
Air+, Inc | 222 Purchase St, Suite 210, Rye, NY 10580
Ph: 203-883-6700 | Fax: 203-883-6724 | info@air-plus.com | air-plus.com
OPERATION
The DMR-6000 has an Alarm Circuit that provides for communication to the BMS. The Alarm
Circuit utilizes a relay with normally closed contacts. The contacts are open whenever the unit is
not powered or there is a fault in the system. When the DMR-6000 is operating normally and pro-
ducing ions, the contacts close and the LED on the outside of the unit will illuminate. Connect
the BMS control wires to the BMS terminal block on the outside of the unit. (See Figure 3).
.
TROUBLESHOOTING
BMS ALARM CONTACTS
ON
OFF
When the power switch is turned to the “On” position, the DMR-6000 will activate, the LED will
illuminate, and the unit will produce ions. After about a minute, the self-cleaning mechanism
will run through its complete cleaning cycle and the unit will produce ions again. .
1.
If the DMR-6000 is not operating, check that the power switch is set to the “On” position and
the Ionization LED is illuminated. .
1.
The DMR-6000 has an internal automatically resetting fuse. If the fuse trips, remove power by
turning the power switch off, wait 2-5 minutes for the fuse to reset and turn power back on. If
the fuse trips again, contact customer support. .
3.
Confirm that all power wiring is connected properly to the terminal block on the outside of
the unit. Test the BMS Dry Contacts using a multimeter set to continuity mode. If the multime-
ter alarms, the circuit is continuous, and operation is confirmed. If it does not alarm, the circuit
is not continuous and there is a problem. Contact Air+ customer support as needed. ..
2.
Because the DMR-6000 is self-cleaning, no maintenance of any kind is required. The cleaning
cycle is factory programmed to initiate every 24 hours and upon start-up. .
2.
FIGURE 4
ON/OFF
SWITCH IONIZATION
LED
VALIDATED
ZERO OZONE EMISSIONS -
MEASURED OZONE
EMISSIONS FROM AIR+
DM-6000 DURING USE
PHASE DOES NOT EXCEED
0.005 PPM AS TESTED BY
UL 867
UL.COM/ECV
E534812
Once power is connected to the unit, press the power switch to the "ON" position. The LED
should illuminate. (See Figure 4). .
.
CAUTION: Do not connect power to the DMR-6000 before the installation is complete.
Always disconnect power before handling any of the unit components. .
CAUTION: Surge protection should be utilized for this product at the equipment or
circuit feeding the ionizer. A transformer used to power the product must be grounded.