Ansul AUTOPULSE IQ-396X Owner's manual

PROGRAMMING AUTOPULSE®IQ-396X
MANUAL ANALOG
ADDRESSABLE
ALARM/RELEASE
CONTROL SYSTEM
ANSULâ

WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 72-
1993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49OC and at a
relative humidity of 85% RH (non-condensing) at 30O C. However, the useful life
of the system's standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humidity. Therefore, it is
recommended that this system and its peripherals be installed in an environment
with a nominal room temperature of 60-80OF.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.
Fire Alarm System Limitations While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system - typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm control
with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Further-
more, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.
FCC Warning
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-
tions du Canada.
Technical Publishing Document PRECAULG.PM6 7/12/96

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 3
1. Introduction to IQ-396X Programming
2. Program Change
3. Status Change
Disable/Enable .......................................................................................... 21
Detector Sensitivity................................................................................... 22
Clear Verification Counters ...................................................................... 23
Clear the History File................................................................................ 23
Set the Time and Date .............................................................................. 23
Walk Test ................................................................................................... 24
Overview ................................................................................................ 24
What the Control Panel Does in Walk Test............................................. 24
Before Selecting Walk Test ..................................................................... 24
How to do a Walk Test ........................................................................... 25
Finishing a Walk Test .............................................................................. 25
Contents
How to Enter Program Mode ................................................................... 8
Entering a Password ................................................................................. 8
Changing a Password ............................................................................... 8
Clear Programming Information .............................................................. 9
Autoprogram
Point Programming................................................................................... 11
How to modify a point........................................................................... 11
Type Codes for Monitor modules .......................................................... 12
Monitor Module Default Zone Assignment ........................................... 12
Programming a Control Module ............................................................ 13
Control Module Type Codes .................................................................. 13
Programming NAC/Panel Output Circuits.............................................. 13
NAC/Panel Output Circuit Type Codes .................................................. 14
System Defaults...................................................................................... 14
Changing a Password ............................................................................... 15
Changing the System Message .................................................................. 15
Changing a Custom Label......................................................................... 16
Rules for Changing a Custom Label ....................................................... 16
How to change a Custom Label ............................................................. 16
Special Zone Change ................................................................................ 17
Definitions of Special Functions ............................................................ 17
F0 (Presignal) ......................................................................................... 17
F7 (Holiday) ........................................................................................... 18
F8 (Code Type) ...................................................................................... 18
F9 (Pre-Alarm) ........................................................................................ 18
F5-F6 (Time Control Functions) ............................................................ 18
R0-R9 (Releasing Functions) .................................................................. 18
System Function Programming................................................................. 19
Check........................................................................................................ 20
Continued on the next page...
Benefits..................................................................................................... 5
Overview................................................................................................... 5
In this Manual........................................................................................... 5
Conventions and Symbols ........................................................................ 6
Entering information from the Control Panel .......................................... 6
Choosing a programming method ........................................................... 7
Transferring programs between a PC and the Control Panel ................... 7
Using the Programming Keys ................................................................... 7

4AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
Contents
Appendix A: Releasing Applications
Appendix B: Outputs
Overview ................................................................................................. 26
NFPA Standards ....................................................................................... 26
Programming .......................................................................................... 27
Delay Timer ...................................................................................... 27
Abort Timer ...................................................................................... 27
Cross Zoning .................................................................................... 28
Soak Timer (NFPA 16 applications only) .......................................... 28
Special Module Types ....................................................................... 29
Initiating Devices .............................................................................. 29
Warning Sounders ................................................................................... 30
Auxiliary Control Functions .............................................................. 30
ACS Annunciation ............................................................................. 30
Presignal and Positive Alarm Sequence (PAS) ......................................... 31
Presignal .......................................................................................... 31
Positive Alarm Sequence (PAS) ........................................................ 31
Time Control ........................................................................................... 31
Coding .................................................................................................... 31
Appendix C: Nominal Detector Sensitivity Settings
Selecting Pre-Alarm and Alarm Sensitivity .............................................. 32
Required Testing for Detectors Set Below 0.50% .................................... 33

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 5
1. Introduction to IQ-396X Programming
The IQ-396X is an intelligent, field-programmable Fire Alarm Control Panel.
Field-programming the IQ-396X lets you customize the fire alarm system by
selecting and setting program options for output circuits, intelligent/addressable
devices, Notification Appliance Circuit (NAC )circuits, and monitor/control
modules.
This manual contains instructions for programming the IQ-396X from the
control panel keypad. The following diagram outlines the contents of this
manual.
In this Manual
Benefits
Overview
Benefits of IQ-396X programming include the following:
Ease-of-use field-program the control panel without needing special soft-
ware skills.
Autoprogramming Function Automatically detects newly installed, address-
able devices, allowing quicker installation;
Local programming program directly from the control panel keypad to
reduce installation time;
Remote programming input long data entry programming information on a
PC; transfer programming data between a PC and the control panel;
Security use passwords to control access to the control panel and protect
memory; and
80-Character (2x40) Liquid Crystal Display view programming and device
information on the control panel.
This manual contains information for entering programming data to the control
panel using programming keys on the front panel. For details on control panel
operation, refer to the IQ-396X Operations Manual.
Programming
Basics
Introduction
Overview
Benefits
Conventions
AdditionalInformation
Using the control panel
Selectingand entering passwords
Selectinga programmingmethod
ProgrammingScreens
Programming
the IQ-396X
Entering Program Mode
ProgramChange Selections
Clearing control panel memory
Autoprogramming
Programmingpoints
Changinga password
Changing the system message
Programmingzones
Selectingspecialfunctions
Setting system functions
Checkingprogram information
StatusChange Selections
Assigning the password
Disable or enable system points
Setting detector sensitivity
Clear tally counters from memory
Clear the history file
Set the system time and date
Walk test the fire alarm system

6AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
Conventions and Symbols This manual uses conventions and symbols to provide the following
types of information:
!
Note indicates supplementary information.
Warning indicates information about procedures that
could cause error, programming errors, runtime errors, or
equipment damage.
For presentation and printing purposes, this manual uses different
typeface characters, in place of the actual LCD letters that you see
on the panel display.
Entering information from the
Control Panel
The following documents contain more information on some items
discussed in this manual:
This manual uses the following conventions for entering data and
pressing control panel keys:
Additional Information
QWERTY keypad
Programming
keys
Cursor movement
keys
eesuoynehWsihtoDelpmaxE
nitxet<>stekcarbehtepyTtxet1epytotsnaem>1<
ehtfocihpargayeksserP
S
CSEehtsserpotsnaemyek
eltiTtnemucoD
tnemuco
D
ecnerefeR
.oN
LUSNA
N/PtnemucoD
tnemucoDytilibitapmoCeciveDLUSNA45005120814
noitallatsnIX693-QIESLUPOTUA
launaM 10405632914
snoitarepOX693-QIESLUPOTUA
launaM 30405832914
gnimmargorPeniLffO004eriFireV
ytilitU
67305314914

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 7
Using Programming Keys
GG
GG
G
The IQ-396X provides two methods for field-programming the control
panel: using the Autoprogram feature or the VeriFireTM 400 Programming
Utility. The following table lists the benefits of each method:
gnimmargorpsihT
...dohtem
...rofelbatiustsomsi
margorpotuAfoecneinevnocdnadeepS
;ylkciuqenilnolenaplortnocehtgnittup
dna
.noitamrofnignimmargorpgnignahc
004eriFireVgnitidednagnitaercfosnaemtneiciffE
.yrtneatadfotolaeriuqertahtsmargorp
Choosing a Programming
Method
The following table contains definitions for the keys that you use to pro-
gram the control panel.
yeksihtsserPoT
C
.noitamrofnitpeccA
S
gnivastuohtiwnoitarepotsalstrobA
.edommargorPtixeotesuoslA.noitamrofni
L
.dleiftxenehtotrosrucehtevoM
M
.dleifsuoiverpehtotrosrucehtevoM
G
.sdleifatadgnomarosrucehtevoM
Common Programming Keys
Programming Methods
The VeriFire 400 Off Line Programming Utility lets you load or down-
load programs between a personal computer and the control panel. To
use the VeriFire 400, follow these steps:
Transferring programs
between a PC and the
control panel
VeriFire 400
Programming
Utility
TB2
Cable 75267
PC-to-Control Panel Transfer Connections
For detailed installation
information, refer to the
following:
the VeriFire 400 Product
Installation Document.
(Document 50376); and
the VeriFire 400 online
help file.
petSnoitcA
1ehtnotrop232-AIEehtotretupmocelbitapmoc-CPatcennoC
:lenaplortnoc
tropMOCCPehtot)76257N/P(elbacdeilppusehttcennoC)a
.)4MOC1MOC(
)lanimreT/CP(2BTlanimretotelbacehtfodnerehtoehttcennoC)b
ehtno
:swollofsa)noitcennocfoepytehtnognidneped(lenaplortnoc
2.CPehtotnierawtfos004eriFireVehtdaoL
3.ytilitUgnimmargorPeniLffO004eriFireVehtnuR
2BT
)lanimreT/CP(
eriWtceriD
snoitcennoC
medoM
snoitcennoC
XTkcalBneerG
XRneerGkcalB
FERdeRdeR

8AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
2. Program Change
Press <1>. The control panel displays the Enter Password screen.
Changing a Password
Enter Program Mode by pressing <Enter>. The control panel
displays the Program Entry screen:
Enter a password to enter Program Change or Status Change. In
Program Change or Status Change, the control panel does the
following:
activates the trouble relay (TB5 on the MPS-400);
shuts off the panel sounder; and
flashes the System Trouble LED (and cannot be made steady).
For example, if you enter a Program Change password, the control
panel displays the Program Change screen:
The IQ-396X provides two types of selectable passwords: Program
Change and Status Change. Refer to the following table for uses and
the factory-set password for each:
drowssaP
epyt
otdesuyrotcaf
gnittes
margorP
egnahC
)levelhgih(
otedomegnahCmargorPretnE
snoitcnuflenaplortnocmargorp
.sretemarapmetsystesdna
00000
egnahCsutatS
)levelwol(
tesotedomegnahCsutatSretnE
wolekamro,tsetklawretne,emit
.segnahcsutatslevel
11111
Entering a Password
Types of Passwords
For security purposes, you can change your passwords. Do so by
following the instructions in Password Change in the Program
Change section.
Program Entry Screen
1=PROGRAMMING 2=READ STATUS ENTRY
(ESCAPE TO ABORT)
ENTER PROG OR STAT PASSWORD, THEN ENTER.
(ESCAPE TO ABORT)
Enter Password Screen
How to Enter Program
Change
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
If the Password does not work
The control panel displays: Incorrect
Password and a hexadecimal error
code number. Contact the manufac-
turer for assistance.
Program Change Screen

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 9
After accepting all devices, the Program Change screen appears in the
panel display.
For each new device, the Autoprogram option selects and displays
default program values. For example, the following figure shows
Autoprogram default values for a detector:
The Autoprogram option provides the following features:
identifies all installed, addressable devices connected to a Signaling
Line Circuit (SLC);
detects new (unprogrammed) devices and new panel modules;
lets you view, edit, and accept any new devices; and
loads default program information for new devices.
If programming for the first time, the control panel displays a screen
similar to the following:
SLC devices already programmed into control panel memory do not
change and do not appear in the Autoprogram Device Count Screen.
Devices not matching the program (not same SLC address and type)
display in the Autoprogram Device Count Screen. To accept
autoprogrammed devices, press <Enter>. The control panel displays
the following message:
Autoprogram
Clear Programming
Information
0
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
1
The Clear option removes all programming information from control
panel memory. If installing the control panel for the first time, use
Option 0 to clear control panel memory. To do so, follow these steps:
1) From the Program Change screen, press <0> to display the Clear
screen. The control panel prompts for verification.
2) Press <Enter> to clear control panel memory or press <Esc> to exit
the screen without clearing.
dleiFnoitpircseD
:2L,:1Lseludomdna,secived,srotcetedforebmuneht
.poolCLShcaeno
:stuptuOlenaP.stuptuolenapdemmargorpforebmuneht
:slleB)40B-10B(stiucriclleb/CANlenapforebmuneht
.40otlauqesyawla
L1:02 DETS, 02 MODS L2:00 DETS, 00 MODS
PANEL OUTPUTS: 00 BELLS: 04
ACCEPT ALL DEVICES PLEASE WAIT!
Autoprogram Device Count Screen
Autoprogram Default Values for a Detector
PROGRM SMOKE (PHOTO) DETECTOR ADDR 101
ZO3 Z Z Z Z AL:5 PA:0 ** D101
Control-by-Event
(CBE) Equation
Type code
Alarm Threshold
Pre-Alarm level
Multidetector mode
Alarm Verification
2-digit address
Loop number
Continued on the next page...

10 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
If a detector exists in the control panel program, but is missing (no
response from the program), the control panel displays a screen similar to
the following:
To delete the device from memory, press Enter. The next new device
appears in the display.
To keep the device in memory, press <Esc>. The control panel
displays the Program Change screen.
Autoprogram Defaults The following table contains descriptions for the fields that display in the
Autoprogram Default screen.
Autoprogram Default Fields
If using CPX-551 Ion detectors
in a duct application, set the
Alarm Sensitivity level to 1.
dleiFnoitpircseD
)OTOHP(EKOMS ehtfonoitcnufehtsenifedtahtrotcetedehtfoedocepyT
:rotceted
)taeH(golanA
)otohP(ekomS
)noI(ekomS
)resaL(ekomS
)itluM(ekomS
RDDAROTCETED
101
.)10sserdda=10;1pool=1(101:lebalmotsuctluafeD
tnevE-yb-lortnoC
noitauqE)EBC(
:noitcelesenoztluafeD
srotcetedtaeH10enoZ
srotcetednoI20enoZ
)tluafed(srotcetedotohP30enoZ
srotcetedresaL40enoZ
srotceteditluM50enoZ
rofsenozeromruofddasallewsasenozegnahcnacuoY
.EBCsrotcetedhcae
5:LA mralAevitisnestsaeleht9htiw,levelytivitisnesmralAehT
otrefeR.levelmralAevitisnestsomeht1dnalevel
.noitamrofnieromrofCxidneppA
0:AP rebmunagnitteslevelytivitisnesmralA-erPehtswohS
:swollofsa9dna0neewteb
.mralA-erPon0
.levelmralA-erPevitisnestsom1
.levelmralA-erPevitisnestsael9
.noitamrofnieromrofCxidneppAotrefeR
** rotceteditlumrotcetedehtsetacidniot)*(ksiretsatsrifehT
:edom
ehthtiwnoisicedmralas'rotcetedehtsenibmocA
.evobasserddatxen
ehthtiwnoisicedmralas'rotcetedehtsenibmocB
.wolebsserddatxen
txenehthtiwnoisicedmralas'rotcetedehtsenibmocC
.woleb.sserddatxenehtdnaevobasserdda
PROGRM SMOKE (ION) DETECTOR ADDR 133
DEVICE NOT ANSWERING DELETE FR MEM? D133
Type code
2-digit address
SLC Loop number (1 or 2)
D (Detector), M (Module)

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 11
After programming all SLC-connected devices into the system, you can
modify or delete points using the Option 2, Point. From the Program
Change screen, press <2> to display the Point screen:
The Modify Point and Delete Point screens let you edit or delete points
for a detector, module, or output circuit. To select a device, follow these
steps:
You can now modify or delete a point. To modify a point for a detector,
module, or output circuit: press <1> to display the Modify Point screen;
or press <2> to display the Delete Point screen.
How to modify a point
Modify Point screen
Device Address
Enter
AAA,EAAA,E
AAA,EAAA,E
AAA,E
Address (01-99)
The Type Code is used to
change the function of a
point.
Point Programming
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
2
When you select a device, the control panel returns a screen that displays
information about the point. For example, the following figure shows
information for a sample monitor module (M101) on the panel display:
Loop (1=L1; 2=L2)
...tcelesoT...gniwollofehtoD
elbasserddA
rotceteD sserP
H
rotceteddna)2ro1(rebmunpoolehtepyT
)99-1(sserdda
sserP
R
elbasserddA
eludoM sserP
I
eludomehtdna)2ro1(rebmunpoolehtepyT
)99-1(sserdda
sserP
R
tuptuOlenaP
tiucric sserP
J
)8-8(hguorht)1-0(:sserddatiucrictuptuoehtepyT
sserP
R
POINT PROG. 1=MODIFY POINT
2 = DELETE POINT
Delete Point screen
POINT PROG. ENTER: DETECTOR=*,AAA,E
MODULE=#,AAA,E OUTPUT CKT=$,A-A,E
Point Screen
DELETE POINT. ENTER: DETECTOR=*,AAA,E
MODULE=#,AAA,E OUTPUT CKT=$,A-A,E
Continued on the next page...
The Type Code selection blinks, meaning you can press the Next or
Previous keys to scroll through the Type Code selections. Refer to the
table, Monitor Module Type Codes which lists the function for all
Monitor Module Type Codes. You can also do the following:
1) Use the arrow and alphanumeric keys to modify point information,
such as the CBE equation.
2) When finished modifying a point, press <Enter>; then use the Next
and Previous keys to select another point.
PROGRM MONITOR MODULE ADDRESS 101
ZO4 Z Z Z Z M101
Blinking Type Code Selection
2-digit address
SLC Loop number (1 or 2)
D (Detector), M (Module)

12 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
Programming a Point, continued
Type Codes for Monitor
Modules
The following table lists the monitor module address range and the
default zone assignment for each range:
Continued on the next page...
Monitor Module Default Zones
Change default zones for a monitor module as shown in the table,
Autoprogramming Default Fields.
Monitor Module Type Codes
lebaLedoCepyTnoitcnuFlaicepS
rotinoM)tluafed(enon
noitatSlluPenon
tceteDekomSenon
tceteDtaeHsrotcetedlanoitnevnocrotinomotesU
)secaps21(knalB)seilppaedoCepyTrehtoonnehwesu(enon
wolfretaWmralaelbaecnelis-nonasesuac
yrosivrepuStniopyrosivrepusasemoceb
repmaTtniopyrosivrepusasemoceb
eriFnoNtniopmrala-nonlaiceps
trelAdrazaHtniopmrala-nonlaiceps
lortnoCeriFtniopmrala-nonlaiceps
hctiwStrobAenozesaelerehtstroba
esaeleR.naMtrobAsedirrevo
ecneliShctiwsecneliSehtekilsnoitcnuf
teseRmetsyShctiwsteseRehtekilsnoitcnuf
etaucavEhctiwsetavitcAmralAehtekilsnoitcnuf
tibihnISAPlangiserPsedirrevo
noMelbuorTelbuort=trohs
alAralgruBtrohsroneponanomralaytiruceSasesuac
egaP.eleTaeraerifaotgnigapetomerswolla
egaPllaCllAehtnienohpetomeramorfgnigapllaCllAswolla
noitallatsni
yaleDleRnaMyaleddnoces-01htiwesaelerlaunametaitini
tohSdnoceSegrahcsidtnegadnoces,tuptuoesaeleretavitcaer
sySrlknirpS emasnognirotinomyrosivrepusdnawolfretawswolla
eludom
rotinoM.bmoC emasnognirotinomyrosivrepusdnawolfretawswolla
ld
The following table lists Monitor module Type Codes:
Monitor Module Default Zone
Assignment
sserddAeludoMrotinoMtluafeDenoZ
91hguorht1040Z
93hguorht0250Z
95hguorht0460Z
97hguorht0670Z
99hguorht0880Z

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 13
Programming a Point, continued
Programming Control modules is similar to Monitor modules except the
default zone is always set to Zone 00 (General Alarm). The following is a
Programming Output Circuits (four NACs or Panel Output Circuits con-
nected through one of the panel NAC circuits) is like programming Control
Modulesexcept for the Type Code and device address.
Programming NAC/Panel
Output Circuits
The following table contains Control Module Type Codes:
ARelease Ckt is always non-
silenceable.
edoCepyTnoitcnuFlaicepS
lortnoCCANdesivrepuS
yaleRtuptuoyaleR
tiucriClleBCANdesivrepuS
tkCebortSCANdesivrepuS
tiucriCnroHCANdesivrepuS
tkCelbiduACANdesivrepuS
rekaepSCANdesivrepuS
lleBdnEleRCANdesivrepuS
lebalknalbedoCepyTrehtoonnehwesu(CANdesivrepuS
)seilppa
tkCesaeleRrofdesivrepus,detimilrewopnon,tiucriCgnisaeleR
stluafdnuorgdna,strohs,snepo
CLUtkCleR,sneporofdesivrepus,detimilrewop,tiucriCgnisaeleR
stluafdnuorgdna,strohs
CmroF.aeleResaelernopuetarepostcatnoc,tuptuoyaleR
elbiduAleResaelernopudetavitca,CAN
ltCteseRnoNdnammocteseRmetsySybdetceffanu,tuptuoyaleR
enohpeleTtiucricenohpeletdradnatS
The table of Type Codes
contains a comprehensive
list of Type Codes. The
Type Codes that display,
however, depend on the
configuration.
Default parameters for the
Control Module Programming
screen follow:
Switch Inhibit (I) annuncia-
tors in the modules range
cannot activate;
Silenceable (S); and
Walk Test (*) not selected.
The Type Code selection blinks, meaning you can press the Next or Previous
keys to scroll through the Type Code selections. Refer to the table, Control
Module Type Codes. You can also do the following:
1) Use the arrow and alphanumeric keys to modify point information, such
as the CBE equation.
2) When finished modifying a point, press <Enter>; then use the Next and
Previous keys to select another point.
Silenceable (S=selected; *=off)
PROGRM CONTROL MODULE ADDRESS 108
Z00 Z Z Z Z IS * M108
Blinking Type Code Selection
Walk Test Selection (*=off;
W=Walk Test Selected)
Switch Inhibit (I=selected; *=off)
Defaults for the NAC/Panel
Output Circuits Screen include the
following:
Default zone selection is Z00
(general alarm); and
Walk Test (W) is selected.
PROGRM BELL CIRCUIT PANEL CIRCUIT NO. 3
Z00 Z Z Z Z IS W B03
Address of a NAC/Panel Output
Circuit connected through NAC1
(B01), NAC2 (B02), NAC3 (B03),
or NAC4 (B04)
Blinking Type Code Selection
Switch Inhibit (I=selected; *=off)
Silenceable (S=selected; *=off)
Walk Test Selection (*=off;
W=Walk Test Selected)
The Type Code selection blinks, meaning you can press the Next or Previous
keys to scroll through the Type Code selections. Refer to the table, NAC/
Output Circuit Type Codes.
Programming a Control
Module
Control Module Programming Screen
Control Module Type
Codes
Control Module Type Codes

14 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
Programming a Point, continued
NAC/Panel Output Circuit
Type Codes
Type Code selections for NAC/Panel Output Circuits follow:
NAC/Panel Output Circuit Type Codes
edoCepyTnoitcnuFlaicepS
lortnoCCANdesivrepuS
yaleRtuptuoyaleR
tiucriClleBCANdesivrepuS
tkCebortSCANdesivrepuS
tiucriCnroHCANdesivrepuS
tkCelbiduACANdesivrepuS
rekaepSCANdesivrepuS
lleBdnEleRCANdesivrepuS
lebalknalbedoCepyTrehtoonnehwesu(CANdesivrepuS
)seilppa
tkCesaeleRrofdesivrepus,detimilrewopnon,tiucriCgnisaeleR
stluafdnuorgdna,strohs,snepo
CLUtkCleR,sneporofdesivrepus,detimilrewop,tiucriCgnisaeleR
stluafdnuorgdna,strohs
CmroF.aeleResaelernopuetarepostcatnoc,tuptuoyaleR
elbiduAleResaelernopudetavitca,CAN
enohpeleTtiucricenohpeletdradnatS
lleBedoCleR)ylnoCAN004-SPM(CANdesivrepuS
The table of Type Codes contains
a comprehensive list of Type
Codes. The Type Codes that
display, however, depend on the
type of circuit.
Autoprogram selects the following default system functions the first
time you program the control panel. System defaults do not appear on
the display. Subsequent Autoprogramming will not change previous
editing of these functions. The following table contains a list of the
default functions and values.
System Defaults
System Defaults
snoitcnuFseulaVtluafeD
00enoZenoZmralAlareneG=lebalmotsuC
98hguorht10senoZknalbsilebalmotsuC
0FN=SAP;081=yaleD;yaleDSAP/langiserP=lebaL
9R-0RlortnoCesaeleRtcnuFesaeleR=lebaL
;ILU=TROBA
;N=SSORC
;0000=KAOS
A/N
6Fdna5FlortnoCemiTnoitcnuFemiT=lebaL
HSFTWTMS=syaD;00:00=ffO
7F00/00erasyadlla;tcnuFyadiloH=lebaL
8FemiThcraM=epyTedoC=lebaL
9Ffo%07=trelA;tcnuFmralA-erP=lebaL
mralafo%00=noitcA;mrala
sretemaraPmetsyS;51=YFIREV;000=OTUA;000=HNILIS
;TmeR;VPUSNON=NUNNA;EMITASU
N=SPVA;4=TS;Y=KNILB
sdrowssaP1111=egnahCsutatS,00000=egnahCmargorP
lamroNsmetsySllAA/N
egasseMmotsuCsknalb04
For details on programming
special zones F0-F9 and R0-R9,
refer to Special Zone Change.
For details on programming
system parameters, refer to
System Function Program-
ming.

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 15
Changing a Password
The Message option lets you change the 40-character All Systems
Normal message. From the Program Change screen, press <4>.
The control panel displays the Message Change screen:
Message Change screen
Changing a Password
To change a password, follow the instructions in the following table:
How to Change a Password
Password Change lets you customize a high-level or low-level pass-
word. From the Program Change screen, press <3> to display the
Change Password screen, then follow the instructions in the table.
Change Password screen
SYS NORMAL MESSAGE
Message change area
1) Change one character at a time, indicated by the blinking cursor
on the second line of the display.
2) Enter up to 40 characters maximum.
3) Enter lower case and special characters by pressing and holding
the <Lower Case> key then typing the character.
CHANGE PASSWORD *,NNNNN,E=PROGRAM
#,NNNNN, E=STATUS
Display area for
new password.
3
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
4
Changing the System
Message
Blinking cursor
How to change the System
Message
...oTsserP...neht
ehtegnahC
drowssapmargorP
H
wenehtepyt
.drowssapmargorP
sutatSehtegnahC
drowssap
I
sutatSwenehtepyt
.drowssap
drowssapehtevaS
C
egnahCdrowssaPeht
.sraeppaneercs
tideehtevaeL
tuohtiwneercs
agnignahc
d
>ecapskcaB<egnahCdrowssaPeht
.sraeppaneercs
...oTsihtoD
retcarahcgniknilbaegnahCehtmorfretcarahcaepyT
dapyek
retcarahctxenehtotevoM
sserP
G
egassemwenehtevaS
sserP
C

16 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
Changing a Custom Label
Zone Change Screen
The Zone option lets you change the custom label assigned to zones
1-99. From the Program Change screen, select <5> to display the
Zone Change screen.
Changing a Custom Label
How to change a Custom Label
CHANGE ZONE LABEL SELECT ZONE 01-99:
ENTER UP TO 19 CHAR
Custom Label (22-40)
Blinking cursor
5
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
Rules for Changing a Custom
Label
oTsihtoD
lebalenozaegnahC.dapyekehtmorflebalenozwenaepyT
nilebalenozehtevaS
yromemsserP
C
nilebalenozehtserotsmargorpehT
egnahCenoZehtsyalpsiddnayromem
.knalbsdleifllahtiwneercs
egnahCenoZehtevaeL
agnignahctuohtiwneercs
lebalenoz
sserP
S
edoMmargorPehtotsnruteryalpsidehT
The zone number displays in the first line, characters 39 and 40.
For single digit numbers, enter a leading zero before the digit.
Enter an alphanumeric zone label into line 2, characters 2240.
The program forces a blank for the first character which inserts a
space between the device and zone labels for a printout.
To change a custom label for a zone or a device, follow these
instructions:

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 17
Special Zone Change The Special Zone Change option lets you change the program for
special zones F0-F9 or releasing zones R0-R9. From the Program
Change screen, select <6> to display the Special Zone Change
screen.
The following table contains descriptions for each special function
that appears in the Special Zone Change screen.
Definitions of Special Functions
Select Function screens by entering the special function letter and
number (for example, F0, R0, and so on) from the Special Zone
Change screen. The following sections show sample screens that
display when you select a special function.
The Presignal screen provides fields for changing the delay time or
PAS. From the Special Zone Change screen, select <F0> to
display the Presignal Function screen.
F0 (Presignal)
Continued on the next page...
Special Function Screens
Special Zone Change Screen
1) Refer to Appendix A for additional
information on Releasing functions
(R0-R9).
2) Refer to Appendix B for additional
information on Special Functions
(F0-F9).
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
6
noitcnuFlaicepS...seificepS
)langiserP(0F.noitcelesSAPehtroemityaledeht
1Fafiffo/nonrutotdemmargorptuptuona
rewopCAnanahtrehtoelbuortmetsys
.sruccossol
2FCAnafiffo/nonrutotdemmargorptuptuona
.srucconoitidnoctuonworbrossolrewop
3Fafiffo/nonrutotdemmargorptuptuona
.setavitcatupniytiruceS
4Fafiffo/nonrutotdemmargorptuptuona
.setavitcatupniyrosivrepuS
)gnisaeleR(9R-0Rro,gninozssorc,epyttroba,semityaledeht
.emitkaos
emiT(6F-5F
)lortnoC
.keewehtfosyadro,emitpots,emittratseht
)yadiloH(7Fdemmargorp-7FnA.setadyadiloheninotpu
.setadyadilohdeificepsehtnosetavitcaecived
8F,laropmeT,emiThcraM:sepytedocruoffoeno
fitceffesekatylno8F.egatSowTro,ainrofilaC
.8FotsCANeromroenomargorpuoy
9F.levelmralA-erPnoitcAdnatrelAeht
Special Zones
Presignal Screen
SPECIAL FUNCTION: F0=PRESIG R0-R9=REL
F5-F6=TIME F7=HOL F8=CODE F9=PRE-ALARM
PRG PRESIGNAL FUNCT PRESIGNAL DELAY
DELAY=180 PAS=NO F00

18 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
The Time Control screen provides fields for changing the start
time, stop time, or days of the week. From the Special Zone
Change screen, select F5 or F6 to display the Time Control
screen.
F7 (Holiday) The Holiday screen provides fields for specifying up to nine
holiday dates. From the Special Zone Change screen, select F7 to
display the Holiday screen.
The Code Type screen provides fields for specifying one of four
code types: March Time, Temporal, California, or Two Stage.
From the Special Zone Change screen, select F8 to display the
Code Type screen.
F9 (Pre-Alarm)
Special Zone Change, continued
The Releasing Function screen provides fields for changing the
delay time or PAS. From the Special Zone Change screen, select a
function (R0-R9) to display the Releasing Function screen.
Releasing Function Screen
Time Control Screen
Holiday Screen
Code Type Screen
The Pre-Alarm screen provides fields for programming the Alert
and Action Pre-Alarm functions. From the Special Zone Change
screen, select F9 to display the Pre-Alarm screen.
Pre-Alarm Screen
PRG HOLIDAY FUNC **/** **/** **/**
**/** **/** **/** **/** **/** **/**
PRG CODING FUNCTION CODE TYPE
MARCH TIME F08
PRG PREALARM FUNCT ALERT
F09
F5-F6 (Time Control Functions)
R0-R9 (Releasing Functions)
F8 (Code Type)
PRG TIME FUNCTION TIME CONTROL
ON=**:** OFF=**:** DAYS=******** F05
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=00 ABORT=ULI CROSS=N SOAK=0000 R00

AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 19
Toggle the TERM_SUPERV, LocT,
ST-4/ST-6, and ACS functions by
pressing the Next and Previous
keys.
System Function Screen
The following table contains settings for general system functions.
System Function
Programming
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
7
The System option lets you set general system functions. From the
Program Change screen, select <7> to display the System Function
screen.
Annunciator Selection 1 Screen
Use the Annunciator Selection screen to select information that will
display on the ACS annunciators. The following table contains the ACS
display selections.
Continued on the next page...
noitcnuFmetsySgnitteStluafeD
)emittibihnIecneliS(HNILISsdnoces003ot00
)emitecneliSotuA(OTUA)enon(orez
sdnoces009ot006
0
noitacifireVmralA(YFIREV
)emit
sdnoces03ot00
EMITASUsuoiverP/txeNhtiwemitRUE
syek
segnahctamrofemitnaeporuE
ehtsecalpdna,emitruoh-42ot
htnomehterofebyad
emitASU
VREPUS_MRETseYrooNoN
eerhtfoenoedomlanimreT
roCPfosedomgnitarepo
ehtotdetcennoclanimret
no2BThguorhtlenaplortnoc
etelpmocaroF.004-UPCeht
ehtotrefer,snoitcnuffotsil
.launaMnoitallatsnI
otdetcennoclanimret(TcoL
nidetacoldnalenaplortnoc
;)mooremas
tubTcoLsaemas(McoL
seriuqer
ro;)drowssap
detcennoclanimret(TmeR
daeRrofmedomahguorht
.)ylnosutatS
TcoL
)knilbDELecived(Y=KNILByb)knilbon(N=knilBotteS
.syeknwoD/pUehtgnisserp
Y=knilB
elytsgniriwAPFNeht4=TS
.poolCLSehtrofdesu
)gniriwpoolCLS6elytS(6=TS
)gniriwpoolCLS4elytS(4=TS
4=TS
noitceleSSCAesUSCA
ehtotrefer(spuorG
roflaunaMnoitallatsnI
YroNN=SCA
Setting General System Functions
If UDACT=N, the control panel displays the Annunciator Selection 2
Screen, addresses A11A19:
ANNUN SELECTION2 A11=* A12=* A13=*
A14=* A15=* A16=* A17=* A18=* A19=*
Annunciator Selection 2 Screen
Setting ACS=Y displays the Annunciator Selection 1 Screen, address
A1A10. If UDACT=Y, you can use addresses A11-A19 with UDACTs
having software release #UDACT01.0 or higher to send panel status to
a UDACT.
SIL INH=000 AUTO=000 VERIFY=00 USA TIME
TERM_SUPERV=NO LocT BLINK=Y ST=4 ACS=N
A=ACS Address
ANNUN SELECTION1 A1=* A2=* A3=* A4=*
A5=* A6=* A7=* A8=* A9=* A10=* UDACT=N
ACS Selection Group (1-9) or *=not selected

20 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
System Function
Programming
ACS Selection Groups
The following screen shows an example of ACS Selection Groups.
This example shows annunciator selections for addresses A1-A3 (ad-
dresses A4-A10 not selected) and addresses A11A19 set to send panel
status to a UDACT.
Annunciators set to Address 1 display the status of detectors 1-64
(ACS Selection Group 6) on SLC loop 1;
Annunciators set to Address 2 display the status of detectors 1-64
(ACS Selection Group 7) on SLC loop 2; and
Annunciators set to Address 3 display the status of the NAC/Panel
Output Circuit modules (ACS Selection Group 9).
8
Check
Display After Successful Program Check
When finished programming, use the Check option to search the pro-
gram entries for possible errors. From the Program Change screen,
select <8>. The Check option searches the program for the following
conditions:
Output points mapped to a zone without a mapped input.
A zone with mapped input points without mapped output points
(including Z00 outputs).
Releasing zone inputs (R0-R9) with no RELEASE CKT outputs mapped
to them; or RELEASE CKT outputs with no R0-R9 inputs mapped to
them.
RO-R9 inputs not mapped to MAN RELEASE.
If the Check option detects multiple devices that fail the check, press the
Previous or Next keys to step through the devices. If you get errors,
return to Point Programming and correct the errors.
Annunciator Selection Screen Example
SCA
noitceleS
puorG
yalpsiDrotaicnunnA
165-1senoZdnasutatSUPC
2laicepS61dna4-1stkCCAN,99ot75senoZ
senoZ
3461ot101seludoMtnegilletnI
4462ot102seludoMtnegilletnI
5ot562dna691ot561seludoMtnegilletnI
692
61poolCLSno461ot101srotceteD
72poolCLSno462ot102srotceteD
8692ot562dna691ot561srotceteD
946(seludoMtiucriCtuptuOlenaP/CAN
)stniop
0ro*sserddAtAdellatsnItoNrotaicnunnA
Program Check OK.
RE-TEST PANEL NOW 09:50A Fri 08/04/95
ANNUN SELECTION1 A1=6 A2=7 A3=9 A4=*
A5=* A6=* A7=* A8=* A9=* A10=* UDACT=Y
If UDACT=N, you can use
addresses A11A19 on Annuncia-
tor Selection 2 Screen to select
annunciators.
The control panels annunciation points are divided into nine ACS
selection groups of 64 points, listed in the following table. Refer to
Appendix A in the Installation Manual for a list of the 64 points within
the ACS Selection Groups.
For detailed information on
annunciators, refer to Appendix A,
Annunciators, in the IQ-396X
Installation Manual (Document
50401).
Other manuals for AUTOPULSE IQ-396X
1
Other Ansul Control System manuals
Popular Control System manuals by other brands

Next Wave Automation
Next Wave Automation CNC Shark HD4 owner's manual

Air Lift Performance
Air Lift Performance 3S user guide

GRAUPNER
GRAUPNER MC-22S Programming manual

Ericsson
Ericsson MRS3000 Field service manual

Conrad
Conrad Steelmate operating instructions

Dickey-John
Dickey-John IntelliAg Operator's manual

Bticino
Bticino L4561N instruction sheet

Parking Facilities
Parking Facilities PF5700 Installation, operation & maintenance manual

Rain Bird
Rain Bird ICI+ Installing

Woodward
Woodward MicroNet TMR 5009FT product manual

Pilz
Pilz PMCprimo C2 operating manual

Vertiv
Vertiv Liebert Mini-Mate MT048 Installer/user guide