11 Connect the button CLOSE between the clamp
21 and 25 of the control unit.
ATTENTION: Leave it open if not used.
21
26
COM.
STOP
12
Connect the NORMALLY CLOSED contact of
the STOP between the clamp 21 and 26 of the
terminal box.
ATTENTION: jumper the input 21 to the input
26 if not used.
Connect the NORMALLY CLOSED contact of the
OPENING LIMIT SWITCH (L.S.OP.) between the
clamp 21 and 27 of the terminal board.
Connect the NORMALLY CLOSED contact of the
CLOSING LIMIT SWITCH (L.S.CL.) between the
clamp 21 and 28 of the terminal box.
The automation can not work without limit
switches.
Before actioning the installation ensure that the limit
switches are functioning and correctly cabled.
13
21
27
28
COM.
L.S.CL.
L.S.OP.
14 30
29
• Connect the signal cable to the clamp 29 of
the control unit.
• Connect the earth of the antenna to the clamp
30 of the control unit.
The presence of the metallic parts or humidity in the
walls could have negative influences on the range
of the system. We suggest therefore to not place
the receiving antenna and/or transmitters near big
metallic objects, near the floor or on the ground.
15
31
32
33
COM.
PHOTO1
PHOTO2
Connect the NORMALLY CLOSED contact of
the photocell 1 (PHOTO1) between the clamp
31 and 32 of the terminal box.
Connect the NORMALLY CLOSED contact of
the photocell 2 (PHOTO2) between the clamp
31 and 33 of the terminal box..
ATTENTION: jumper the inputs 32 and 33 to
the clamp 31 if not used
The functioning of the PHOTOCELLS can be set
Entering the menu and
16
36
35
34
-
-
+
• Connect the clamp 36 of the control unit to
the clamp + of power supply for the
photocell’s transmitter.
• Connect the clamp 35 of the control unit to the
clamp - of power supply for the photocells
receiver and transmitter.
• Connect the clamp 34 of the control unit to
the clamp + of power supply for the photocells
receiver.
The photocells test is enabled by the menu
ATTENTION: the control unit supplies a voltage of
24 Vdc and can supply a maximum power of 3W.
For the safety edges test connect the test device of
the edge on the power supply pin TX (test activated
with low logical signal 0Vdc.)
37
38
EDGE 1
39
40
EDGE 2
17
41
42
24 Vac Acccessories output 24 Vac 3W.
18
Connect the 230 Vac SINGLE PHASE motor
between the clamps 43 - 44 - 45.
Connect the neutral on the clamp 43, phase 1
on the clamp 44, phase 2 on the clamp 45 and
the capacitor between clamps 44 and 45.
In case that a THREE PHASE 400 Vac motor
is used, connect the three phases to the clamps
43, 44 and 45.
Before activating the automatism check that the
wiring of the motor is compliant with the installation.
To do this, follow the procedure of the preliminary
checks.
!!! Risk of electric shock !!!
CLOSE INPUT
STOP INPUT
LIMIT SWITCHES INPUTS
ANTENNA INPUT
PHOTOCELLS INPUT
PHOTOCELLS POWER SUPPLY
SAFETY EDGE INPUTS
43
44
45
19 ~
43
44
45
W
~
~
~
V
U
36
35
34
-
-
+
36
35
34
+
-
+
Connect the safety edge 1 between the clamps
37-38 and the safety edge 2 between the
clamps 39-40.
The safety edge contact must be normally
closed or resistive 8K2 depending on the
selection.
Select the type of security edge used (mechanical or
8K2) through the menu and
The inputs, if are not used, must be jumpered in
case of selection of mechanical safety edge or, they
have to be closed through a 8.2K resistance
(supplied ) in case of the safety edge 8K2.