Ansul AUTOPULSE IQ-636X-2/E User manual

K3
P/N 52853:K3 ECN 15-230
Document 52853
9/28/15 Rev:
AUTOPULSE
®
IQ-636X-2/E
ANALOG ADDRESSABLE
CONTROL SYSTEM
Fire Alarm Control Panel Installation Manual
(Meets the Requirements of UL 864 9th Edition)

2IQ-636X-2 Installation Manual — P/N 52853:K3 9/28/15
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notifi-
cation capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of
an automatic fire alarm system (as described above) and a life
safety communication system that may include an autonomous
control unit (ACU), local operating console (LOC), voice commu-
nication, and other various interoperable communication meth-
ods—can broadcast a mass notification message. Such a
system, however, does not assure protection against property
damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premises following
the recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no charge
to all installing dealers. This document can be found at http://
www.systemsensor.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-floor
or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, chim-
neys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reach-
ing the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at var-
ious levels of smoke density. If such density levels are not cre-
ated by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing cham-
bers tend to detect smoldering fires better than flaming fires,
which have little visible smoke. Detectors that have ionizing-type
sensing chambers tend to detect fast-flaming fires better than
smoldering fires. Because fires develop in different ways and
are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide
adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn-
ing of fires caused by arson, children playing with matches
(especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi-
als, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detec-
tors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for
the connection of alarm transmission wiring, communications,
signaling, and/or power. If detectors are not so located, a devel-
oping fire may damage the alarm system, compromising its abil-
ity to report a fire.
Audible warning devices such as bells, horns, strobes,
speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device
may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note
that:
• An emergency communication system may take priority over
a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligi-
bility requirements as defined by NFPA, local codes, and
Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis-
seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear
a fire alarm signal, do not respond to or comprehend the
meaning of the signal. Audible devices, such as horns and
bells, can have different tonal patterns and frequencies. It is
the property owner's responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm
signals and instruct them on the proper reaction to alarm sig-
nals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat-
ible with the control panel. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem-
ises to a central monitoring station may be out of service or tem-
porarily disabled. For added protection against telephone line
failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFPA 72 shall be fol-
lowed. Environments with large amounts of dust, dirt, or high air
velocity require more frequent maintenance. A maintenance
agreement should be arranged through the local manufacturer's
representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be per-
formed by authorized professional life safety system installers
only. Adequate written records of all inspections should be kept.
Limit-D-1-2013

IQ-636X-2 Installation Manual — P/N 52853:K3 9/28/15 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
HARSH™ and NIS™ are trademarks; and Acclimate®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®, Intelligent FAAST®,
NOTIFIER®, ONYX®, ONYXWorks®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. AUTOPULSE™ is a trademark of
Tyco Fire Products LP. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. The Chrome™ browser is a trademark of Google
Inc.
©2015. All rights reserved. Unauthorized use of this document is strictly prohibited.

4IQ-636X-2 Installation Manual — P/N 52853:K3 9/28/15
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our cus-
tomers, we make frequent upgrades to the embedded software in our products. To ensure that you are
installing and programming the latest features, we strongly recommend that you download the most cur-
rent version of software for each product prior to commissioning any system. Contact Technical Support
with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or
suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.T[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues,
please contact Technical Services.

IQ-636X-2 Installation Manual — P/N 52853:K3 9/28/15 5
Table of Contents
Section 1: About This Manual.................................................................................................7
1.1: Standards and Other Documents....................................................................................................................7
1.2: UL 864 Compliance.......................................................................................................................................8
1.2.1: Products Subject to AHJ Approval......................................................................................................8
1.3: Related Documents........................................................................................................................................8
1.4: Cautions and Warnings ..................................................................................................................................9
Section 2: System Overview..................................................................................................10
2.1: System Description......................................................................................................................................10
2.1.1: Standard Features ..............................................................................................................................10
2.1.2: Options ..............................................................................................................................................11
2.1.3: System Limitations ............................................................................................................................11
2.2: System Components ....................................................................................................................................11
2.2.1: Basic Equipment................................................................................................................................11
2.2.2: Control Panel Circuit Board .............................................................................................................12
2.2.3: Main Power Supply (CPS-24/E) .......................................................................................................12
2.2.4: Circuit Board Components ................................................................................................................13
2.3: System Cabinets...........................................................................................................................................15
2.4: Compatible Equipment ...............................................................................................................................16
Section 3: Installation............................................................................................................. 18
3.1: Preparing for Installation .............................................................................................................................18
3.1.1: Standards and Codes..........................................................................................................................18
3.2: Installation Checklist ...................................................................................................................................19
3.3: Mounting a Cabinet .....................................................................................................................................19
3.4: Laying Out Equipment in Cabinet and Chassis ...........................................................................................20
3.5: Installing the Control Panel .........................................................................................................................24
3.5.1: Control Panel Circuit Board & Keypad/Display Unit .......................................................................24
3.5.2: Using AutoPulse-NCA-2 as Primary Display ...................................................................................25
3.6: Mounting Option Boards .............................................................................................................................26
3.6.1: Option Boards in the IQ-636X-2/E Chassis ......................................................................................26
3.6.2: Option Boards in CHS-4L .................................................................................................................27
3.6.3: Option Boards on BMP-1 in Dress Panels ........................................................................................28
3.6.4: Transmitter Module TM-4.................................................................................................................29
3.6.5: Loop Expander Module.....................................................................................................................29
3.7: Connecting the Power Cables......................................................................................................................30
3.7.1: Overview ...........................................................................................................................................30
3.7.2: Connecting the Control Panel to AC Power......................................................................................31
3.7.3: Checking AC Power ..........................................................................................................................31
3.7.4: Installing and Connecting the Batteries ............................................................................................32
3.7.5: External DC Power Output Connections...........................................................................................32
3.7.6: Accessories DC Power Output Connections .....................................................................................33
3.8: NAC Connections and Releasing Circuits...................................................................................................34
3.9: Output Relay Connections...........................................................................................................................35
3.10: Backup-Alarm Switches ...........................................................................................................................35
3.11: UL Power-limited Wiring Requirements...................................................................................................36
3.11.1: Labeling Modules and Circuits........................................................................................................37
3.12: Installing EIA-485 Devices .......................................................................................................................37
3.13: Installing Remote Printers and/or CRT......................................................................................................37
3.13.1: Custom Cable Fabrication ...............................................................................................................37
3.13.2: Installing and Configuring the PRN Series Printer .........................................................................37
3.13.3: Installing and Configuring a Keltron Printer...................................................................................39
3.13.4: Installing and Configuring a CRT-2................................................................................................40
3.13.5: Connecting Multiple Printers, CRTs, or CRT/PRN Combination ..................................................42
3.14: Wiring a Signaling Line Circuit (SLC)......................................................................................................42

Table of Contents
6IQ-636X-2 Installation Manual — P/N 52853:K3 9/28/15
3.15: Connecting a PC for Off-Line Programming.............................................................................................43
Section 4: Applications .......................................................................................................... 44
4.1: Overview......................................................................................................................................................44
4.2: Devices Requiring External Power Supervision..........................................................................................44
4.3: NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit) ..................................45
4.4: Central Station Fire Alarm System Canadian Requirements.......................................................................47
4.5: NFPA 72 Proprietary Fire Alarm Systems...................................................................................................47
4.6: Fire/Security Applications ..........................................................................................................................48
4.6.1: General Operation..............................................................................................................................48
4.6.2: Installing a Security Tamper Switch..................................................................................................48
4.6.3: Receiving Unit ...................................................................................................................................49
4.6.4: Programming .....................................................................................................................................49
4.6.5: Wiring for Proprietary Security Alarm Applications ........................................................................49
4.7: Releasing Applications ................................................................................................................................50
4.7.1: Overview............................................................................................................................................50
4.7.2: Programming .....................................................................................................................................51
4.7.3: Connecting a Releasing Device to the Control Panel........................................................................51
4.7.4: Connecting a Releasing Device to the FCM-1 Module.....................................................................53
4.7.5: Connecting Releasing Devices to the FCM-1-REL Control Module................................................55
4.7.6: Connecting an NBG-12LRA Agent Release-Abort Station ..............................................................56
Section 5: Testing the System .............................................................................................. 57
5.1: Acceptance Test ...........................................................................................................................................57
5.2: Periodic Testing and Service........................................................................................................................57
5.3: Operational Checks......................................................................................................................................57
5.4: Battery Checks and Maintenance.................................................................................................................58
Appendix A: Power Supply Calculations ............................................................................. 59
A.1: Calculating AC Branch Circuit Current......................................................................................................59
A.2: Calculating the System Current Draws ......................................................................................................59
A.2.1: Calculating the Maximum Secondary Power Fire Alarm Current Draw..........................................61
A.3: Calculating the Battery Requirements ........................................................................................................63
A.3.1: Calculating the Battery Capacity ......................................................................................................63
A.3.2: Calculating the Battery Size .............................................................................................................64
Appendix B: Electrical Specifications .................................................................................. 65
B.1: Electrical Specifications..............................................................................................................................65
B.2: Wire Requirements......................................................................................................................................67
Appendix C: Canadian Applications..................................................................................... 69
C.1: Standalone Application ...............................................................................................................................69
C.1.1: IQ-636X-2/E with KDM-R2.............................................................................................................69
C.1.2: IQ-636X-2/E with AutoPulse-NCA-2 ..............................................................................................69
C.2: Manual Controls..........................................................................................................................................69
C.3: Automatic Alarm Signal Silence.................................................................................................................69
C.4: Annunciator Applications ...........................................................................................................................69
C.5: Releasing Devices .......................................................................................................................................69

IQ-636X-2/E Installation Manual — P/N 52853:K3 9/28/15 7
Section 1: About This Manual
1.1 Standards and Other Documents
This Fire Alarm Control Panel complies with the following NFPA standards:
•NFPA12CO
2Extinguishing Systems
• NFPA 12A Halon 1301 Extinguishing Systems
• NFPA 13 Sprinkler Systems
• NFPA 15 Water Spray Systems
• NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
• NFPA 17 Dry Chemical Extinguishing Systems
• NFPA 17A Wet Chemical Extinguishing Systems
• NFPA 72 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected
Premises Unit (requires Notifier UDACT/UDACT-2).
• NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems.
• NFPA 72 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires TM-4).
• NFPA 72 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
• NFPA 72 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected
Premises Unit).
• NFPA 2001 Clean Agent Fire Extinguishing Systems
The installer should be familiar with the following documents and standards:
• NFPA 72 Initiating Devices for Fire Alarm Systems
• NFPA 72 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 1076 Proprietary Burglar Alarm Systems
• UL 2017 Standard for General-Purpose Signaling Devices and Systems
• UL 2572 Standard for Mass Notification Systems
• UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
• Standard CAN/ULC-S527-M99
• CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
• EIA-485 and EIA-232 Serial Interface Standards
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction

8IQ-636X-2/E Installation Manual — P/N 52853:K3 9/28/15
About This Manual UL 864 Compliance
1.2 UL 864 Compliance
1.2.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in
retrofit applications. Operation of the IQ-636X-2/E with products not tested for UL 864 9th Edition
has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864.
These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
• For a complete list of all peripherals that can be used with this fire alarm control panel (FACP),
and which of those peripherals have not received UL 864, 9th Edition certification and may
only be used in retrofit applications, see Section 2.4, “Compatible Equipment”, on page 16.
1.3 Related Documents
Table 1.1 below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-ANS) provides the current
document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable) Document Number
(Part no. if applicable)
Device Compatibility Document 50054
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
(Part no. if applicable)
IQ-636X-2 Installation, Operations, and Programming Manuals 52853, 52854, 52855
AutoPulse SLC Wiring Manual 52184 (432780)
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming Utility Document Number
(Part no. if applicable)
VeriFire® Tools CD help file AP-TCD
Cabinets & Chassis Document Number
(Part no. if applicable)
CAB-3/CAB-4 Series Cabinet Installation Document 15330
Battery/Peripherals Enclosure Installation Document 50295
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
(Part no. if applicable)
ACPS-2406 Installation Manual 51304
ACPS-610 Installation Manual 53018
APS-6R Instruction Manual 50702
APS2-6R Instruction Manual 53232
CHG-120 Battery Charger Manual 50641
FCPS-24 Field Charger/Power Supply Manual 50059
FCPS-24S6/FCPS-24S8 Field Charger/Power Supply Manual 51977
Table 1.1 Reference Documentation (1 of 2)

IQ-636X-2/E Installation Manual — P/N 52853:K3 9/28/15 9
Cautions and Warnings About This Manual
1.4 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
AutoPulse-NCA-2 Network Control Annunciator Manual 52857
ANSUL-NCA Network Control Annunciator Manual 52185 (432781)
System Components Document Number
(Part no. if applicable)
Annunciator Control System Manual 15842
FDU-80/FDU-80G Remote Annunciator Manual 51264/52707
LCD-80 Liquid Crystal Display Remote Annunciator 15037
LCD2-80 Liquid Crystal Display Remote Annunciator 53242
LDM Series Lamp Driver Annunciator Manual 15885
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
DPI-232 Direct Panel Interface Manual 51499
TM-4 Installation Document (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050
UDACT-2 Manual (Universal Digital Alarm Communicator/Transmitter) 54089
UDACT-2 Listing Document (Universal Digital Alarm Communicator/Transmitter) 54089LD
RA100Z Remote LED Annunciator Installation Document I56-0508
XP Transponder Manual 15888
XP10-M Installation Document I56-1803
XP5 Series Manual 50786
XP6-C Installation Document I56-1805
XP6-MA Installation Document I56-1806
XP6-R Installation Document I56-1804
Table 1.1 Reference Documentation (2 of 2)
!
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment
damage.
!
WARNING:
Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.

10 IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15
Section 2: System Overview
2.1 System Description
The IQ-636X-2/E control panel is a modular, intelligent fire alarm control panel (FACP) with an
extensive list of powerful features. The control panel uses the CPS-24/E integral power supply with
battery charger. This is combined with a mounting chassis and cabinet to create a complete fire
alarm control system. The panel supports FlashScan® protocol. A single SLC loop is supported
with the basic equipment package; a second SLC loop can be added by attaching an optional loop
expander module (LEM-320).
Modular devices mount to the chassis to provide additional output circuits. Five cabinet options are
available for enclosing system components; each is available in red or black.
The control panel has the capacity for installing up to 636 addressable points; 159 detectors and
159 monitor/control modules per SLC (Signaling Line Circuit).
2.1.1 Standard Features
• Uses the VIEW® early warning fire detection and the FlashScan or Classic Loop Interface
Protocol (CLIP) families of detectors and modules
• Integral power supply with battery charger
• Four standard Notification Appliance Circuits (NAC), Class A or B
• Alarm, Trouble, Supervisory and Security relays
• Support for 32 annunciator addresses, with 10 special annunciator groups
• Supports Style 4, Style 6, Style 7 SLC loops
• Connections to easily mount an expander board to add a second SLC loop
• Releasing service using on-board NACs or FCM-1 modules
• Logic Equations
• Display scroll selection
• Alarm verification supervisory indication (NYC)
• Supervisory duct detectors
• Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms
• Battery charger supports 18 to 200 amp hour sealed lead-acid batteries
• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
• EIA-232 connections for printer, CRT or printer/CRT
• Autoprogram feature for faster programming of new devices
• The control panel provides 6 amps of usable output power in an alarm condition; it provides
3 amps of usable output power in normal or continuous operating conditions
• Diagnostic LEDs and switches
• Ground fault detection (0 ohm impedance)
• Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
• Disconnect of deeply-discharged battery (low battery disconnect)
• Programmable for strobe synchronization
• Mass Notification System compatible

IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15 11
System Components System Overview
2.1.2 Options
Refer to Section 2.4 “Compatible Equipment” for other peripherals listed for use with this panel.
• QWERTY silicone-rubber keypad with a 2x40 LCD display and eight indicator LEDs
• Optional LEM-320 provides a second SLC loop that is electrically identical to the one on the
main board
• Optional devices include: UDACT/UDACT-2 Universal Digital Alarm
Communicator/Transmitter and ACM-8R remote relay module to increase point capacity.
• Optional annunciators connected through the EIA-485 interface allow remote system
monitoring.
2.1.3 System Limitations
System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries). (Note that batteries larger than
26 AH will require a separate battery backbox.)
2.2 System Components
2.2.1 Basic Equipment
A basic IQ-636X-2/E system has the following components:
1. The control panel with integral power supply. IQ636X-CPU2 (120V operation) or IQ636X-
CPU2E (240V operation) is the “control panel” itself and the heart of the system; it ships with
a grounding cable, battery interconnect cables, and document kit. It includes power supply
CPS-24/E, mounted directly on the IQ636X-CPU2/E.
NOTE: The CPS-24/E is an integral part of the IQ636X-CPU2/E and is not available separately.
2. One or more chassis. The IQ-636X-2/E chassis (included with the CPU) mounts the IQ636X-
CPU2/IQ636X-CPU2E and peripherals. Mount additional rows of equipment in a compatible
chassis selected from Table 3.3 on page 23.
3. Optional: A primary display. Generally this is a KDM-R2 keypad/display behind a DP-DISP2
or ADP2-640 dress panel. For information on using AutoPulse-NCA-2 as primary display
instead of KDM-R2, see Section 3.5.2 “Using AutoPulse-NCA-2 as Primary Display” and the
AutoPulse-NCA-2 Manual.
4. A backbox and door:
SBB-A4 and AP-DR-A4 (one row of equipment) or
SBB-B4 and AP-DR-B4 (two rows of equipment) or
SBB-C4 and AP-DR-C4 (three rows of equipment) or
SBB-D4 and AP-DR-D4 (four rows of equipment)
(For a solid-metal door add “B” to the part number; for a red door add “R”.)
5. A battery dress panel AP-BP2-4 is required.
6. Batteries (Refer to Appendix A.3 “Calculating the Battery Requirements” for system current-
draw calculations; CAB-4 series backboxes holds batteries up to 26 AH maximum.)
Refer to Section 2.4, “Compatible Equipment” for other peripherals listed for use with this FACP.

12 IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15
System Overview System Components
2.2.2 Control Panel Circuit Board
The control panel electronics are contained on one printed circuit board that incorporates a
signaling line circuit (SLC) and the central processing unit (CPU). The built-in power supply
includes an integral battery charger. A keypad/display unit can be installed over the power supply;
see Figure 2.1. Wiring connections and system components are detailed in Figures 2.2 and 2.3.
Figure 2.1 IQ-636X-2/E Control Panel with Optional Keypad/Display Unit Installed
2.2.3 Main Power Supply (CPS-24/E)
The main power supply is an integral part of the IQ-636X-2/E and mounts directly over the control
panel’s circuit board. It provides a total of 3 A (6 A in alarm) and contains an integral battery
charger. This can be used for many functions including:
• Powering the IQ-636X-2/E
• Powering a variety of UL-listed 24 VDC notification appliances from four built-in NAC
outputs
• Providing up to 1.25 A of resettable power for four-wire smoke detectors
• Providing up to 1.25 A of non-resettable power for external devices such as the TM-4
Transmitter Module.
• Providing auxiliary 24 VDC power @ 0.5A and 5 VDC power @ 0.15A.
• Fuse: 8 amps, 250 V, 5 x 20 mm, Fast-Acting, ceramic, p/n 12117.
When AC Power is lost, the deeply-discharged battery cutoff protection will be invoked at 17 volts.
The power supply will be disconnected from the batteries. The power supply’s normal operation
will be restored when AC power returns.
See Figure 2.2, “IQ636X-CPU2/IQ636X-CPU2E and Power-Supply: Wiring Connections” and
Figure 2.3, “IQ636X-CPU2/IQ636X-CPU2E and Power-Supply: Jumpers, LEDs and Switches” for
details.
CPU2-640-assyfront.wmf
DP-DISP2.wmf
Displayed
Behind DP-
DISP2
Mounted in
IQ-636X-2/E
Chassis
(with no
peripherals)

IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15 13
System Components System Overview
2.2.4 Circuit Board Components
The following two figures illustrate the location of the various connections, switches, jumpers and
LEDs on the IQ636X-CPU2/IQ636X-CPU2E and its power supply. Figure 2.2 shows wiring
connections; Figure 2.3 shows jumpers, LEDs and switches. See Section 3 “Installation” for larger
images and more details. (Larger images are referenced on these drawings.)
TB13 - SLC Loop
#1 (supervised,
power-limited)
(Figure 3.27)
TB11 - EIA-485 ACS Mode Connection (supervised)
TB10 - DC Power
(24 VDC power-limited)
Resettable
Non-resettable
(See Figure 3.15 on page 32) TB12 - EIA-232 Printer Connection (Figures 3.23 & 3.24)
TB12 - EIA-232 PC/Terminal Connection (CRT)
(Figure 3.25)
J1 - Network/Service Connection (NUP)
(power-limited, supervised)
J2 - USB A VeriFire Tools Connection
J3 - USB B VeriFire Tools Connection
TB8 - NAC#2
All NAC Circuits: power-
limited, supervised
(Figure 3.19 on page 35)
TB9 - NAC#1
TB7 - NAC#3
TB6 - NAC#4
Output Relays - power-limited only if connected to a power-
limited source. (See Section 3.9 for details.)
TB5 -
Supervisory Relay
Security Relay
TB4 -
Alarm Relay
Trouble Relay
J4 - LEM-320 Connector
for (SLC Loop #2)
J5 - Security Tamper Switch
J6 - Auxiliary Trouble Input
J7 - KDM-R2
Connection
CPU2640-KAPS-2.wmf
Figure 2.2 IQ636X-CPU2/IQ636X-CPU2E and Power-Supply: Wiring Connections
TB3 - Battery Connection
(over-current protected, non-power-limited)
TB1 - AC Power Connection (non-
power-limited)
Hot
Neutral
Earth Ground
TB2 - Secondary Power Auxiliary Outputs
(power-limited)

14 IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15
System Overview System Components
NAC
LEDs
Disable - Enable Switches for
Backup Alarm (Figure 3.10)
LED10 – SLC Loop 1
Ground Fault LED
LED9 – SLC Loop 2
Ground Fault LED
LED5 - Supervisory LED
LED7 - Pre-Alarm LED
LED6 - Security LED
LED3 - Point Disabled LED
LED2 - Signals Silenced LED
LED4 - System Trouble LED
LED8 - Fire Alarm LED
LED1 - Power-on LED (AC or battery)
System Switches for No-
Keyboard Operation
SW5 - Acknowledge
SW6 - Silence
SW7 - Reset
CPU2640-KAPS-2.wmf, CPU2-640-LEDs.wmf
JP1 - Ground Fault
Jumper (SLC#1)
F4 - AC Fuse
SW1 - Ground Fault Detection Enable/Disable
LED3 - Earth Fault LED (general board ground fault)
Figure 2.3 IQ636X-CPU2/IQ636X-CPU2E and Power-Supply: Jumpers, LEDs and Switches
LED5 - +24V Aux LED
LED4 - AC Power LED
LED6 - +5V Aux LED
LED1 - Logic Power LED
LED2 - Trouble LED

IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15 15
System Cabinets System Overview
2.3 System Cabinets
The control panel and modules are installed in a CAB-4 series backbox . There are four different
sizes available, holding from one to four rows of equipment plus batteries (up to two 26 AH
batteries). Backboxes are ordered separately from doors. The doors can be mounted on the left or
the right side of the cabinet; reversible hinges are provided so that this choice can be made in the
field. Doors open a full 180 degrees and have locks. Mounting methods include surface-mounting
or semi-flush mounting on a wall between 16 inch (40.64 cm) on-center studs. A trim ring option is
available for semi-flush mounting.
External measurements for each backbox are provided below; door dimensions are larger. Refer to
CAB-3/CAB-4 Series Cabinet Installation Document (shipped with the cabinet) for specific
mounting drawings and door dimensions.
For details on mounting options within the cabinet, see Section 3.4, “Laying Out Equipment in
Cabinet and Chassis”.
A-size backbox
(one row)
24.00 in (60.96 cm) wide
20.00 in (50.8 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-A4
Optional trim ring TR-A4
Opening: 24.062 in (61.118 cm) wide;
20.062 in (50.881 cm) tall.
Molding width: 1.375 in (3.493 cm)
B-size backbox
(two rows)
24.00 in (60.96 cm) wide
28.5 in (72.39 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-B4
Optional trim ring TR-B4
Opening: 24.062 in (61.118 cm) wide;
28.562 in (72.548 cm) tall.
Molding width: 1.375 in (3.493 cm)
C-size backbox
(three rows)
24.00 in (60.96 cm) wide
37.125 in (94.297 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-C4
Optional trim ring TR-C4
Opening: 24.062 in (61.118 cm) wide;
37.187 in (94.455 cm) tall.
Molding width: 1.375 in (3.493 cm)
D-size backbox
(four rows)
24.00 in (60.96 cm) wide
45.75 in (1162.05 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-D4
Optional trim ring TR-D4
Opening: 24.062 in (61.118 cm) wide;
45.812 in (114.775 cm) tall.
Molding width: 1.375 in (3.493 cm)
Trim Rings: When using trim rings, mount backbox with at least 1 inch (2.54 cm) between wall surface and
front of backbox, to allow door to open fully past the trim ring.
Table 2.1 Backbox Measurements

16 IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15
System Overview Compatible Equipment
2.4 Compatible Equipment
These are the most common devices at time of publishing; the most complete list of compatible
intelligent SLC loop devices is provided in the AutoPulse SLC Wiring Manual; for conventional
non-addressable equipment see the Device Compatibility Document. These devices are UL and
ULC listed unless marked otherwise (in parentheses next to the product). For products
documented separately, see Section 1.3 “Related Documents”.
AutoPulse and Notifier Compatible Equipment
NOTE: Products marked with a checkmark have not received UL 864 9th Edition certification
and may only be used in retrofit applications.
Electronic Equipment
ACM-24AT Annunciator Control Module
ACM-48A Annunciator Control Module
ACM-8R Annunciator Control Module
ACPS-610 Addressable Charger/Power Supply
APS2-6R Auxiliary Power Supply
AEM-24AT Annunciator Expander Module
AEM-48A Annunciator Expander Module
AKS-1Annunciator Key Switch
BAT-12120 Battery 12-volt, 12 amp-hour
BAT-12180 Battery 12-volt, 18 amp-hour
BAT-12250 Battery 12-volt, 25 amp-hour
BAT-12260 Battery 12-volt, 26 amp-hour
BAT-12550 Battery 12-volt, 55 amp-hour
BAT-12600 Battery 12-volt, 60 amp-hour
BX-501 Intelligent Detectors/Sensors Base
B501 Intelligent base
B501BH Sounder base
B501BH-2 Sounder base, steady tone
B501BHT-2 Sounder base, temporal tone
B210LP/A Intelligent detector base
CCM-1 Communication Converter Module
CMX-1 Addressable Control Module
CMX-2 Addressable Control Module
IQ636-CPU2/E Control Panel Circuit Board
CPX-551 Ionization Smoke Detector
CPX-751 Intelligent Ionization Smoke Detector
CRT-2 Video Display Monitor with Keyboard
DPI-232 Direct Panel Interface
FCM-1 NAC Module
FCM-1-REL Control Module
FCPS-24S6/S8 Field Charger Power Supply
FDX-551 Intelligent Thermal Sensor
FDU-80G Remote Fire Annunciator
FMM-1 Monitor Module
FMM-101 Mini Monitor Module
FSB-200S Single-ended beam smoke detector with
sensitivity testing
FSB-200 Single-ended beam smoke detector.
FSD-751P Photoelectric Duct Detector
FSD-751RP Photoelectric Duct Detector with alarm relay
FSD-751PL Low-flow Duct Detector
FSD-751RPL Low-flow Duct Detector with alarm relay
FSP-851R/DNR Remote Test Capable Photoelectric Smoke
Detector
FDRM-1 Dual Monitor/Dual Relay
DHX-501, DHX-502 Duct Detectors
FSI-751, FSI-851 Ion Detector
Acclimate ™ FAPT-751, FAPT-851 Combination
Photoelectric/Heat Detector
FSH-751 HARSH™ Smoke Detector
HPX-751 Intelligent HARSH™ Detector
FSL-751 VIEW® Low Profile Laser Detector
FSM-101 Pull Station Monitor Module
FRM-1 Relay Module
FSP-751, FSP-851 Photo Detector
FSP-751T, FSP-851T Photo/Thermal Detector
FST-751, FST-851 Thermal Detector
FST-751R, FST-851R Thermal Detector (rate of rise)
FST-851H High Temperature Detector
FZM-1 Monitor and Zone Interface Module
FDM-1 Dual Monitor Module
ISO-X Loop Fault Isolator Module
ISO-6/A Loop Fault Isolator Module
KDM-R2 Keypad/Display Unit
LCD-80 Liquid Crystal Display Annunciator
LCD2-80 Liquid Crystal Display Annunciator
LDM-32 Lamp Driver Module
LDM-E32 Lamp Driver Module
LDM-R32 Lamp Driver Module
LEM-320/A Loop Expander Module
LPX-751 VIEW® Low Profile Laser Detector (CLIP)
AP-NBG-12LR/NBG-12LRA Agent Release-Abort Station
NBG-12 Series Manual Pull Station
NBG-12LX Addressable Manual Pull Station
AP-NCA-2 Network Control Annunciator
AWS-3 NFN Webserver
N-ELR Assortment ELR Pack with Mounting Plate
PRN-6 80-Column Printer
PRN-7 80-Column Printer
R-120 120 Ohm End-of-Line Resistor
R-2.2K 2.2K End-of-Line Resistor
R-27K 27K End-of-Line Resistor
R-470 470 End-of-Line Resistor
R-47K 47K End-of-Line Resistor
A77-716B End-of-Line Resistor Assembly
RPT-485F EIA-485 Repeater (Fiber)
RPT-485W EIA-485 Repeater (Wire)
RPT-485WF EIA-485 Repeater (Wire/Fiber)
SDX-551 Intelligent Photoelectric Detector
SDX-751 Intelligent Photoelectric Detector
SLC-IM Signaling Line Control Integration
STS-1 Security Tamper Switch
TM-4 Transmitter Module
UDACT Universal Digital Alarm Communicator Transmitter
UDACT-2 Universal Digital Alarm Communicator Transmitter
XP6-C/A Supervised Control Module
XP6-R Six Relay Control Module
XP6-MA/A Six Zone Interface Module
XP10-M/A Ten Input Monitor Module
DNR/W/A Intelligent Non-Relay Photoelectric Duct Detector
Backboxes, Chassis, and Dress Panels, etc.
ABF-1B Annunciator Flush Box ABF-1DB Annunciator Flush Box with Door
!
WARNING: UL 9th Edition Compliance
This product has been certified to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of the IQ-636X-2/E with products
not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or
the latest edition of UL 864. These applications will require the approval of the local Authority Having
Jurisdiction (AHJ).
Peripheral devices in the second list were listed under UL 8th Edition and may only be used in retrofit
applications (see Section 1.2, “UL 864 Compliance”, on page 8).

IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15 17
Compatible Equipment System Overview
ABF-2B Annunciator Flush Box
ABF-2DB Annunciator Flush Box with Door
ABF-4B Annunciator Flush Box
ABM-16AT Annunciator Blank Module
ABM-32A Annunciator Module Blank
ABS-1TB Annunciator Surface Box
ABS-1B Annunciator Surface Box
ABS-2B Annunciator Surface Box
ABS-4D Annunciator Surface Box
ABS-8RB Annunciator Backbox for ACM-8R
ADP2-640 Dress Panel: NFS2-640/E in lower row
ADP-4B Annunciator Dress Panel
BMP-1 Blank Module Plate
AP-BP2-4Battery Dress Plate
CAB-4 Series Doors (Black unless “R” is added to the
P/N. Add B to the P/N for blank door)
AP-DR-A4 A-sized door, 1 row of equipment
AP-DR-B4 B-sized door, 2 rows of equipment
AP-DR-C4 C-sized door, 3 rows of equipment
DR-D4 D-sized door, 4 rows of equipment
CAB-4 Series Backboxes (Black unless “R” is added to
the P/N.)
SBB-A4 A-sized backbox
SBB-B4 B-sized backbox
SBB-C4 C-sized backbox
SBB-D4 D-sized backbox
CAB-4 Series Trim Rings (Black unless “R” is added to
the P/N)
TR-A4 A-sized trim ring
TR-B4 B-sized trim ring
TR-C4 C-sized trim ring
TR-D4 D-sized trim ring
CA-1 Audio Chassis
CA-2 Audio Chassis
CHS-4L Low-Profile Chassis
CHS-4, CHS-4N Chassis for 4 Option Boards
NFS2-640 Chassis for 1st row (included in basic equipment
package)
DP-1B Blank Dress Plate
DPA-1 Dress Plate
DPA-2B Dress Plate
DPA-1A4 Dress Plate
DP-DISP2 Dress Panel: NFS2-640/E in top row
DPDW-1B Double Well Dress Plate
DPSW-1B Single Well Dress Plate
NFS-LBBR Red Battery Box
VP-2B 2” Filler Dress Plate
System Sensor Equipment
A2143-00 End of Line Resistor Assembly
EOLR-1 End-of-Line Resistor Assembly
FSB-200, FSB-200S Beam Detectors
Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous
Editions of UL 864
NOTE: The products in this list have not
received UL 864 9th Edition certification and
may only be used in retrofit applications (see
Section 1.2, “UL 864 Compliance”, on page 8).
ACM-16AT Annunciator Control Module
ACM-32A Annunciator Control Module
ACPS-2406 Auxiliary Charger/Power Supply
AEM-16AT Annunciator Expander Module
AEM-32A Annunciator Expander Module
ANSUL-NCA Network Control Annunciator
APS-6R Auxiliary Power Supply
BGX-101L Addressable Manual Pull Station
CHG-120 Battery Charger
FCPS-24 Field Charger Power Supply
IPX-751 Advanced Multi-Sensor Intelligent Detector
P-40 Keltron Printer
PRN-4, PRN-5 80-Column Printers
P40-KITB Dress plate for Keltron Printer
RA400 Remote Annunciator
RA400Z Remote Annunciator with diode
XPC-8 Transponder Control Module
XPDP Transponder Dress Panel
XPM-8 Transponder Monitor Module
XPM-8L Transponder Monitor Module
XPP-1 Transponder Processor
XPR-8 Transponder Relay Module
XP5-C Transponder Control Module
XP5-M Transponder Monitor Module

18 IQ-636X-2/E Installation Manual — P/N 52853:K3 9/28/15
Section 3: Installation
3.1 Preparing for Installation
Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate
temperature. The area should be readily accessible with sufficient room to easily install and
maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors
needed for all devices and find the appropriate knockouts. (Refer to Section 3.11 “UL Power-
limited Wiring Requirements” for selection guidelines.)
Before installing the fire alarm system, read the following:
• Review the installation precautions at the front of this manual, including temperature and
humidity limits for the system (Page 3).
• All wiring must comply with the National and Local codes for fire alarm systems.
• Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a
separate battery cabinet; this space is for internal battery installation.
• Review installation instructions in Section 3.2 “Installation Checklist”.
3.1.1 Standards and Codes
In addition, installers should be familiar with the following standards and codes:
• NEC Article 300 Wiring Methods.
• NEC Article 760 Fire Protective Signaling Systems.
• Applicable Local and State Building Codes.
• Requirements of the Local Authority Having Jurisdiction.
• C22.1-98 The Canadian Electrical Code, Part 1.
• CAN/ULC-S5524-01 Standard for the Installation of Fire Alarm Systems.
!
CAUTION:
Make sure to install system components in the sequence listed below. Failure to do so can damage
the control panel and other system components.
!
WARNING:
This system contains static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits. Use static-suppressive packaging to protect electronic assemblies
removed from the unit.

IQ-636X-2/E Installation Manual — P/N 52853:K3 9/28/15 19
Installation Checklist Installation
3.2 Installation Checklist
Table 3.1 provides an installation checklist for installing, wiring, and testing the IQ-636X-2/E
system. It has references to installation information included in manuals listed in Section 1.3
“Related Documents”.
3.3 Mounting a Cabinet
This section provides instructions for mounting a CAB-4 Series backbox to a wall. Follow these
guidelines when mounting the backbox:
• Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the
finished floor.
• Access to the cabinet shall be provided in accordance with NFPA 90, article 110.33.
• Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.3 “System
Cabinets”.)
• Use the four holes in the back surface of the backbox to provide secure mounting. (See
Figure 3.1.)
Seq Task Refer to
1. Mount the cabinet backbox to the wall. Section 3.3 “Mounting a Cabinet”
2. Install hinges for door CAB-3/CAB-4 Series Cabinet Installation Document
3. Install all required chassis in cabinet. Section 3.5 “Installing the Control Panel”
4. Install control panel onto chassis. Section 3.5.1 “Control Panel Circuit Board &
Keypad/Display Unit”
5. Optional: Install auxiliary power supply and/or external
battery charger
Auxiliary power manuals
6. Connect AC wiring, place batteries into backbox without
connecting them, and run cable to optional power supplies,
DC power outputs, NACs, and relays.
CAUTION: Do not apply AC or DC power at this time.
Section 3.7 “Connecting the Power Cables”
7. Set switches for backup alarm (SW1-SW4). Section 3.10 “Backup-Alarm Switches”
8. Optional: Install option boards, and annunciators, Section 3.6, “Mounting Option Boards”, the relevant
annunciator/ manual,
9. Optional: Install output devices such as a printer, or CRT
terminal.
Section 3.13 “Installing Remote Printers and/or CRT”
10. Optional: Install AutoPulse-NCA-2. AutoPulse-NCA-2 Manual,
11. Secure any unused mounting holes in control panel
circuit board.
Figure 3.6
12. Wire the Signaling Line Circuits. Section 3.14 “Wiring a Signaling Line Circuit (SLC)”
13. Terminate wire shielding as instructed. SLC Wiring Manual
14. Apply AC power to the control panel by placing the external circuit breaker to the ON position.
Do NOT connect batteries.
15. Check AC power. Table 3.5 in Section 3.7 “Connecting the Power Cables”
16. Connect the batteries using interconnect cable, P/N 75560 and 75561.
17. Install the CAB-4 series door. CAB-3/CAB-4 Series
Cabinet Installation Document
18. Program the control panel. IQ-636X-2/E Programming Manual
19. Field test the system. Section 5 “Testing the System”
Table 3.1 Installation Checklist

20 IQ-636X-2/E Installation Manual — P/N 52853:K3 9/28/15
Installation Laying Out Equipment in Cabinet and Chassis
• Mount the backbox on a surface that is in a clean, dry, vibration-free area.
Follow the instructions below.
1. Mark and pre-drill holes for the top two keyhole mounting bolts (0.25 inch, 0.635 cm). Use
mounting hardware appropriate for the mounting surfaces and weight of loaded cabinet; see
UL 2017 Pull-Test Requirements.
2. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.11
“UL Power-limited Wiring Requirements”.)
3. Using the keyholes, mount the backbox over the two screws.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all
fasteners securely.
6. Feed wires through appropriate knockouts.
7. Install control panel and other components according to Section 3.5 “Installing the Control
Panel” before installing hinges and door according to CAB-3/CAB-4 Series Cabinet
Installation Document.
3.4 Laying Out Equipment in Cabinet and Chassis
The IQ-636X-2/E allows for flexible system design. Backboxes are available to hold up to four
rows of equipment (four chassis), plus batteries. Each chassis has four “slots” -- the basic positions
available side by side on a chassis. The number of modules that can be mounted in each position
depends on the chassis model and the module size.
Follow these guidelines when deciding where to locate equipment in the backbox.
The IQ-636X-2/E control panel and adjacent first-row modules mount in the IQ-636X-2 chassis,
typically installed in the first/top row of the backbox behind DP-DISP2. (Use ADP2-640 if
mounting IQ-636X-2 chassis in a lower row.) IQ-636X-2 chassis holds four layers of equipment,
including the control panel. See Figure 3.3. The primary display (KDM-R2 or AutoPulse-NCA-2)
mounts in front of IQ-636X-2/E.
!
CAUTION:
Unless you are familiar with the placement of components within this backbox, only use the knockout
locations provided for conduit entry.
Keyholes
2 places
Mounting holes
2 places
CAB-4
Series
Backbox,
A-size (one-
row)
nfs640cabinetmountingholes.wmf
CAB-4
Series
Backbox,
D-size
(four-row)
Figure 3.1 Mounting Holes of a Backbox
Table of contents
Other Ansul Control System manuals
Popular Control System manuals by other brands

Lennox
Lennox Harmony II Zone Control System installation instructions

Polar Electro
Polar Electro Connect instructions

Daspi
Daspi DS 301 RX WIFI manual

Rometron
Rometron WEED-IT Quadro user manual

ASA Electronics
ASA Electronics JENSEN JRVCS1 Installation and operation manual

BACA SYSTEMS
BACA SYSTEMS EDGE XL Operation manual