20 Rockwell Automation Publication 7000-TG002J-EN-P - March 2015
Chapter 1 Fault Messages
X DClnk OvrCurrent 113 The DC Link current given by Idc Feedback (P322) has
exceeded the DC Link current trip settings (P169). Verify the
parameter settings of the drive. Check the HECS and burden
resistor. Confirm stable operation of the drive and any sudden
load transients.
•Verify that the parameters for drive and device ratings, and installed current sensing
components are set accordingly.
•Verify that the DC Link HECS is wired properly and properly powered.
•Verify the burden resistor value.
•Complete a DC Current Test to verify the feedback corresponds to the IDC command.
•Setup trending to capture DC Link current feedback and other related read-only
parameters (Contact factory if you require assistance).
•Check Alpha Line, and verify that the value is not too low (15°) and the current regulator is
not in limit; Decrease Flux Command Base Speed or increase incoming Line Voltage.
•Restart the drive to allow the start up diagnostics to detect any shorted thyristors, but
only attempt this once if shorted SCRs are detected.
X DCLnk OvrTemp 34 The thermal switch in the DC Link inductor has detected an
over temperature condition and opened the AC input to the
standard XIO. Ensure that the converter cooling fan is working
and that the air flow is not obstructed. Also check the 120V
wiring and the XIO card. There is a thermal switch in each DC
Link winding, and they areconnected in series.
•Verify operating conditions (ambient/ altitude/ load levels/ ventilation and fans) and
verify that the DC Link Reactor is within ratings.
•Check the 120V signal through the thermal switch.
•Verify the drive cooling circuit is operating correctly.
•Check the XIO board inputs and parameter status bits.
•Determine through elimination whether there is a faulty switch and replace if necessary.
X DC Neutral VSB 461 This fault indicates that the voltage sensing board associated
with the dc and neutral voltages is not plugged in.
•Check connector J25.
•Verify connection from VSB to ACB.
X X DriveApplication 583 This fault indicates that either the drive application (P751)
has been changed or that one or more of the application-
specific functions are incorrectly set (for example, for Marine
Application 1, P751 Drv Application must be set to ‘Marine 1’,
Speed Ref Select (P7) must be set to ‘App Specific’,
TorqueRef Select (P401) must be set to ‘App Specific’ and
Trq Control Mode (P90) must be set to ‘App Control’).
•Ensure that all application-specific parameters are correctly set.
•Cycle control power.
X Drive OvrLoad 144 Drv OvrLoad Trp (P163) as the absolute trip level,
Drv OvrLoad Dly (P164) as the base trip delay, and
Drv OvrLoad Min (P269) as initial detection level.
The drive has detected an overload condition in the dc link
indicated by Drv Overload (P551).
•Transient Loading – Check torque limit and overload settings and compare loading to
torque settings and trip settings.
•Open Burden Resistor – Check Current feedback and check the burden resistors.
•Verify the drive sizing and that the overload parameters to meet the load requirements.
DvcAnodCath/Snub 154 Device Anode-Cathode or Snubber fault NOT USED
Drv Output Open 161 NOT USED NOT USED
X Duplct Node Flt 603 The drive has detected nodes that have the same Node ID. •Change the affected drive(s) node ID using parameter DCSL Node ID (935).
X Encoder Loss 163 •Be sure that the encoder is powered and connected properly.
•Be sure that all channels are connected properly and not swapped at motor and drive end.
For example, swapping A+ and A- will give this fault
•Z+ and Z- are not to be used in PF7000 Forge drives, remove any wires, jumpers on the Z+
Z- terminals
•Tech notes related to Encoders are PF7000 4th Gen_FMW-11, PF7000 Firmware 9.001 and
9.002 with Encoder Release Notes
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Fault Message Fault Code Description Recommended Action(s)