Amico Alert-2 Installation and operation manual

Operating & Maintenance Manual
Alert-2 Microprocessor Based
Digital Alarm System v5.9
www.amico.com

2Amico Pipeline
Contents
User Responsibility 5
Introduction 5 - 6
Features
Description of the Alarm
Shipment Details
The Alarm Back Box
The Frame/Module Assembly
Description of the Modules 7-10
Common to all Alarms
System Power Supply
Annunciator Module
Blank Module
Area Alarm
Area Display Module
2 in 1 Display Module
Compact Display Module
Sensor Module
Master Alarm
Master/Nema 4 Status Module
Computer Interface Module
Installation Guide 10 - 11
The Alarm Back Box
For Local Sensor Only
Standing Pressure Test
Frame/Module Assembly
Sensor
Local
Remote
Wiring 12 - 14
System Power Supply
Annuciator Module
Sensor Module
Local
Remote
Area Display Module
2 in 1 Display Module
2 Amico Pipeline

www.amico.com 3
Area Display Module
2 in 1 Display Module
Compact Display Module
Master/NEMA 4 Status Module
Computer Interface Module
Closing the Frame Module Assembly
Annunciator Module 14
Noise Level Control
Control of Remote Alarm Buzzer
Steps to Re-Calibrate the Sensor from Area Module v4.0 15
Area, 2 in 1, Compact Display Module 15 - 19
PSI/kPa/ BAR selection
Inch Hg/kPa/BAR selections
Common Settings for Pressure and Vacuum
Setting Factory Default
Setting Gas Identication Switches
Chart of Gas Specic Settings of Dip-Switches
Master/NEMA 4 Status Module 19 - 21
Repeat Alarm
Signal Input Selection
Maintenance Mode
Troubleshooting Guide 22 - 24
Error Code Messages on the Display Module 24
Model Numbers 25 - 28
Area Alarm
Master Alarm
Compact Alarm
NEMA 4 Alarm
Compact Master Combination Alarm
2 in 1 Area Alarm
Spare Part Numbers 29 - 31

4Amico Pipeline
Dimensions 32 - 37
Area Alarm
Master Alarm
Compact Alarm
Compact Master Alarm Combination
2 in 1 Alarm
NEMA 4
Appendix A - Wiring Diagram: Auto-Switching Power Supply 38
Appendix B - Wiring Diagram: Annunciator 39
Appendix C - Wiring Diagram: Automatic Voice/Pager Dialing System 40
Appendix D - Wiring Diagram: Area Display Module (Local Sensor) 41
Appendix E - Wiring Diagram: Area Display Module (Remote Sensor) 42
Appendix F - Wiring Diagram: 2 in 1 Display Module 43
Appendix G - Wiring Diagram: Compact Module 44
Appendix H - Wiring Diagram: Area Module to Master Module 45
Appendix I - Wiring Diagram: 2 in 1 Module to Master Module 46
Appendix J - Wiring Diagram: Abnormal Condition 47
Appendix K - Wiring Diagram: Area Slave 48
Appendix L - Wiring Diagram: Master/NEMA 4 Module 49
Appendix M - Wiring Diagram: Pressure Switch Connection to a Master Alarm 50
Appendix N - Wiring Diagram: Computer Interface Module 51
Appendix O - Wiring Diagram: Master to Slave Module 52
Appendix P - Technical Specication 53
Notes 54 - 55

www.amico.com 5
User Responsibility
Introduction
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to
equipment.
DANGER: denotes steps which can prevent electrical
shock to equipment or to prevent serious injury and/or
death.
Amico Microprocessor Based Alarm
Page: 4
USER RESPONSIBILITY
The information contained in this Installation and Operation Maintenance
Manual, pertains only to the ALERT-2 microprocessor based digital alarm.
This product will perform to conformity with the descriptions contained in this
manual, when assembled, operated, maintained and serviced in accordance
with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing,
worn, distorted or contaminated, must be replaced immediately. Should such
repair or replacement become necessary, please contact Amico Corporation
or their distributors.
All alarms should not be repaired, or altered without prior written or verbal
approval of Amico Corporation or it’s distributors. Failure to comply will void
all warranty on the alarm.
Statements in this manual preceded by the words WARNING,CAUTION,
DANGER and NOTE are of special significance. Please read these sections
carefully.
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
DANGER: denotes steps which can prevent electrical shock to equipment
or to prevent serious injury and/or death.
The information contained in this Installation and Operation Maintenance Manual, pertains only to the ALERT-2 micro-
processor based digital alarm. This product will perform to conformity with the descriptions contained in this manual,
when assembled, operated, maintained and serviced in accordance with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing, worn, distorted or contaminated, must be
replaced immediately. Should such repair or replacement become necessary, please contact Amico Corporation or their
distributors.
All alarms should not be repaired, or altered without prior written or verbal approval of Amico Corporation or its distributors.
Failure to comply will void all warranty on the alarm.
Statements in this manual preceded by the words WARNING, CAUTION, DANGER and NOTE are of special signicance.
Please read these sections carefully.
NOTE: Amico strongly recommends that alarms be checked annually by qualied sta.
The AMICO Medical Gas Alarm System (ALERT-2) incorporates the latest microprocessor technology for alarm and
surveillance systems. The alarm has been designed to provide user exibility and reliability. This manual will enable the
customer to install, use and maintain the alarm properly.
All Gases or Vacuum are displayed with large Red LED’s for clear visibility. To facilitate the monitoring function by hospital
personnel, a trend bar is provided to show the direction of the gas/vacuum pressure. Under normal operation, the gas
trend indicator will be in the GREEN - OK position. If the gas pressure approaches alarm condition, the trend indicator
will display a YELLOW - Caution indicator. If an alarm condition occurs, a RED-Alarm indicator will be displayed and the
buzzer will sound.
There are two buttons located on the front face of the Annunciator module. They are the “TEST” and “ALARM MUTE”
buttons. The function of the “Test”button is to verify that the buzzer and all the alarm LED’s are in normal working condition.
The function of the “Alarm Mute” button is to silence an alarm that has occurred.
A master status module monitors source equipment such as: Oxygen, Nitrous Oxide, Air compressors, Vacuum pumps,
Air dryers, high/low pressure switches, etc. This module can be connected to a “Building Management System”, with a
piggy-back computer interface board, that attaches to the master module.

6Amico Pipeline
Individual Microprocessor on each display, sensor and master module.
Gas specic sensors can be mounted locally or remote, up to 2,500 feet, [750m] utilizing 22 gauge twisted pair
(shielded cable should be used).
DISS gas specic sensor housed in a tamper proof enclosure. The Sensor Module is housed in an anodized aluminum
and nickle-plated brass enclosure to act as an interference barrier.
The Sensor Module is the smallest computer-calibrated temperature-compensated sensor in the industry.
True digital LED display and trend indicator for each service monitored.
Illuminated LED display that is visible at an angle and in dim lighting conditions.
PSI, kPa or BAR display (switch selected).
Self diagnostic circuitry with error display for problem identication.
Highly accurate Solid State Pressure piezo-resistive transducer.
Adjustable repeat alarm (1 to 60 minutes/or o) for the Area, 2 in 1 Alarm and Compact Alarm.
Adjustable repeat alarm (1, 12, 24 hours/or o) for the Master Alarm.
Dry contacts for remote monitoring of High and Low alarm status on the Area, 2 in 1 and Compact Alarm display
module.
Modules are factory mounted on a hinged frame assembly for ease of installation and maintenance.
Field programmable push buttons for adjustment of HI and LOW set-points on display module.
Area alarms available in 1 to 6 display modules.
Compact alarms available in 1 to 12 display modules.
Master alarms available in 10 to 60 points.
2 in 1 alarms available in 1 to 6 display modules with 5 to 30 master points.
Area, 2 in 1, and Compact Modules can be intermixed with Master Modules to create a combination alarm.
Built-In relay for remote annunciator applications.
Area, 2 in 1 and Compact Module indication for calibration (ashing bar graph).
FEATURES
The Alert-2 microprocessor based digital alarm system complies with NFPA-99.
The Alert-2 microprocessor based digital alarm system is UL Listed to U.S. and Canadian safety standards.

www.amico.com 7
Description of the Alarm
SHIPMENT DETAILS
When you receive an ALERT-2 series alarm from Amico Corporation, the package will consist of two main sections; the
Alarm Back Box and the Frame/Module Assembly. The Frame/Module assembly will be pre-congured, with the appro-
priate display modules, based upon the customer’s specications.
THE ALARM BACK BOX
The Alarm Back Box contains the auto-switchable System Power Supply with an ON/OFF switch, a built-in fuse and ter-
minal blocks (115 VAC, or 220 VAC). The back box also incorporates the pipe stubs for applications that require locally
(in box) mounted sensors.
THE FRAME/MODULE ASSEMBLY
The Frame/Module Assembly consists of the frame and all the modules that are pre-assembled to the customers speci-
cation. The hinged frame is designed to swing down from the back box to facilitate installation and servicing of the
alarm. This design will reduce installation time and eliminate the risk of improper installation since all the modules are
connected and tested at the factory.
The ALERT-2 alarm is divided into 4 or 7 main modules:
COMMON TO ALL ALARMS
1. SYSTEM POWER SUPPLY
The System Power Supply has been pre-installed into the back box assembly. The System Power Supply converts the
AC voltage supply to the alarm into two voltages: 5 VDC (regulated) required by the microprocessor hardware and 15
VDC (unregulated) required by the buzzer and the LED’s. This unit also contains the main ON/OFF power switch, the
transformer, the heat sink, the main fuse and fuse cover, the rectifying circuitry, the terminal blocks and the low voltage
DC power cable for connecting this unit to the annunciator module. The System Power Supply can be easily removed
and reinstalled by unscrewing it from the back box.
Description of the Modules

8Amico Pipeline
2. ANNUNCIATOR MODULE
The Annunciator Module contains the buzzer, a “Power On” LED, the “TEST” and the
“ALARM MUTE”buttons. The function of the“TEST”button is to verify that the buzzer and all
the LED’s are in working condition. An alarm will be heard when this button is pushed and
all the LED’s will light up. When the button is released, the alarm will silence. The “ALARM MUTE”
button is used to silence an alarm that has occurred. This module also contains a fail-safe relay
that de-energizes when the buzzer is activated. This relay can be used with the “Amico remote
buzzer”, for applications requiring a remote audible alarm (see Appendix B), for connection to
another Amico Alarm or a Building Management System.
3. BLANK MODULE
The Blank Module is used as a ller board for future provisions of the alarm.
Amico Microprocessor Based Alarm
Page: 8
DESCRIPTION OF MODULES
The ALERT-2 alarm is divided into (4) or (7) main modules:
COMMON TO ALL ALARMS
1. SYSTEM POWER SUPPLY
The System Power Supply has been pre-installed into the back box
assembly. The System Power Supply converts the AC voltage supply to
the alarm into two voltages: 5 VDC (regulated) required by the
microprocessor hardware and 15 VDC (unregulated) required by the
buzzer and the LED’s. This unit also contains the main ON/OFF power
switch, the transformer, the heat sink, the main fuse and fuse cover, the
rectifying circuitry, the terminal blocks and the low voltage DC power
cable for connecting this unit to the annunciator module. The System
Power Supply can be easily removed and reinstalled by unscrewing it
from the back box.
2. ANNUNCIATOR MODULE
The Annunciator Module contains the buzzer, a “Power On” LED, the
“TEST” and the “ALARM MUTE” buttons. The function of the “TEST”
button is to verify that the buzzer and all the LED’s are in working condi-
tion. An alarm will be heard when this button is pushed and all the LED’s
will light up. When the button is released, the alarm will silence. The
“ALARM MUTE” button is used to silence an alarm that has occurred. This
module also contains a fail-safe relay that de-energizes when the buzzer
is activated. This relay can be used with the “Amico remote buzzer”, for
applications requiring a remote audible alarm (see Appendix B), for
connection to an other Amico Alarm or a Building Management System.
3. BLANK MODULE
The Blank Module is used as a filler board for future provisions of the
alarm.
AREA ALARM
4. AREA DISPLAY MODULE
The Area Display Module provides a digital display of the actual pressure/vacuum of a
gas being monitored. In addition a gas trend indicator bar with HIGH and LOW alarms
are displayed. The trend bar has three coloured LED’s: Green for Normal condition, YELLOW
for Caution condition, and RED for high and low Alarm conditions.
Each display module contains a gas specic colour coded label (USA or ISO colours are
available). A space is also provided, at the base of the module, to identify the location that
the display module monitors. The display module is eld adjustable for pressure/vacuum
settings, repeat alarm, and units of measure. Whenever the module is in calibration mode,
the bargraph is ashing, indicating the calibration mode. Dry contacts for high and low
alarms are available for remote monitoring of each module.
5. 2 IN 1 DISPLAY MODULE
The 2 in 1 Display Module provides a digital display of the actual pressure/vacuum of the
gas being monitored. In addition, a gas trend indicator bar with High and Low alarms are
displayed. This module has two coloured LEDs - Green for Normal conditions and Red for
High and Low alarm conditions. It is eld adjustable for pressure/vacuum settings, repeat
alarms, and units of measure. Dry contacts for high and low alarms are available for remote
monitoring of each module.
Each module will continuously monitor up to 5 signals from source equipment or pressure
switches. If any of the signals being monitored go into an alarm condition, a Red LED will
illuminate and the audible alarm will sound.
PLEASE NOTE: Contacts located on back of module are Dry Contacts only.
DO NOT apply any voltage.
Alert - 2 Series
Page: 9
AREA ALARM
4. AREA DISPLAY MODULE
The Area Display Module provides a digital display of the actual
pressure/vacuum of a gas being monitored. In addition a gas trend
indicator bar with HIGH and LOW alarms are displayed. The trend
bar has three coloured LED’s: GREEN for Normal condition, YEL-
LOW for Caution condition, and RED for high and low Alarm
conditions.
Each display module contains a gas specific colour coded label
(USA or ISO colours are available). A space is also provided, at the
base of the module, to identify the location that the display module
monitors. The display module is field adjustable for pressure/vacuum
settings, repeat alarm, and units of measure. Whenever the module
is in calibration mode, the bargraph is flashing, indicating the calibra-
tion mode. Dry contacts for high and low alarms are available for
remote monitoring of each module.
5. 2 IN 1 DISPLAY MODULE
The 2 in 1 Display Module provides a digital display of the actual
pressure/vacuum of the gas being monitored. In addition, a gas
trend indicator bar with High and Low alarms are displayed. This
module has two coloured LEDs - green for Normal conditions and
red for High and Low alarm conditions. It is field adjustable for
pressure/vacuum settings, repeat alarms, and units of measure.
Dry contacts for high and low alarms are available for remote
monitoring of each module.
Each module will continuously monitor up to 5 signals from source
equipment or pressure switches. If any of the signals being
monitored go into an alarm condition, a red LED will illuminate and
the audible alarm will sound.
Please Note: Contacts located on back of module are Dry Contacts
only. DO NOT apply any voltage.
6. SENSOR MODULE
The Sensor Module contains the transducer which converts the
pressure/vacuum pressure source into a digital signal that is dis-
played on the display module. The sensor module is housed in a
black ABS plastic fire rated enclosure to reduce the risk of tamper-
ing. Each sensor is clearly labelled and colour coded for the gas or
vacuum being monitored. The sensor module contains a gas spe-
cific DISS fitting to ensure correct connection of the proper sensor to
the respective gas. Each sensor has been factory calibrated for the
specific gas shown on the sensor housing. If it is not connected to
the appropriate gas display module, an error message (E02) will be
displayed.
Alert - 2 Series
Page: 9
AREA ALARM
4. AREA DISPLAY MODULE
The Area Display Module provides a digital display of the actual
pressure/vacuum of a gas being monitored. In addition a gas trend
indicator bar with HIGH and LOW alarms are displayed. The trend
bar has three coloured LED’s: GREEN for Normal condition, YEL-
LOW for Caution condition, and RED for high and low Alarm
conditions.
Each display module contains a gas specific colour coded label
(USA or ISO colours are available). A space is also provided, at the
base of the module, to identify the location that the display module
monitors. The display module is field adjustable for pressure/vacuum
settings, repeat alarm, and units of measure. Whenever the module
is in calibration mode, the bargraph is flashing, indicating the calibra-
tion mode. Dry contacts for high and low alarms are available for
remote monitoring of each module.
5. 2 IN 1 DISPLAY MODULE
The 2 in 1 Display Module provides a digital display of the actual
pressure/vacuum of the gas being monitored. In addition, a gas
trend indicator bar with High and Low alarms are displayed. This
module has two coloured LEDs - green for Normal conditions and
red for High and Low alarm conditions. It is field adjustable for
pressure/vacuum settings, repeat alarms, and units of measure.
Dry contacts for high and low alarms are available for remote
monitoring of each module.
Each module will continuously monitor up to 5 signals from source
equipment or pressure switches. If any of the signals being
monitored go into an alarm condition, a red LED will illuminate and
the audible alarm will sound.
Please Note: Contacts located on back of module are Dry Contacts
only. DO NOT apply any voltage.
6. SENSOR MODULE
The Sensor Module contains the transducer which converts the
pressure/vacuum pressure source into a digital signal that is dis-
played on the display module. The sensor module is housed in a
black ABS plastic fire rated enclosure to reduce the risk of tamper-
ing. Each sensor is clearly labelled and colour coded for the gas or
vacuum being monitored. The sensor module contains a gas spe-
cific DISS fitting to ensure correct connection of the proper sensor to
the respective gas. Each sensor has been factory calibrated for the
specific gas shown on the sensor housing. If it is not connected to
the appropriate gas display module, an error message (E02) will be
displayed.

MASTER ALARM
8. MASTER/NEMA 4 STATUS MODULE
Each Master Status Module will continuously monitor up to 10 signals from source equipment
and pressure switches. If any of the signals being monitored go into an alarm condition, a
Red LED will illuminate and the audible alarm will sound. The module has a slow and
a rapid ashing LED rate. The last alarm condition always ashes at a rapid rate, while the
previously acknowledged alarms always ash at a slow rate.
PLEASE NOTE: Contacts located on back of module are Dry Contacts only.
DO NOT apply any voltage.
For Annual Test
• Reset power to make sure all LED’s light up
• Push and hold the‘Test’ button to light up all LED’s and the audible alarm
7. SENSOR MODULE
The Sensor Module contains the transducer which converts the pressure/vacuum pres-
sure source into a digital signal that is displayed on the Display Module. The sensor
module shall be housed in an anodized aluminum and nickel-plated brass enclosure
to act as an interference barrier also it is temperature compensated. Each sensor is
clearly labeled and colour coded for the gas or vacuum being monitored. The sen-
sor module contains a gas specic DISS tting to ensure correct connection of the proper
sensor to the respective gas. Each sensor has been factory calibrated by computer for the
specic gas shown on the sensor housing. If it is not connected to the appropriate gas
display module, an error message (EO2) will be displayed.
www.amico.com 9
6. COMPACT DISPLAY MODULE
The Compact Display Module shall have 2 displays in 1 board. The Compact Module
provides a digital display of the actual pressure/vacuum of a gas being monitored. In
addition a gas trend indicator bar with High and LOW alarms are displayed. The trend bar
as two colored LED’s: GREEN for Normal and RED for High and Low condition.
Each display module contains a gas specic colour coded label (USA or ISO colours are
available). The Display Module is eld adjustable for pressure/vacuum settings, repeat
alarm, and unit of measure. Dry contacts for high and low alarms are available for remote
monitoring of each module.

9. COMPUTER INTERFACE MODULE
The Computer Interface Module is a piggyback board that ts on top of the master
status module. This module plugs into the status module via a connector, located at the
bottom end of the status module. There are three mounting screws provided to secure this
module to the status module. This module provides dry contacts for interface to a “Build-
ing Management System”. The module is “Fail-Safe”, closed circuit monitoring.
PLEASE NOTE: The computer interface module is not compatible with the 2 in 1 board.
Amico Microprocessor Based Alarm
Page: 10
MASTER ALARM
7. MASTER/NEMA 4 STATUS MODULE
Each Master Status Module will continuously monitor up to 10 signals from
source equipment and pressure switches. If any of the signals being
monitored go into an alarm condition, a red LED will illuminate and the
audible alarm will sound. The module has a slow and a rapid flashing LED
rate. The last alarm condition always flashes at a rapid rate, while the
previously acknowledged alarms always flash at a slow rate.
PLEASE NOTE: Contacts located on back of module are Dry Contacts
only. DO NOT apply any voltage.
8. COMPUTER INTERFACE MODULE
The Computer Interface Module is a piggyback board that fits on top of the
master status module. This module plugs into the status module via a
connector, located at the bottom end of the status module. There are three
mounting screws provided to secure this module to the status module.
This module provides dry contacts
for interface to a “Building Manage-
ment System”. The module is “Fail-
Safe”, closed circuit monitoring.
NOTE: The computer interface
module is not compatible with the 2
in 1 board.
10 Amico Pipeline
Installation
THE ALARM BOX
Install the back-box to the studs of the wall at the desired height. Ensure that the box is securely in place. The mounting
brackets are adjustable to suit the thickness of the wall. MAKE SURE the box is parallel, squared and ush with the nished wall
surface, to ensure that the frame assembly will t properly.
FOR LOCAL SENSOR ONLY
If the sensors are to be mounted locally (inside the back box), the pipe stubs must be connected to the pipeline. Using
silver-brazing techniques, connect each pipe stub to it’s appropriate gas or vacuum while ensuring that the bottom of
the pipe stub is wrapped with a damp cloth. BE CAREFUL not to damage the DISS check-valve by overheating the lower
portion of the copper pipe. When the brazing of pipe stubs has been completed, the system can be pressure tested.
STANDING PRESSURE TEST
Perform a standing pressure test on the piping system as per NFPA-99 “Health Care Facilities”. Inspect all joints for leaks
and make certain each gas is piped to a correspondingly labelled gas service.
FRAME/MODULE ASSEMBLY
Step #1 Remove the frame/module assembly from its protective box.
Step #2 Remove screws from the frame section (6 screws).
Step #3 Attach the at head screws (provided with frame in plastic bag) to the hinge. This will line up with holes
on the box.
Step #4 Attach the frame wire with 2 dome head screws (provided with frame in plastic bag).
Step #5 Close the frame panel and tighten the screws on the frame plate.
Step #6 Carefully place the front frame over the fastened plate. Refasten the screws that were removed in Step #2.

www.amico.com 11
CAUTION: The microprocessor circuitry on the ALERT-2 alarm contains sophisticated integrated semiconductors. If it
becomes necessary to remove a module, PLEASE hold the boards by the edges. DO NOT TOUCH any of the components
on the board. Static discharge can cause the modules to malfunction, or become damaged.
SENSOR
LOCAL (Inside the Back Box)
1. Locate the gas specic sensor module to be installed.
2. In the back box, there are colour coded gas labels located
under the DISS Demand check valves. Each label identies
where each sensor module is to be placed.
3. The sensor module contains a gas specic DISS tting. Push
the sensor module hex-nut and nipple adapter up into the
demand check-valve. With a wrench, tighten the nut so that
it makes a good seal.
NOTE: Pressure on sensors are not to exceed 250psi for Pressure
sensors and 30” for vacuum sensors.
The new style sensors can read pressure up to:
Mid Pressure 99 Psi
Hi Pressure 249 Psi
Vacuum 30” Hg
REMOTE (Outside the Back Box)
1. Connect a Tee (supplied by others) to the pipeline with a
1/4”NPT female connection that will accept the DISS Demand
check-valve.
2. Locate the gas specic sensor module to be installed.
3. Thread the DISS Demand check-valve into the correct gas
pipe line.
4. The sensor module contains a gas specic DISS tting. Push
the sensor module hex-nut and nipple adapter up into the
demand check-valve. With a wrench, tighten the nut so that
it makes a good seal.
Amico Microprocessor Based Alarm
Page: 12
CAUTION: The microprocessor circuitry on the ALERT-2 alarm con-
tains sophisticated integrated semiconductors. If it becomes necessary
to remove a module, PLEASE hold the boards by the edges. DO NOT
TOUCH any of the components on the board. Static discharge can
cause the modules to malfunction, or become damaged.
SENSOR
LOCAL (In the Back Box)
1. Locate the gas specific
sensor module to be in-
stalled.
2. In the back box, there are
colour coded gas labels
located under the DISS
Demand check valves. Each
label identifies where each
sensor module is to be
placed.
3. The sensor module contains
a gas specific DISS fitting.
Push the sensor module
hex-nutand nipple adapter
up into the demand check-
valve. With a wrench, tighten the nut so that it makes a good seal.
NOTE: Pressure on sensors are not to exceed
250psi
for Pressure sensors and
30”
for Vacuum sensors
REMOTE (Outside the Back Box)
1. Connect a Tee (supplied
by others) to the pipeline
with a 1/4" NPT female
connection that will accept
the DISS Demand check-
valve.
2. Locate the gas specific
sensor module to be
installed.
3. Thread the DISS Demand
check-valve into the
correct gas pipe line.
4. The sensor module contains a gas specific DISS fitting. Push the
sensor module hex-nut and nipple adapter up into the demand
check-valve. With a wrench, tighten the nut so that it makes a
good seal.
OLD LOOK
Amico Microprocessor Based Alarm
Page: 12
CAUTION: The microprocessor circuitry on the ALERT-2 alarm con-
tains sophisticated integrated semiconductors. If it becomes necessary
to remove a module, PLEASE hold the boards by the edges. DO NOT
TOUCH any of the components on the board. Static discharge can
cause the modules to malfunction, or become damaged.
SENSOR
LOCAL (In the Back Box)
1. Locate the gas specific
sensor module to be in-
stalled.
2. In the back box, there are
colour coded gas labels
located under the DISS
Demand check valves. Each
label identifies where each
sensor module is to be
placed.
3. The sensor module contains
a gas specific DISS fitting.
Push the sensor module
hex-nutand nippleadapter
up into the demand check-
valve. With a wrench, tighten the nut so that it makes a good seal.
NOTE: Pressure on sensors are not to exceed
250psi
for Pressure sensors and
30”
for Vacuum sensors
REMOTE (Outside the Back Box)
1. Connect a Tee (supplied
by others) to the pipeline
with a 1/4" NPT female
connection that will accept
the DISS Demand check-
valve.
2. Locate the gas specific
sensor module to be
installed.
3. Thread the DISS Demand
check-valve into the
correct gas pipe line.
4. The sensor module contains a gas specific DISS fitting. Push the
sensor module hex-nut and nipple adapter up into the demand
check-valve. With a wrench, tighten the nut so that it makes a
good seal.
OLD LOOK
NEW LOOK
Amico Microprocessor Based Alarm
Page: 12
CAUTION: The microprocessor circuitry on the ALERT-2 alarm con-
tains sophisticated integrated semiconductors. If it becomes necessary
to remove a module, PLEASE hold the boards by the edges. DO NOT
TOUCH any of the components on the board. Static discharge can
cause the modules to malfunction, or become damaged.
SENSOR
LOCAL (In the Back Box)
1. Locate the gas specific
sensor module to be in-
stalled.
2. In the back box, there are
colour coded gas labels
located under the DISS
Demand check valves. Each
label identifies where each
sensor module is to be
placed.
3. The sensor module contains
a gas specific DISS fitting.
Push the sensor module
hex-nutandnipple adapter
up into the demand check-
valve. With a wrench, tighten the nut so that it makes a good seal.
NOTE: Pressure on sensors are not to exceed 250psi
for Pressure sensors and 30” for Vacuum sensors
REMOTE (Outside the Back Box)
1. Connect a Tee (supplied
by others) to the pipeline
with a 1/4" NPT female
connection that will accept
the DISS Demand check-
valve.
2. Locate the gas specific
sensor module to be
installed.
3. Thread the DISS Demand
check-valve into the
correct gas pipe line.
4. The sensor module contains a gas specific DISS fitting. Push the
sensor module hex-nut and nipple adapter up into the demand
check-valve. With a wrench, tighten the nut so that it makes a
good seal.
NEW LOOK

12 Amico Pipeline
Wiring
SYSTEM POWER SUPPLY
TURN OFF THE POWER SWITCH BEFORE CHANGING ANY MODULES AND/OR DISCONNECTING ANY CABLES, OR ELSE
THE FUSE WILL BLOW TO PROTECT THE CIRCUITRY.
1. Ensure that the ON/OFF switch is in the OFF position.
2. Through the top left side of the back box, bring in the AC power wires. Knockouts are
provided for making conduit connections to the box. All wiring is to be installed according
to local and national codes.
3. Connect the AC power to the terminal blocks as shown in the wiring diagram in Appendix
A and as specied in the technical specication in Appendix P.
ANNUNCIATOR MODULE
1. The Annunciator Module has a female receptacle located at the top right side of the board (J1).
2. Connect the DC power cable from the System Power Supply into the receptacle connection located on
the annunciator module. The connector is keyed and can only be plugged in one way, (Appendix B).
Amico Microprocessor Based Alarm
Page: 4
USER RESPONSIBILITY
The information contained in this Installation and Operation Maintenance
Manual, pertains only to the ALERT-2 microprocessor based digital alarm.
This product will perform to conformity with the descriptions contained in this
manual, when assembled, operated, maintained and serviced in accordance
with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing,
worn, distorted or contaminated, must be replaced immediately. Should such
repair or replacement become necessary, please contact Amico Corporation
or their distributors.
All alarms should not be repaired, or altered without prior written or verbal
approval of Amico Corporation or it’s distributors. Failure to comply will void
all warranty on the alarm.
Statements in this manual preceded by the words WARNING,CAUTION,
DANGER and NOTE are of special significance. Please read these sections
carefully.
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
DANGER: denotes steps which can prevent electrical shock to equipment
or to prevent serious injury and/or death.
SENSOR MODULE
LOCAL (Inside the Back Box)
1. The sensor module is provided with a 6”-8” [0.1m-0.2m] twisted pair of wires. One wire is Red (positive) and the
other wire is Black (negative). Connect the wires to the display module as shown in Appendix D. Take the Red
wire fromthe sensor and attach it to terminal “Sensor +” on the display module. Take the Black wire from the sensor
and attach it to terminal “Sensor -”. The terminal block on the display module is clearly marked for proper
connection of the sensor wires.
2. Repeat the above procedures with the remaining sensor modules.
REMOTE (Outside the Back Box)
1. The sensor module is provided with a 6”- 8” [0.1m - 0.2m] twisted pair of wires. Connect the wires to a junction box
(not supplied) located near the sensor as per the wiring diagram in Appendix E.
2. Connect a shielded twisted pair cable from the junction box to the back box assembly. Knockouts are provided
throughout the alarm back box. Up to 2,500 feet [750m] of 22 Gauge, shielded twisted pair cable can be used.

www.amico.com 13
3. Connect the Red wire from the cable to the terminal on the display module marked ”Sensor +”. Connect the
black wire to terminal “Sensor -” (see Appendix D).
4. Repeat the above procedures with the remaining sensor modules using the wiring diagram in Appendix E.
PLEASE NOTE: When remote sensors are used, a shielded or twisted pair cable is required (BELDEN #8451 or equivalent,
supplied by others). Ensure that the proper gas sensor module is connected to its corresponding area display module,
otherwise an error message (E02) will be displayed on the Area Display module.
AREA DISPLAY MODULE
1. If the dry contacts for High and Low alarm are to be used for remote monitoring, connect the wires to the appropriate
terminals, Com (Common), NO (Normally Open) or NC (Normally Closed), using the diagram in Appendix H.
2. See Appendix P for contact rating.
2 IN 1 DISPLAY MODULE
1. If the dry contacts for High and Low alarms are to be used for remote monitoring, connect the wires to the appropriate
terminals, COM (Common), NC (Normally Closed), or NO (Normally Open), using the diagram in Appendix F.
2. Pull the remote signal wires into the alarm panel. Make the connections to the terminal blocks located on the side
of the status module. The wiring fail-safe normally closed (NC) connections from the source equipment. The signal
level is 5 VDC. Please refer to Appendix I.
3. ENSURE that the unused terminals are jumpered. If this is not done, the terminals that have not been jumpered will
go into alarm.
COMPACT DISPLAY MODULE
1. If the dry contacts for high and low are to be used for remote monitoring, connect the wires to the appropriate
terminals, Com (Common), NO (Normally Open), NC (Normally Closed), using the diagram in Appendix G.
2. See Appendix P for contact rating.
MASTER/NEMA 4 STATUS MODULE
1. Pull the remote signal wires into the alarm panel. Make the connections to the terminal blocks located on the side
of the status module. The wiring is fail-safe normally closed (NC) connections from the source equipment. The
signal level is 5 VDC.
2. Make the appropriate wiring connections as per the wiring diagram in APPENDIX M and N.
3. For Version 3 ENSURE that the unused terminals in the master module are jumpered. If this is not done, the terminals
that have not been jumpered will go into alarm.
For Version 4, turn o switches for any unused points (SW2).

14 Amico Pipeline
COMPUTER INTERFACE MODULE
1. Pull the remote signal wires from the “Building management system” into the alarm panel. Make the connections
to the terminal blocks located on the side of the module. The wiring is fail-safe normally open, held closed, dry
contacts to the monitoring equipment.
2. Make the appropriate wiring connections as per wiring diagram in Appendix N.
CLOSING THE FRAME/MODULE ASSEMBLY
1. Swing up the frame assembly, ensuring that the stopper wires are folded into the back box.
2. Screw in the frame module to the top of the back box assembly by using the screws provided with the frame/module
assembly. The alarm is now ready for use!
Annunciator Module
NOISE LEVEL CONTROL
Factory Default: 90 Decibels
To decrease noise level:
1. Locate jumper at J5. Move jumper to:
LVL1 = 90 dBa.
LVL2 = 80 dBa.
LVL3 = 70 dBa.
CONTROL OF REMOTE ALARM BUZZER
Factory Default: Normal Condition
To silence remote alarm buzzer, when silencing the
annunciator module:
1. Locate jumper at J6. Move jumper to:
NORM =
Remote alarm buzzer will silence when annunciator
module is silenced.
ALRM =
Remote alarm will not silence when annunciator
module is silenced. The buzzer will only silence when
alarm condition has been cleared. Please refer to
Appendix B.
Amico Microprocessor Based Alarm
Page: 16
FIELD ADJUSTMENTS
THE ANNUNCIATOR MODULE
NOISE LEVEL CONTROL
Factory Default: 90 Decibles
To decrease noise level:
1. Locate jumper at J5. Move jumper to:
LVL1 = 90 dBa.
LVL2 = 80 dBa.
LVL3 = 70 dBa.
CONTROL OF REMOTE ALARM BUZZER
Factory Default: Normal Condition
To silence remote alarm buzzer when silencing the
annunciator module:
1. Locate jumper at J6. Move jumper to:
NORM =
Remote alarm buzzer will silence when annunciator
module is silenced.
ALRM =
Remote alarm will not silence when annunciator
module is silenced. The buzzer will only silence
when alarm condition has been cleared. Please
refer to Appendix B.
J
6
TEST
ALRM
NORM
SILENCE
LVL1
LVL2
LVL3
J5
Amico Microprocessor Based Alarm
Page: 16
FIELD ADJUSTMENTS
THE ANNUNCIATOR MODULE
NOISE LEVEL CONTROL
Factory Default: 90 Decibles
To decrease noise level:
1. Locate jumper at J5. Move jumper to:
LVL1 = 90 dBa.
LVL2 = 80 dBa.
LVL3 = 70 dBa.
CONTROL OF REMOTE ALARM BUZZER
Factory Default: Normal Condition
To silence remote alarm buzzer when silencing the
annunciator module:
1. Locate jumper at J6. Move jumper to:
NORM =
Remote alarm buzzer will silence when annunciator
module is silenced.
ALRM =
Remote alarm will not silence when annunciator
module is silenced. The buzzer will only silence
when alarm condition has been cleared. Please
refer to Appendix B.
J
6
TEST
ALRM
NORM
SILENCE
LVL1
LVL2
LVL3
J5

www.amico.com 15
Steps to Re-Calibrate the Sensor from Area Module v4.0
1. Turn on Alarm
2. Set switches #8 & #10 the OFF position
3. Set switches #5 & #6 the ON position
4. The display will show the current reading of the pressure
5. Adjust the calibration, using the“UP” and “DOWN” push buttons, to the desired value.
6. Set switches #5 & #6 the OFF position
7. Turn on #10 if Aims is connected (do not turn on #8)
When you have completed step #7, the display module will automatically go into a “RESET” mode. This will store the
data that you had entered.
A dip-switch is located on the back of the display module which is used to identify the gas of the display module. The
dip-switch contains ten switch settings.
PRESSURE ONLY
Factory Default:
High = 60 Psi, Low = 40 Psi
Repeat time = 30 min.
HIGH PRESSURE/NITROGEN
Factory Default:
High = 195 Psi, Low = 140 Psi
Repeat time = 30 min.
During programming, the “Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to accept a
new High set point. Adjust set point, using the“UP” and “DOWN” push buttons, to the desired value.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready to accept a
new Low set point. Adjust set point, using the“UP” and “DOWN” push buttons, to the desired value.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to accept a
new Repeat time set point. Adjust set point using the “UP” and “DOWN” push buttons, to the desired
value. [(Display dd=Disabled) Range from 1 to 60 Minutes]
7. Set switch #6 to the OFF position.
Area, 2 in 1, Compact Display Module
Alert - 2 Series
Page: 17
THE AREA/2 IN 1 DISPLAY MODULE
A dip switch is located on the back of the display module
which is used to identify the gas of the display module. The
dip-switch contains ten switch settings.
PRESSURE ONLY
Factory Default:
High = 60 Psi, Low = 40 Psi
Repeat time = 30 min.
HIGH PRESSURE/NITROGEN
Factory Default:
High = 195 Psi, Low = 140 Psi
Repeat time = 30 min.
During Programming the
“Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-HI-
HI-HI-
HI-), followed by the current set point.
Indicating the system is ready to accept a new High set point.
Adjust set point, using the “UP” and “DOWN” push buttons, to the
desiredvalue.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-LO-
LO-LO-
LO-), followed by the current set point.
Indicating the system is ready to accept a new Low set point.
Adjust set point, using the “UP” and “DOWN” push buttons, to the
desiredvalue.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-I-I-
I-I-I-I-
I-I-), followed by the current set point.
Indicating the system is ready to accept a new Repeat time set
point. Adjust set point using the “UP” and “DOWN” push buttons,
to the desired value. [(Display dd=Disabled) Range from 1 to 60
Minutes]
7. Set switch #6 to the
OFF position.
2in1 Alarm
Board
AreaAlarm
Board
When you have completed
step #7, the display module
will automatically go into a
“RESET” mode. This will store
the data that you had entered.
Compact Alarm
Board (v2.01)
Dip-Switches
2 in 1 Alarm
Board
Dip-Switch
Area Alarm
Board
Dip-Switch
Dip-Switch
Compact Alarm
Board (v2.02)

16 Amico Pipeline
When you have completed step #7, the display module
will automatically go into a“RESET” mode. This will store the
data that you had entered.
PSI / kPa / BAR selection
Factory Default - PSI
For PSI mode, set the switch #4 to the ON position. The LED PSI indicator located next to the GAS
pressure reading will illuminate.
For kPa mode, set the switch #4 to the OFF position and switch #9 to the ON position. The LED kPa
indicator located next to the GAS pressure reading will illuminate.
For BAR set the switch #4 to the OFF and the switch #9 to the OFF position. The LED kPa indicator
located next to the GAS pressure reading will illuminate. (There is no separate indicator for BAR).
VACUUM ONLY
Vacuum alarm set-point adjustment
Factory Default:
High = 30”Hg, Low = 12”Hg
Repeat time = 30 min.
During programming, the “Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to
accept a new High set point. Do not adjust this set point since the High set point is not used.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready
to accept a new Low set point. Adjust set point, using the“UP” and “DOWN” push buttons, to
the desired value.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to
accept a new Repeat time set point. Adjust set point using the“UP” and “DOWN”push buttons,
to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes]
7. Set switch #6 to the OFF position.
When you have completed step #7, the display module will automatically go into a “RESET” mode.
This will store the data that you had entered.
PSI
KPA
BAR
Alert - 2 Series
Page: 17
THE AREA/2 IN 1 DISPLAY MODULE
A dip switch is located on the back of the display module
which is used to identify the gas of the display module. The
dip-switch contains ten switch settings.
PRESSURE ONLY
Factory Default:
High = 60 Psi, Low = 40 Psi
Repeat time = 30 min.
HIGH PRESSURE/NITROGEN
Factory Default:
High = 195 Psi, Low = 140 Psi
Repeat time = 30 min.
During Programming the
“Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-HI-
HI-HI-
HI-), followed by the current set point.
Indicating the system is ready to accept a new High set point.
Adjust set point, using the “UP” and “DOWN” push buttons, to the
desiredvalue.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-LO-
LO-LO-
LO-), followed by the current set point.
Indicating the system is ready to accept a new Low set point.
Adjust set point, using the “UP” and “DOWN” push buttons, to the
desiredvalue.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-I-I-
I-I-I-I-
I-I-), followed by the current set point.
Indicating the system is ready to accept a new Repeat time set
point. Adjust set point using the “UP” and “DOWN” push buttons,
to the desired value. [(Display dd=Disabled) Range from 1 to 60
Minutes]
7. Set switch #6 to the
OFF position.
2in 1Alarm
Board
AreaAlarm
Board
When you have completed
step #7, the display module
will automatically go into a
“RESET” mode. This will store
the data that you had entered.

www.amico.com 17
InchHg / KPA / BAR selections
Factory Default - InchHg
For InchHg mode, set the switch #4 to the ON position. The LED indicating InHg located next to the
VACUUM source reading will illuminate.
For KPA mode, set the switch #4 to the OFF position and the switch #9 to the ON position. The LED
indicating KPA located next to the VACUUM source reading will illuminate.
For BAR mode, the KPA indicating source must be changed to BAR by use of a label. Set the switch
#4 to the OFF and the switch #9 to the OFF position. The LED indicating BAR located next to the
VACUUM source reading will illuminate.
COMMON SETTINGS FOR PRESSURE AND VACUUM
Repeat Alarm Enable/Disable
Factory Default - Disable
Disable
Set switch #5 to the OFF position to disable the repeat alarm.
NOTE: When the repeat alarm function is disabled, the alarm will not repeat.
Enable
Enable Mode: (Factory Default 30 min, when enabled).
Set switch #5 to the ON position.
PLEASE NOTE: The Module with the Lowest set Repeat Time is the one that controls the Repeat
Time. For example if one Module is set for 5min and one for 30min and both are Repeat Alarm en-
abled, the Alarm will now Repeat every 5min.
InchHg
KPA
BAR

18 Amico Pipeline
SETTING FACTORY DEFAULT
To quickly reset the module (Pressure or Vacuum) to the factory default settings as follows:
- Pressure: High set-point 60 Psi, Low set-point 40 Psi.
- Nitrogen & HP Air: High set-point 195 Psi, Low set-point 140 Psi.
- Vacuum: Low set-point 12 inchHg.
- No Repeat alarm, but set for 30 min..
1. Set switch #8 to the ON position.
2. Turn the power o (wait 5 seconds) then back on.
3. Set switch #8 to the OFF position.
The module is now in the default mode.
Amico Microprocessor Based Alarm
Page: 4
USER RESPONSIBILITY
The information contained in this Installation and Operation Maintenance
Manual, pertains only to the ALERT-2 microprocessor based digital alarm.
This product will perform to conformity with the descriptions contained in this
manual, when assembled, operated, maintained and serviced in accordance
with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing,
worn, distorted or contaminated, must be replaced immediately. Should such
repair or replacement become necessary, please contact Amico Corporation
or their distributors.
All alarms should not be repaired, or altered without prior written or verbal
approval of Amico Corporation or it’s distributors. Failure to comply will void
all warranty on the alarm.
Statements in this manual preceded by the words WARNING,CAUTION,
DANGER and NOTE are of special significance. Please read these sections
carefully.
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
DANGER: denotes steps which can prevent electrical shock to equipment
or to prevent serious injury and/or death.
SETTING GAS IDENTIFICATION SWITCHES
PLEASE NOTE: DO NOT tamper with switches #1, #2 and #3 on the dip-switch. Tampering with these positions will
result in an error message being displayed (EO2) and will disable the electrical interlock from the gas specic sensor.
Changes to these switches should only be done by properly trained personnel, when circuit
boards have to be changed in the eld.
Switches # 1, #2 and #3 are used for the gas identication of the display module. These will be set at the factory and
should not be tampered with in the eld.

www.amico.com 19
CHART OF GAS SPECIFIC SETTINGS OF DIP-SWITCHES
Alert - 2 Series
Page: 21
SETTING GAS IDENTIFICATION SWITCHES
NOTE: DO NOT TAMPER WITH SWITCHES #1, 2 AND 3
ON THE DIP-SWITCH. TAMPERING WITH THESE
POSITIONS WILL RESULT IN AN ERROR MESSAGE
BEING DISPLAYED (EO2) AND WILL DISABLE THE
ELECTRICAL INTERLOCK FROM THE GAS SPECIFIC
SENSOR.
CHANGES TO THESE SWITCHES SHOULD ONLY BE
DONE BY PROPERLY TRAINED PERSONNEL, WHEN
CIRCUITBOARDSHAVETOBECHANGEDINTHEFIELD.
Switches # 1, 2 and 3 are used for the gas identification of the
display module. These will be set at the factory and should not
be tampered with in the field.
CHART OF GAS SPECIFIC SETTINGS OF DIP-SWITCHES
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
N
4
4
4
4
4
4
4
4
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10
10
#1 - off
#2 - off
#3 - on
#1 - off
#2 - off
#3 - off
#1 - off
#2 - on
#3 - off
#1 - on
#2 - on
#3 - on
#1 - on
#2 - off
#3 - on
#1 - on
#2 - on
#3 - off
#1 - off
#2 - on
#3 - on
#1 - on
#2 - off
#3 - off
Oxygen
Nitrogen
Vacuum
Carbon Dioxide
Medical Air
WAGD
Nitrous Oxide
HP Air
Master/NEMA 4 Status Module
REPEAT ALARM
Factory Default - Disable
Disable Set switch #1 to the OFF position.
Set switch #2 to the OFF position.
Enable Set switch #1 to the ON position.
Set switch #2 to the OFF position.
Enable 12 HR Set switch #1 to the OFF position.
Set switch #2 to the ON position.
Enable 24 HR Set switch #1 to the ON position.
Set switch #2 to the ON position.
PLEASE NOTE: The above repeat alarm only applies to the Master/NEMA 4 alarm, for the 2 in 1 please
refer to page 17.
1 HR
12 HR
24HR
Version
34
5 min 1 HR
15 min 12 HR
30 min 24 HR
Version
34

20 Amico Pipeline
SIGNAL INPUT SELECTION
Factory Default - Normally Closed as per NFPA 99.
The Amico alarm can detect eld devices in the Normally Open or Normally Closed position.
For Normally Closed Set switch #3 to the OFF position.
For Normally Open Set switch #3 to the ON position.
PLEASE NOTE: The above signal input selection, applies to both alarm systems - the Master/NEMA 4
and the 2 in 1.
MAINTENANCE MODE
Factory Default - Disabled
The Maintenance (or Latch) mode is used to allow hospital personnel to identify loose wiring or faulty source equipment.
By putting the master module into “Latch” mode, any alarms received; even transient ones, will be latched-on so that
maintenance personnel can identify the source of the problem. The Maintenance mode will disable the automatic reset,
if a fault condition has been rectied. The alarm indicator can only be turned-o by pushing the “alarm silence” button
on the annunciator module twice. The “Maintenance” LED will illuminate whenever the maintenance mode is enabled.
1 HR
12 HR
24HR
Version
34
Disable Set switch #4 to the OFF position.
Enable Set switch #4 to the ON position.
Other manuals for Alert-2
1
Table of contents
Other Amico Security System manuals

Amico
Amico Alert-4 Manual

Amico
Amico Alert-3 LCD v2.3 Installation and operation manual

Amico
Amico Alert-3 LCD v2.3 Installation and operation manual

Amico
Amico Chemetron User manual

Amico
Amico Alert-2 User manual

Amico
Amico Alert-3 LCD v2.3 User manual

Amico
Amico Alert-4 Installation and operation manual

Amico
Amico A3P-SENS-L-GAS Installation and operation manual

Amico
Amico Alert-3 LCD v2.3 Installation and operation manual

Amico
Amico Alarm Valve Combo Unit Manual