Anden A200V1 User manual

SAFETY INSTRUCTIONS
WARNING
1. High voltage may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power
disconnected until installation/service is completed.
2. Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling duct work.
3. Dropping may cause personal injury or equipment damage. Handle with care and follow installation instructions.
CAUTION
1. Read all instructions before beginning installation.
2. Improper installation may cause property damage or injury. Installation, service, and maintenance must be performed by a qualified service
technician.
3. Do not use in pool applications. Pool chemicals can damage the dehumidifier.
4. Wait 24 hours before running the unit if it was not shipped or stored in the upright position
READ AND SAVE THESE INSTRUCTIONS
Model A200V1, A300V1, A300V3
Dehumidifier
Installation and Operating Instructions
1

TABLE OF CONTENTS
SPECIFICATIONS
TABLE 1 – SPECIFICATIONS Model A200V1 Model A300V1 Model A300V3
Capacity (AHAM DH-1-2008 80°F, 60% RH) 210 pints per day 300 pints per day 300 pints per day
Airflow @ 0"w.c. 400 CFM 500 CFM 500 CFM
Unit Weight 140 lbs 140 lbs 145 lbs
Voltage 240 VAC 240 VAC 277 VAC
Nominal Operating Current @ 80°F / 60% RH* 6.6 Amps 12.0 Amps 9.5 Amps
Filter MERV 11 MERV 11 MERV 11
*Do not use for circuit wire sizing or overcurrent protection sizing; see POWER WIRING section on page 6 for this information.
SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SET UP DEHUMIDIFIER FOR INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 3
Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ducting & Filter Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
HANGING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
DRAIN INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
POWER WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
MODEL A76 CONTROL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Alternate External Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
SERVICE PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2

SET UP DEHUMIDIFIER FOR INSTALLATION
LOCATION CONSIDERATIONS
The dehumidifiers should be spaced evenly
throughout the area to be dehumidified with
the following recommendations:
1. Avoid placement where the discharge of
one dehumidifier is pointing toward the
inlet of another See FIGURE 1.
2. Account for handling dehumidifier
condensate by considering drain or sump
pump locations. See FIGURE 2.
3. Leave appropriate room on the electrical
service side to remove panel for field
connections. See FIGURE 3.
The recommended orientation is to install
the dehumidifiers around the perimeter
of the room with the dehumidifier inlet
pointing toward the wall and the outlet
pointed to distribute the dry air over the
canopy. This installation maximizes allowable
plant space and works with the existing
room fans to distribute air over the canopy.
ELECTRICAL
SERVICE PANEL
FIELD WIRING
ACCESS
DRAIN FITTING
16"
MINIMUM CLEARANCE
FROM WALL TO
DEHUMIDIFIER
INLET
CANOPY
HEIGHT
90-232890-2328
90-2329
FIGURE 3 – SERVICE SIDEFIGURE 2 – CONDENSATE DRAIN LOCATION
FIGURE 1 – PLACEMENT WITHIN SPACE
3

INSTALLATION
IMPORTANT: Remove plywood shipping base before proceeding to the next installation steps.
The preferred method of installation is hanging – see HANGING section on page 5.
The alternate method is floor level placement. Replace the eye bolts with the included 1/4"–20, 1.0" thread length rubber cushioned leg levelers.
In each installation the unit must be level for proper draining.
DUCTING & FILTER INSTALLATION
The preferred methods of installation are hanging, followed by floor level placement with straight through airflow. There are alternate discharge
openings on the top, bottom, and side of the unit. See FIGURE 5. If ducting the inlet, all duct connections should be installed in accordance with local
and national standards. For the highest fan efficiency, any duct bends and transitions should be made to minimize airflow losses. For the A200V1, at
least one discharge opening must remain uncovered and for the A300V1 or A300V3, at least two discharge openings must remain uncovered, one
of which must be the large opening on the panel opposite the inlet panel. More discharge openings uncovered will provide the highest capacity and
efficiency. Covers are included with the dehumidifier to close off discharge openings that are not to be used.
Before installing the unit, remove the shipping platform from the unit and install the inlet duct with filter using the 6 provided screws. Install the filter
access door using the knob to secure. See FIGURE 6.
ALTERNATE DISCHARGE
AND ONE ON BOTTOM
SHIPPING
PLATFORM
FILTER DOOR
FILTER
AND RACK
14.00 FILTER ACCESS DOOR
14.13
15.50
14.88
14.88
15.50
All discharge openings are the same size. Use 6" x 15" duct.
OUTLET DUCTINGINLET DUCTING
90-2328 90-2328
90-2328
FIGURE 5 – ALTERNATE DISCHARGE LOCATIONS FIGURE 6 – PREPARE UNIT FOR INSTALLATION
FIGURE 4 – DUCT CONNECTION SIZES (INCHES)
4

UNISTRUT
1/4"–20 UNC THREADED ROD
1/4"–20 UNC EYE BOLT
1/4"-20 EYE BOLT
OR 1/4"-20
THREADED ROD
RIVNUT
MOUNTING
FOOT BRACKET
FLAT WASHER
1/4"-20 NUT
WITH INTEGRAL
WASHER
90-233590-2335 90-2339
FIGURE 9 – HANGING UNIT
WITH THREADED ROD
FIGURE 7 – HANGING UNIT
WITH CHAIN AND EYE BOLTS
FIGURE 8 – HARDWARE FOR
SUSPENDING DEHUMIDIFIER
HANGING
The recommended method for hanging the dehumidifier is to use the eye bolts and hardware included in the parts bag. See FIGURE 7. Assemble the
four eye bolts to the mounting foot brackets as shown in FIGURE 8, and suspend using cable, chain, strapping or other support methods. NOTE: The
chain, cable or strapping must have a 200 lb. working load minimum, and each eye bolt must be used to suspend the dehumidifier.
The dehumidifier can be suspended using 1/4"-20 threaded rod as shown in FIGURE 9. IMPORTANT: Place the provided nuts and washers in the
same location as shown in Figure 8 when suspending with threaded rod.
The dehumidifier must be level for proper draining. Adjust the length of the chain, cable, threaded rod, etc., to level in all directions.
CABLE TIE FLEXIBLE 3/4"
DRAIN TUBING
KEEP TOP OF LOOP
BELOW THE BOTTOM
OF THE DEHUMIDIFIER
2"
MIN
1/8" PER FT
90-233190-2331
FIGURE 11 – FLEXIBLE DRAIN TUBINGFIGURE 10 – PVC DRAIN TUBING
DRAIN INSTALLATION
The blower draws air through the dehumidifier putting the cabinet under negative pressure. As a result a P-trap is required for proper draining.
The drain outlet on the dehumidifier can be hard piped using a 3/4" PVC Slip x 1" MNPT right angle fitting and 3/4" nominal drain tubing. If flexible,
clear PVC tubing is preferred, the provided drain fitting with a right angle bend to a 3/4" hose barb fitting can be installed. NOTE: PTFE thread seal
tape is recommended for threaded connections and hand tighten only. If hard pipe is used, PVC primer and cement is recommended for the slip
fit connections. After installing the drain, pour enough water (about 2 pints) into the dehumidifier to prime the traps. Remove the air filter from the
dehumidifier to access the drain pan.
5

POWER WIRING
WARNING
ELECTRICAL SHOCK HAZARD: High voltage may cause serious injury or death from electrical shock. Disconnect and tag electrical service before
starting installation or field-service. Leave electrical service disconnected until installation or field-service is complete.
ELECTRICAL SHOCK HAZARD: An interrupted or broken ground may cause property damage, serious injury or death should an electrical fault
occur. The cabinet must be grounded in accordance with NEC ANSI/NFPA 70-2011 or local codes. In Canada, refer to Canadian Electrical Code
CSA C22.1.
FIRE HAZARD: Use of improper wire may cause serious injury, property damage or death due to fire. Do not use aluminum wire for electrical
service to the dehumidifier. Use only copper wire.
CAUTION
Use of an undersized circuit breaker may cause property damage and/or the need for mold remediation service. See Specifications for wire and
circuit breaker sizing.
The dehumidifier must be hard wired, and an electrical disconnect switch must be installed to comply with appropriate codes or ordinances.
United States Installations: Make all electrical connections in accordance with the current edition of the NEC ANSI/NFPA 70 and any local codes or
ordinances that may apply.
Canada Installations: Make all electrical connections in accordance with the current edition of the Canadian Electrical Code CSA C22.1 and any local
codes or ordinances that may apply.
TABLE 2 – ELECTRICAL SPECIFICATIONS FOR HARD WIRING Model A200V1 Model A200V1 Model A200V1
Voltage 230-240 VAC, 60 Hz, 1 phase 230-240 VAC, 60 Hz, 1 phase 265-277 VAC, 60 Hz, 1 phase
Minimum Circuit Capacity 13 A 18 A 15 A
Maximum Fuse or Circuit Breaker Amps 20 A 30 A 25 A
Minimum Wire Size AWG 14 AWG 12 AWG 14 AWG
If using the alternate drain fitting, follow the steps below to remove the
existing drain and install the alternate.
1. Remove the side panel adjacent to the inlet duct. See FIGURE 12.
2. Remove the nut and O-ring from the existing drain and pull out
existing drain.
3. Remove the nut from the alternate 90° drain fitting with hose barb
connection and insert the new fitting into the drain. NOTE: Use
plumber's putty between the drain and water side of the drain pan.
4. Install the nut and hand-tighten.
5. Pour a small amount of water in the drain to verify the seal between
the drain fitting and drain pan.
REMOVE THIS PANEL
INLET DUCT AND FILTER
90-2328
FIGURE 12
6

WIRING INSTRUCTIONS
1. Disconnect electrical service at the main fuse or circuit breaker box.
2. Install an electrical disconnect to the line service, located per local and national standard.
3. Remove the electrical service panel from the dehumidifier. See FIGURE 13.
4. Route the service cable through one of the holes in the top of the dehumidifier. USE ONLY COPPER SUPPLY WIRES.
5. Secure the cable/conduit to the dehumidifier using fittings/connectors approved for the type of cable/conduit used.
6. Connect the ground wire of the service cable to the ground lug in the electrical service box. See FIGURE 14.
7. Connect the line voltage wires of the service cable to the L1 and L2 terminals. See FIGURE 14.
8. Reattach the electrical service panel.
9. Restore electrical service at the main fuse or circuit breaker box.
GND
L2
L1
2-POSITION POWER TERMINAL BLOCK AND GROUND LUG
LOCATED IN DEHUMIDIFIER ELECTRICAL PANEL. INSERT WIRE
INTO OPENING AND SECURE USING THE TERMINAL SCREWS.
ELECTRICAL SERVICE OPENINGS
ELECTRICAL
COMPARTMENT
90-2328
FIGURE 14 – POWER WIRINGFIGURE 13 – ELECTRICAL CABINET (SERVICE PANEL REMOVED)
7

MODEL A76 CONTROL
NOTE: Use 18–22 AWG wire for control wiring.
A Model A76 Control must be wired to the
dehumidifier for external control:
1. Turn off power to the dehumidifier at the
fuse or breaker until wiring is completed.
2. Run a 3-wire thermostat cable (use 18–22
AWG wire) from the Model A76 to the
electrical panel of the dehumidifier.
3. Trim about 1/4" of insulation from the end of
the wires on each end. Insert a small blade
screwdriver into the square opening next to
the desired terminal in the dehumidifier to
open the clamping spring of the terminal.
Insert the wire and remove the screwdriver to
catch the wire. At the Model A76 secure the
wires into the terminals and tighten the cage
screws. See FIGURE 15.
4. Use extra wire to make a small jumper to
wire between the R/+ terminal and one of
the DH terminals of the Model A76 Control.
The Model A76 will measure the relative
humidity and turn the dehumidifier on and off to
control the humidity level to the desired setting.
The humidity setting can be adjusted from the
control while the display allows easy access and
monitoring of the humidity level in the space. It
is recommended that the Model A76 be mounted
at/near canopy height.
Press the ON button on the Model A76 to turn
on the control. The UP/DOWN arrow buttons
are used to set the desired humidity setting. At
all other times, the Model A76 will display the
measured humidity level. Reference the Model
A76 Installation Instructions and Owner’s Manual
for set-up.
ALTERNATE EXTERNAL CONTROLS
A Model 8840 thermostat can be used to control
the HVAC equipment, and for dehumidifier
control in place of the Model A76. The
Model 8840 thermostat has Wi-Fi capability.
Additionally, up to four remote sensors can
be mounted near the canopy and connected
to a single thermostat. The four humidity
measurements can be averaged and the
thermostat will turn on the dehumidifier based
on the averaged value.
Reference the 8840 Installation Instructions and
Owner’s Manual for set-up and operating details.
DH
DH
R/+
C/-
B
A
R/
DH
C
DH
1
2
3
4
N
NOT
USED
MODEL A76 CONTROL
5-POSITION TERMINAL BLOCK IN
DEHUMIDIFIER ELECTRICAL PANEL
INSERT A SMALL FLAT BLADE SCREWDRIVER
TO OPEN THE WIRING LATCH. INSERT THE
WIRE AND RELEASE THE LATCH TO COMPLETE.
MAKE A SMALL JUMPER AND PUT IT IN
THE R/+ AND ONE OF THE DH TERMINALS
R/
DH
C
DH
1
2
3
4
N
NOT
USED
CONTROL MODULE OF MODEL 8840 THERMOSTAT
INSERT A SMALL FLAT BLADE SCREWDRIVER
TO OPEN THE WIRING LATCH. INSERT THE
WIRE AND RELEASE THE LATCH TO COMPLETE.
5-POSITION TERMINAL BLOCK IN
DEHUMIDIFIER ELECTRICAL PANEL
FIGURE 15 – MODEL A76 WIRING
FIGURE 16 – MODEL 8840 WIRING
8

OPERATION
1. Check all wiring from the electrical service line to the dehumidifier.
2. Check all wiring between the dehumidifier and the Model A76 Control.
TURN ON & SET MODEL A76 CONTROL
1. When power is supplied to the dehumidifier, the control will display the measured humidity and initially be in OFF Mode.
2. Press the ON button on the Model A76 Control.
3. The default humidity setting is 60%RH. Use the UP/DOWN arrow buttons to adjust the humidity setting. The first button press will display the
current setting and SET on the LCD display. Each subsequent push of the buttons will change the setting by 1%RH.
4. When desired humidity setting has been set, the control will return to Normal Mode, displaying the measured humidity 5 seconds after the last
button press/release.
SEQUENCE OF OPERATION
When the measured humidity is greater than the setting, the control will activate the dehumidifier output, the dehumidifier will begin dehumidifying,
and ON will blink on the Model A76 LCD display. When the measured humidity falls 3% below the setting, the control will deactivate the dehumidifier
output, the dehumidifier will stop dehumidifying and the LCD will display a solid ON.
CONTROL LIMITS
If the control measures a dew point below 40°F OR a temperature above 99°F, the control will deactivate the dehumidifier output, if actively
dehumidifying, the dehumidifier will stop dehumidifying and ON and *will blink on the LCD screen. The control will resume normal operation when
the measured dew point is greater than 45°F or the measured temperature is below 94°F, depending on what control limit was exceeded.
Reference the Model A76 Installation Instructions for additional information.
ALTERNATE CONTROLS
If using an alternate control, reference the Installation and Operating Instructions supplied with the control.
MAINTENANCE
FILTER
After initial installation, the air filter should be replaced every 6 months. Remove the filter access panel to remove and replace the filter.
DRAIN
The drain should be checked periodically to ensure there are no blockages or air lock in the drain system.
CONTROL
The surface of the Model A76 Control can be cleaned with a damp cloth or non-abrasive general cleaner. Do not spray any liquid directly on the
control. Spray water or cleaner onto a soft cloth and gently wipe the surface of the control.
9

TROUBLESHOOTING
Technical Support is available Monday through Friday, 7:00 a.m. to 5:00 p.m. CST, at (800) 972-3710. Use the guide below to identify and correct
system faults. Contact Technical Support before replacing the unit or any components and for additional troubleshooting.
TABLE 3 – TROUBLESHOOTING GUIDE
Symptom Possible Reason Troubleshooting Procedure
Dehumidifier does not turn on/run. No power to unit. • Check the wiring to the dehumidifier.
• If using a Model A76, check that the control is turned ON.
• Check that the circuit breaker has not tripped.
Dehumidifier blower is running but
with little or no airflow.
Pressure drop across dehumidifier is
higher than 0.6"w.c.
• Check dehumidifier air filter, replace if heavily loaded.
• Check that nothing is obstructing air flow into, or out of the dehumidifier.
Dehumidifier is not draining properly. Drain line blocked or unit not level. • Verify that the unit is level.
• Check that the p-trap is installed correctly and primed.
• Check the drain line for blockages and for a continuous downward slope.
Dehumidifier is producing hot air. Normal function. • Air is reheated across the condenser coil, resulting in a temperature rise
between inlet and outlet.
10

SERVICE PARTS
No. Part Description Part No.
1Transformer, 350VA 5712
2Transformer, 50VA 5713
3Contactor, Compressor 5714
4Time Delay Relay 5715
5Capacitor, Run 5716
6Filter, Merv 11 5717
7Outlet Patch 5718
8Electrical Access Panel 5719
9Filter Access Panel 5720
10 Leveling Feet 5721
11 90 Degree Elbow Fitting with 3/4" Hose Barb Fitting 5722
No. Part Description Part No.
12 Fan Assembly 5723
13 Fan Relay 5727
Not Shown
Model A76 Control 76
Eye Bolts 5728
1A Fuse 5729
3A Fuse 5730
High Pressure Switch 5731
Low Pressure Switch 5732
Crankcase Heater 5733
ELECTRICAL PANEL
12
7
8
2
1
5
3
13
4
9
10
6
11
90-2333
11

anden.com
P.O. Box 1467
Madison, WI 53701-1467
800.972.3710 F: 608.257.4357
Printed in USA
©2018 Anden – A Quality brand from Research Products Corporation
61001584 B2207841B 1.18
LIMITED WARRANTY
Your Research Products Corporation Anden™ Dehumidifier is expressly warranted for five (5) years from date of installation to be free from defects in materials or workmanship.
Research Products Corporation’s exclusive obligation under this warranty shall be to supply, without charge, a replacement for any component which is found to be defective within such
five (5) year period and which is returned not later than thirty (30) days after said five (5) year period by you to either your original supplier or to Research Products Corporation, Madison,
Wisconsin 53701, together with the model number and installation date of the dehumidifier.
THIS WARRANTY SHALL NOT OBLIGATE RESEARCH PRODUCTS CORPORATION FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS
FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE DEHUMIDIFIER ITSELF.
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID FIVE YEAR PERIOD. RESEARCH PRODUCTS
CORPORATION’S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORESAID
IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED. THIS LIMITED WARRANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS UNIT
INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR. IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR, ALL DISCLAIMERS
OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above exclusion or limitations may
not apply to you.
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
WARRANTY REGISTRATION
Visit us online at anden.com to register your Anden product. If you do not have online access, please mail a postcard with your name, address, phone number, email address, product
purchased, model number, date of purchase, and dealer name and address to: Research Products Corporation, P.O. Box 1467, Madison, WI 53701.
Your warranty registration information will not be sold or shared outside of this company.
12
This manual suits for next models
2
Table of contents
Other Anden Dehumidifier manuals

Anden
Anden A320V1 User manual

Anden
Anden A210V1 User manual

Anden
Anden SURNA S320V1 User manual

Anden
Anden A210V1 User manual

Anden
Anden A710V1/V3 User manual

Anden
Anden A95F User manual

Anden
Anden Surna S210V1 User manual

Anden
Anden A320V1 User manual

Anden
Anden 5859 User manual

Anden
Anden A710V1 User manual