placing the controller into “Stop”
mode. Placing the controller back into “Run” mode by pressing Start will allow the outputs to operate as the controller
requires.
Touch Panel
From the Home screen press the Status button to access the run mode menu. When the controller is stopped, “System OFF”
will be displayed in red. When the controller is running, “System ON” will be flashing in green.
Software
The controller can be started or stopped from the PC software by pressing the “Run/Stop” button in the lower left corner when
connected to the controller.
1.The home screen; press “Stopped”
button to enter run mode screen. 2. Press “Run” to place the system into
‘run’ mode or “Stop” to stop the
controller. Press “Back” to return to the
previous screen.
Day/Night/Off
mode display
NOTE
Before any outputs will activate, the system must be placed into “Run” mode.
When the system is in “Run” mode, the outputs can be turned on. When in “Stop” mode, all outputs will be disabled.
3. The home screen will show green for
run and the current zone’s day or night
mode.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected]
9
Inputs & Outputs (I/O)
Outputs
The controller turns equipment on and off by controlling outputs. Each control function (thermostats, timers, etc.) is
programmed to one of the available outputs as desired.
The controller comes with twelve (12) programmable outputs (GC-Pro-xD is equipped with 20 outputs.) The user names each
output for reference then assigns control functions to the outputs as required.
Note: “Output Sequence Delay Timer” may delay the activation of any output by the delay time. This prevents multiple
outputs from activating simultaneously thereby reducing electrical load spikes.
Inputs
Four (4) “Digital” inputs are available to connect switch type sensors (float switches, door switches, leak sensors, smoke
detectors, etc.) Digital inputs can be programmed to act in a variety of different ways including turning an output device on or
off when the input it tripped.
Touch Panel
The I/O controls menu displays the current status of all the digital inputs and outputs. An input or output will be green when
activated, and red when inactive. Touching any of the input or output numbers will display the settings for that input or
output.
Software
The PC software contains the I/O controls on the ‘IO’ tab. If an input or output is activated, it will be shown in green.
Click an input or output button to start, stop or set to automatic mode, change the name or set the interlock/interrupt
output#.
Status button indicates run or stopped,
and day or night (if in run mode.) Inputs and outputs that are on are
shown in green; off are shown in red.
Pressing an input or output number
displays the control functions for the
input or output.
Output can be named for reference,
manually operated or disabled, and be
programmed to disable another output
when on (advanced settings.)
Inputs
Outputs

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected] 10
Output Settings
Outputs are devices that the controller turn on or off as required (such as lights, fans, pumps, etc.) Each output has its
operation designated by the controls functions, (described later) but the output can be manually operated or disabled, and can
utilize an ‘interrupt’ function.
Output Interrupts
The interrupt function causes a selected output number to be disabled any time the parent output is activated. This function
is most typically used to prevent CO2 outputs from activating when ventilation stages are active.
Interrupt Example: If the output shown above (output #1) is assigned to ventilation fans, and output #2 is assigned to CO2,
enter “2” in the interrupt value of output 1. (Also see temperature limit functions to cancel CO2 in anticipation of ventilation or
to prevent combustion generators from operating above a set limit temperature.)
Input Settings
Digital Inputs are those that act like switches (float switches, leak sensors, motion sensors, smoke detectors, etc.)
Digital inputs can be assigned to perform specific tasks when activated such as activate or disable an output.
Manual over-ride or
automatic control.
Output status; green when on, red when off.
Output name Modify output name
Output # to cancel when
the output (#1) is on.
Show advanced Show manual over-
ride controls.
Manual over-ride
or automatic
control.
Input status; green when on, red when off.
Input
name Modify input name
Output # to take
action on when
input is true (on.)
Show advanced settings. Show manual over-
ride controls.
Select action to take
when this in
p
ut is true.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected]
11
Controls Functions
“Controls” are functions such as thermostats, timers, etc. that the controller uses to operate the “outputs” (greenhouse
equipment.) The grower decides which of the controls functions the controller will use to control the equipment in the
environment(s.)
Any control function that is used must be assigned to an output or VSC channel #.
Any control function can be disabled by setting the output number (and VSC channel) to 0.
Multiple controls functions can be assigned to the same output.
For example; a cooling thermostat and a de-humidistat can both be assigned to an output connected to a ventilation fan in
order to turn the fan on for either high temperature or high humidity.
Controls functions can be assigned to a zone.
The controller can monitor up to two sensor zones and the control you set up needs to know if it should respond to the sensor
readings for zone 1 or zone 2. (A zone number of 0 defaults to zone 1.)
Touch Panel
The controls functions are accessed via the main menu.
Software
The controls functions are accessed on the “Controls” tab page when connected to a controller. Click on the controls buttons to
modify the settings.
Active controls are highlighted with their respective function color.
Clicking on a control button will display the settings for that control function.
Press “Menu” button to enter main
menu. Press “Controls” to enter controls menu.
Controls are broken down into basic
categories. Press “Next” to access
additional controls.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected] 12
Lights, Day & Night Mode Controls
The day and night modes controls determine how the controller will decide when to switch between the day and night settings
that are entered in controls functions.
Day/Night Mode
“Synchronize with Lights” mode synchronizes with the lighting timer; day when lights are on, and night when off.
“Light Irradiance Sensor” mode activates day mode when the light level reaches the “W/m2 Day” set point and activates night
mode when the light level falls to the “W/m2 Night” set point. This mode is intended to be used in environments with sunlight.
“Flip-Box Mode” is designed to be used with dual zone environments. When in flip-mode the controller will assume zone 1 is in
day mode when the flip trigger is off and zone 2 is in night mode. When ‘flipped’ zone 1 will be in night mode and zone 2 will
be in day mode. Use the light flip timer to set the flip time, change delay and trigger outputs.
Day/Night Outputs: Enter an output number to activate during the day or night period. For example, if you want air
circulation fans to run all day but not at night, enter the fans output number into the “day” output.
W/m2 Day/Night: Light intensity levels which determine day and night when using the light sensor mode, and which will
activate light alarms (see alarms.)
The day and night modes are accessed via the “Controls” menu.
System administrator password is required to access the day/night mode menu if set.
The day and night mode settings are accessed on the first page
of the controls menu by pressing the “Light” controls button
then “Day/Night Mode” button.
Each zone can detect day/night from the lighting
timer, light sensor or flip box position. Also, an
output can be activated during the day or night
p
eriod.
Activated
Control
(highlighted)

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected]
13
Lights Timers
The controller has special timer controls for lighting equipment including two 24-hour lighting timers (one for each zone,) each
with their own secondary ‘B’ bank. The ‘B’ bank can be delayed to activate after the ‘A’ bank for reduced electrical load on
start-up.
Each lighting stage has its own hot-fire prevention timer which will prevent the lighting outputs from re-activating for a set
duration once turned off. The hot fire prevention timer ensures lamp bulbs and ballasts will not be damaged due to hot-firing.
See ‘System Settings’ for hot-fire timer configuration.
Lighting Timer: Enter the time of day (in 24-hour format 0:00-23:59) when the lights should turn on and off.
Output: Enter the output(s) for the primary (A) and secondary (B) lighting banks as connected to the controller. If B is not
used, leave it assigned to 0.
Delay (B Bank): Delay time (seconds) to start bank ‘B’ after bank ‘A.’
The lighting menu is accessed from the “Controls” menu under the “Lights” button.
Light-Flip Box Control
GrowControlTM is designed to safely and properly switch over lights on a light flip box. For extended light flip box contactor life,
ballasts should be turned off prior to switching the flip box trigger position. This prevents arcing and burning of the contacts
and also ensures the ballasts fire the bulbs properly after being switched.
Simply set the time of day to turn the flip trigger on and off and enter a delay time for switching. The delay time (seconds) will
be applied after turning off the lighting output before changing the state of the flip trigger, and after the trigger has been
flipped before re-starting the lights.
Bank A
Output
Bank B
Output
On
Off
On
Off
Lights ‘On’ Time Lights ‘Off’ Time
Bank B
Dela
y
Hot-fire timer keeps lights Of
f
The lights timer settings are accessed on the first page of the
controls menu by pressing the “Light” controls button then
“Light Timer” button.
Lights can be operated by a 24-
hour on/off timer. Enter the on
and off times, and select the
lights output#. Press “Bank”
button to show delayed bank B.
The 24-hour light timer can be
divided into two banks with a
on-delay to reduce electrical
load spikes when the lighting
timer activates.
Lights
Output
Flip Box
Output
On
Off
On
Off
Flip Box ‘On’ Time Flip Box ‘Off’ Time
Delay

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected] 14
Flip Delay: Seconds to delay before and after switching flip box trigger.
Light Flip Trigger ON/OFF time: Time of day (hh:mm) to turn flip trigger on and off.
Light Output: Output which operates the lighting contactor(s) to turn the ballasts on and off.
Flip Output: Output which operates the light-flip trigger cord.
Lighting Controls in Software
The day/night mode and lighting controls are located at the top of the controls tab. Click on the controls buttons to modify the
settings.
Light flip settings are found
in the Light controls menu. The light flip timer controls the ballast contactors and
the fli
p
box for inte
g
rated smart control.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected]
15
Temperature Controls
Temperature controls consist of heating and cooling thermostats, and high and low temperature limits (shut-offs.)
Heating & Cooling Thermostats
Cooling Thermostats turn an output on or open VSC’s when the temperature is too hot. Cooling thermostats are used to
operate ventilation fans, curtains, windows, chillers, evaporative coolers and more.
Heating Thermostats turn an output on or close VSC’s when the temperature is too cool. Use heating thermostats to
operate heating systems including hvac air handlers, water heaters, floor heating and more.
Limit Thermostats
Lo-Temp Limits turn an output off or close VSC’s when the temperature is too cool. Low temperature limits can be used to
close down vents and curtains or stop ventilation fan outputs from operating if the outdoor temperature is too low.
Hi-Temp Limits turn an output off or close VSC’s when the temperature is too hot. High temperature limits can turn off CO2
combustion generators, light banks, and other equipment if a room is too hot, or to disable heating systems if the outdoor
temperature is above a minimum.
Limit thermostats take precedence over other commands to an output # or VSC channel.
Staging Thermostats
Thermostats can be staged for multiple levels of heating and cooling.
In the example above:
Heat 1 will operate any time the temperature drops below 58 and will continue to heat until 60.
Heat 2 will operate any time the temperature drops below 50 and will continue to heat until 55.
Cool 1 will operate any time the temperature rises above 75 and will continue to cool until 72.
Cool 2 will operate any time the temperature rises above 85 and will continue to cool until 80.
Cool 3 will operate any time the temperature rises above 90 and will continue to cool until 85.
Cooling T-stat #1
Set Point 75°F
Dead Band 3°F
45 50 55 60 65 70 75 80 85 90 95
Cooling T-stat #2
Set Point 85°F
Dead Band 5°F
Cooling T-stat #3
Set Point 90°F
Dead Band 5°F
Heating T-stat #1
Set Point 60°F
Dead Band 2°F
Heating T-stat #2
Set Point 55°F
Dead Band 5°F
Temperature
Reading Limit
Control If sensor reading exceeds
set-points
Turn OFF output
If output # is not 0
Set VSC Position on Channel #
Both close the VSC
If channel # is not 0
Temperature
Reading Thermostat
Control If sensor reading exceeds
set-points
Turn ON output
If output # is not 0
Set VSC Position on Channel #
Cooling Opens, Heating Closes
If channel # is not 0

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected] 16
Thermostat Settings
Each thermostat has specific settings which control its function.
Zone#: The zone that the thermostat will take sensor readings from.
Temperature Source: The sensor type from the selected zone (air temperature, water temperature or outdoor temperature.)
Day/Night Set Points: Temperature values for the day and night which will activate the thermostat.
Dead-band: Temperature drop from set-point before turning on heat or turning off cooling (see dead-band below.)
Output#: Enter an output number to turn on (or off if limit control) when the thermostat is active.
VSC#: Enter a VSC channel # to send the target positions to when the thermostat is active.
Dead-Band
The “Deadband” setting in determines how tightly a thermostat tries to keep the temperature to the set-point. It is necessary
to have some dead-band: generally 2.0-5.0°F or 1.0 – 3.0°C.
Touch Panel
Set Point
Output
On
Off
Dead
Band
Cooling
Set Point
Output On
Off
Dead
Band
Heating
Press “Temp” from the controls menu. Select cooling, heating or high/low limit
functions.
Zone #
(0 defaults to 1)
Thermostat Control
Temperature Source
(Air, Water or Outdoor) Set-Points
Day & Night Values Dead Band
Hysteresis Setting VSC Set-Points
Channel & Position
(if using VSC)
Output #
To turn on/off
Output #
Turn On/Off VSC Channel
Send position to channel
Use standard on/off output, VSC output,
or both simultaneously when thermostat
control is activated.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected]
17
Software
The temperature controls are grouped into cooling thermostats, heating thermostats and temperature limits. Click on the
controls buttons to modify the settings.
Enter the set-points and dead-
band settings. Press “Advanced
Settings” button to change to
advanced settin
g
s.
Select temperature zone, sensor
source and output #. If VSC controls
are used, enter a channel and position
settings if desired.
Select a thermostat to view
its settings. Active controls
will be highlighted.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected] 18
Humidity Controls
Humidity controls consist of humidistats and de-humidistats, and high humidity limits.
Humidistats
Humidification Humidistats turn an output on when the humidity is too low. Humidification is used to operate humidifiers.
De-Humidification Humidistats turn an output on or set a VSC open position when the humidity is too high.
Dehumidification can operate ventilation fans, VSC (vents, shades or curtains) and more to reduce humidity.
Humidity Limits
Hi-Humidity Limits turn an output off when the humidity is too high. Turn evaporative cooler water valves off if the humidity
is too high.
Control Settings
Zone#: The zone that the humidistat will take sensor readings from.
Day/Night Set Points: humidity values for the day and night which will activate the humidistat.
Dead-band: Humidity drop from set-point before turning on humidification or turning off de-humidification.
Output#: Enter an output number to turn on (or off if limit control) when the humidistat is active.
VSC#: Enter a VSC channel # to send the target positions to when the humidistat is active.
Dead-Band
The “Dead-band” setting in determines how tightly a humidistat tries to keep the humidity to the set-point. It is necessary to
have some dead-band: generally 3-10%RH.
Set Point
Output
On
Off
Dead
Band
Dehumidify
Set Point
Output On
Off
Dead
Band
Humidify
Humidity
Reading Humidity Limit
Control If sensor reading exceeds
set-points
Turn OFF output
If output # is not 0
Set VSC Position on Channel #
Close VSC
If channel # is not 0
Humidity
Reading Humidistat
Control If sensor reading exceeds
set-points
Turn ON output
If output # is not 0
Set VSC Position on Channel #
Open VSC (dehumidify only)
If channel # is not 0
Zone #
(0 defaults to 1)
Humidistat Control
Set-Points
Day & Night Values Dead Band
Hysteresis Setting VSC Set-Points
Channel & Position
(if using VSC)
Output #
To turn on/off
Output #
Turn On/Off VSC Channel
Send position to channel
Use standard on/off output, VSC output,
or both simultaneously when humidistat
control is activated.

© 2013 Agrowtek Inc.
www.agrowtek.com | 83 Ambrogio Dr Suite H Gurnee, IL 60031 | [email protected]
19
Touch Panel
Software
The humidity controls are grouped into humidistats, de-humidistats, and humidity limits.
Select a control modify its settings.
Active controls will be highlighted. Enter the set-points and dead-band settings.
Press “Advanced Settings” to show advanced. Enter a zone#, output# and/or VSC
channel and position settings.
Press “Humidity” from the control menu. Select from de-humidify, humidify or
limit humidistats.
Table of contents
Other Agrowtek Control System manuals
Popular Control System manuals by other brands

Lamtec
Lamtec VMS Series manual

INNOVATIVE POOL PRODUCTS
INNOVATIVE POOL PRODUCTS Smart Touch LE owner's manual

Oaks
Oaks Smart Access Control System installation manual

KAR-TECH
KAR-TECH CAN RANGER Operation manual

Safety Xpress
Safety Xpress REMBOLSMU PRODUCT INFORMATION & INSTALLATION GUIDE

SOMFY
SOMFY animeo installation guide