manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Argus Security
  6. •
  7. Marine Equipment
  8. •
  9. Argus Security CWS100 User manual

Argus Security CWS100 User manual

COMPATIBILITY
This acoustic device is only compatible with conventional control panels and systems, unless an approved optional module is fitted. For more
specific information regarding compatibility refer to your fire security system supplier and the technical documentation concerning the control
panel in use.
INSTALLATION - IMPORTANT NOTES
Refer to national and international standards in use for spacing and positioning of the fire security’s system devices; refer also to specific
standards and your supplier if the system is going to be installed in particular environments or environments where specific risks exist.
This device is to be used only with conventional control panels and systems (check the COMPATIBILITY paragraph).
This device must be wired according to the connection details described in this manual.
Disconnect the sounder line from the control panel before installing this device.
Test the device after installation.
SOUNDER OPENING PROCEDURE
In order to detach the upper sounder body from the base:
1) Insert the pins of the compatible key into the holes of one of the two side locking mechanisms.
2) Turn the key 90° to the left whilst applying light pressure.
3) Repeat this step for the second side locking mechanism; the locking mechanism appears as in picture 1 when
in the open position (flush).
4) Detach the sounder body from the base by pulling gently to separate (picture 3).
SOUNDER CLOSING PROCEDURE
In order to assemble the sounder body to the base:
1) Assemble the sounder body to the base using gentle pressure (picture 3).
2) Insert the pins of the compatible key into the holes of one of the two side locking mechanisms.
3) Turn the key 90° to the right.
4) Repeat this step for the second side locking mechanism, starting from point 2; the locking
mechanism appears as in picture 2 once closed (recessed).
5) To secure use the retaining screws, using the location holes on both sides of the base (picture 4).
Picture 1
Picture 2
Picture 3
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it
CWS100
CONVENTIONAL WALL SOUNDER
928w/07
Picture 4
OUTDOORS AND DAMP ENVIRONMENTS INSTALLATION
When installing the sounder outdoors or in a damp environment, carefully apply the self-adhesive
sealing pad to the back of the sounder base (picture 5).
WALL INSTALLATION
1) Choose the installation location for the sounder based upon system design regulations.
2) Fix the sounder base to the wall; the prepared location options for the fixing screws are highlighted in picture 6.
CABLE ENTRIES
The sounder base is provided with a knockout entry for the system cables, located in the centre of the base (picture 7).
The side wall of the base has prepared drilling points to allow for installation of cable glands; a row of three drilling points are provided to allow
for single or twin cable connection (picture 8).
TERMINAL BLOCK INSTALLATION
The terminal block on the back of the sounder body is installed as illustrated in picture 9.
[email protected] L20-CWSXX-0001 (vA.2)
LL
Picture 6 Picture 7
Picture 8
Picture 9
Picture 5
Suitable, but not EN 54-3 approved for
outdoor use.
WIRING
Connect the sounder to the sounder circuit from the control panel; wiring terminal connections are as illustrated in picture 10 and described in
table 1; an example of a typical circuit wiring arrangement is shown in picture 11.
Terminal block number Terminal block designation Notes Usage
1
Pos
Terminal blocks for the line’s positive terminals
(+). These connections are shorted: either one
can be used.
Connect to the positive terminals of the
control panel’s sounder circuit.
2
3
Tone
Terminal blocks for the line’s negative terminals
(-). These connections are shorted: either one
can be used.
Connect to the negative terminals of
the control panel’s sounder circuit.
Wiring to these terminal blocks acti-
vates the main tone set.
4
5
Alt
Terminal blocks for the line’s negative terminals
(-). These connections are shorted: either one
can be used.
Connect to the negative terminals of
the control panel’s sounder circuit.
Wiring to these terminal blocks acti-
vates the alternate tone set.
6
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it
Pos
Tone
Alt
Picture 10
Table 1
Sounder line (+)
Sounder line (-)
Picture 11
Use of the Tone or Alt terminals enable, respectively, the main tone set or the alternate one; refer to the MAIN TONE SET
and the ALTERNATE TONE SET paragraphs.
OUTPUT TONE SETTING
Use the DIP switch on the back of the sounder body to select the tone required; for this function the first five switches are used, highlighted in
picture 12.
The switches positioned upwards acquire value “1”; on the other hand, if positioned downwards acquire value “0”.
1) From the MAIN TONE SET table or the ALTERNATE TONE SET table (the choice of the table depends on how the sounder’s wiring has
been carried out) select the output alarm tone triggered when the sounder is activated.
2) Refer to the corresponding line of the “DIP configuration” column to select the five switch selection settings.
OUTPUT VOLUME SETTING
Use the DIP switch at the back of the sounder body to select the output volume; in particular, switches 6 and 7, highlighted in picture 13, are
used.
The switches positioned upwards acquire value “1”; on the other hand, if positioned downwards acquire value “0”.
1) Select the alarm volume required when the sounder is activated (table 2).
2) Refer to the corresponding line of the “DIP configuration” column to set the two volume selection switches.
Tone volume DIP configuration - switch 6 and 7 dB(A) evaluation Notes
HIGH 11 100 dB(A) +/- 3 All tones
MEDIUM HIGH 01
MEDIUM LOW 10
LOW 00
Picture 12
Picture 13
Table 2
[email protected] L20-CWSXX-0001 (vA.2)
LL
MAIN TONE SET
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it
Tone
number Tone description
DIP switch
configuration:
1, 2, 3, 4 and 5
Tone designation
1 * 800Hz for 500ms, then 1000Hz for 500ms 11101Warble Tone
2 * 970Hz continuous tone 01011Continuous tone
3 * 500-1200Hz for 3500ms, then off for 500ms 10101Slow Whoop (Dutch)
4 * 1200-500Hz swept every 1000ms (1Hz) 00111German DIN tone
52350-2900Hz swept every 333ms (3Hz) 10010Alternate HF slow sweep
6800Hz for 250ms, then 960Hz for 250ms 11110Alternative warble
7500Hz for 250ms, then 600Hz for 250ms 11100Alternative warble
8500-600Hz swept every 500ms (2Hz) 10100Analogue sweep tone
9970Hz for 625ms, then OFF for 625ms 10001Australian Alert (intermittent tone)
10 500-1200Hz sweep for 3750ms, then OFF for 250ms 10110Australian Evac (slow whoop)
11 800Hz for 250ms, then 970Hz for 250ms 00001FP1063.1-Telecom
12 554Hz for 100ms, then 440Hz for 400ms 00101French tone AFNOR
13 2800Hz for 1s, then OFF for 1s 11011HF Back up interrupted tone
14 2800Hz for 150ms, then OFF for 150ms 11001HF Back up interrupted tone – fast
15 2800Hz continuous 01001HF Continuous
16 800Hz for 500ms,then OFF for 500ms 01111Interrupted tone
17 1000Hz for 250ms, then OFF for 250ms 01101Interrupted tone medium
18 970Hz for 500ms, then OFF for 500ms 01110ISO 8201 LF BS5839 Pt 1 1988
19 2850Hz for 500ms, then OFF for 500ms 01100ISO 8201 HF
20 800Hz for 150ms, then OFF for 150ms 11010LF Back up Alarm
21 800-950Hz swept every 9ms 01010LF Buzz
22 800Hz continuous 11000LF Continuous tone BS5839
23 No sound 11111Silent
24 500-1200Hz rising for 3000ms, then falling for 3000ms 00000Siren 2 way ramp (long)
25 500-1200Hz rising for 250ms, then falling for 250ms 00010Siren 2 way ramp (short)
26 660Hz continuous 00100Swedish all clear signal
27 660Hz for 150ms, then OFF for 150ms 00110Swedish Fire signal
28 800-900Hz swept every 1000ms 10111Sweep tone (1 Hz)
29 800-970Hz swept every 333ms (3Hz) 10011Sweep tone (3 Hz)
30 800-970Hz swept every 111ms (9Hz) 01000Sweep tone (9 Hz)
31 (2900Hz for 500ms ON, 500ms OFF) x3, then 1500ms OFF 00011US Temporal Pattern HF
32 800-1000Hz swept every 500ms (2Hz) 10000LF Sweep (Cranford tone)
Table 3*EN 54-3 certified tones
ALTERNATE TONE SET
[email protected] L20-CWSXX-0001 (vA.2)
LL
Tone
number Tone description DIP switch configuration:
1, 2, 3, 4 and 5
1800Hz continuous 11101
21000Hz continuous tone 01011
3500-1200Hz for 3500ms, then off for 500ms 10101
4800Hz continuous 00111
52400Hz continuous 10010
6800Hz continuous 11110
7500Hz continuous 11100
8500Hz continuous 10100
92400Hz continuous 10001
10 500-1200Hz sweep for 3750ms, then OFF for 250ms 10110
11 500-1200Hz rising for 250ms, then falling for 250ms 00001
12 800Hz continuous 00101
13 2800Hz continuous 11011
14 800Hz continuous 11001
15 2800Hz continuous 01001
16 800Hz continuous 01111
17 800Hz continuous 01101
18 970Hz for 500ms, then OFF for 500ms 01110
19 2850Hz for 500ms, then OFF for 500ms 01100
20 800Hz continuous 11010
21 800Hz continuous 01010
22 800Hz continuous 11000
23 970Hz continuous 11111
24 800Hz continuous 00000
25 800Hz continuous 00010
26 660Hz continuous 00100
27 660Hz for 150ms, then OFF for 150ms 00110
28 800Hz continuous 10111
29 800Hz continuous 10011
30 800Hz continuous 01000
31 2900Hz continuous 00011
32 800Hz continuous 10000
Table 4
TESTING
1) Activate an alarm or evacuate condition at the control panel.
2) Check the audible activation of the sounder.
3) Press the SILENCE SOUNDERS button (or equivalent) and ensure all Sounder type devices have silenced before continuing.
4) Reset the system from the control panel.
All devices must be tested after installation and thereafter on a periodic basis as required by local codes.
ACOUSTIC OPERATIONAL PERFORMANCE
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it
TECHNICAL SPECIFICATIONS *
Power supply voltage range 15 - 40 Vdc (24 Vdc standard value)
Activated current range, volume set to HIGH.
Dependent upon tone selected 5 - 8 mA at 24 Vdc
Audible frequency range.
Dependent upon tone selected 440 - 2900 Hz
Maximum sound output, volume set to HIGH.
Valid for all tones 100 dB(A) ± 3
Maximum temperature range -10 °C / +55 °C
Maximum humidity 95% RH (without condensation)
Height (base included) 185 mm
Diameter 130 mm
Weight (base included) 270 g
IP rating (EN 54-3 certified) 21
IP rating (not certified) ** 65
*Consult the latest version of the TDS-CWSXX document for
further information, obtainable from your supplier.
** Independently assessed and certified to IPX5 (not part of the
current EN54-3 certification).
Picture 14
[email protected] L20-CWSXX-0001 (vA.2)
LL
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environ-
mental deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices in
order to minimize the risk of reduced performance caused by external factors. Ensure that this device is only
used with compatible control panels. Detection systems must be checked, serviced and maintained on a
regular basis to confirm correct operation.
Smoke detectors may respond differently to various kinds of smoke particles, thus application advice should
be sought for special risks. Detectors cannot respond correctly if barriers exist between them and the fire
location and may be affected by special environmental conditions.
Refer to and follow national codes of practice and other internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updated
periodically.
WARRANTY
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manufactur-
ing defects, effective from the production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or
usage.
Product must be returned via your authorized supplier for repair or replacement together with full information
on any problem identified.
Full details on our warranty and product’s returns policy can be obtained upon request.
ARGUS SECURITY S.R.L.
Via del Canneto, 14
34015 Muggia (TS)
Italy
15
CO0410CPR
EN 54-3:2001+A1:2002+A2:2006
CWS100
For use in compatible fire detection
and alarm system.
0832
Picture 15

Other manuals for CWS100

1

Other Argus Security Marine Equipment manuals

Argus Security AC-BS-01 User manual

Argus Security

Argus Security AC-BS-01 User manual

Argus Security AC-BS-01 User manual

Argus Security

Argus Security AC-BS-01 User manual

Argus Security TW-BS-01 User manual

Argus Security

Argus Security TW-BS-01 User manual

Argus Security SGWS-MOD/865 User manual

Argus Security

Argus Security SGWS-MOD/865 User manual

Argus Security SGRBS100-AV User manual

Argus Security

Argus Security SGRBS100-AV User manual

Argus Security Taurus TW-BS-01/BL User manual

Argus Security

Argus Security Taurus TW-BS-01/BL User manual

Argus Security SGRBS100-AV/L User manual

Argus Security

Argus Security SGRBS100-AV/L User manual

Argus Security TAURUS TW-BS-01/916 User manual

Argus Security

Argus Security TAURUS TW-BS-01/916 User manual

Argus Security SAGITTARIUS SGWS-MOD+CWS100 User manual

Argus Security

Argus Security SAGITTARIUS SGWS-MOD+CWS100 User manual

Argus Security VEGA FLEXIPLUS VC-BS-01 User manual

Argus Security

Argus Security VEGA FLEXIPLUS VC-BS-01 User manual

Argus Security SGRBS100/L User manual

Argus Security

Argus Security SGRBS100/L User manual

Argus Security SGRBS100-AV/L/865 User manual

Argus Security

Argus Security SGRBS100-AV/L/865 User manual

Argus Security CWS100 User manual

Argus Security

Argus Security CWS100 User manual

Argus Security SGRBS100/L/865 User manual

Argus Security

Argus Security SGRBS100/L/865 User manual

Popular Marine Equipment manuals by other brands

Navman D100 user manual

Navman

Navman D100 user manual

VEXILAR FL-18 owner's manual

VEXILAR

VEXILAR FL-18 owner's manual

BRNKL archipelago LIME LSGI1021 Setup guide

BRNKL

BRNKL archipelago LIME LSGI1021 Setup guide

Fike Twinflex Soundpoint 313-0021 Installation and maintenance instructions

Fike

Fike Twinflex Soundpoint 313-0021 Installation and maintenance instructions

Syqwest HydroBox Installation, operation and maintenance

Syqwest

Syqwest HydroBox Installation, operation and maintenance

Simrad GC80 EXPANDED instruction manual

Simrad

Simrad GC80 EXPANDED instruction manual

AML Oceanographic MVP Operator's guide

AML Oceanographic

AML Oceanographic MVP Operator's guide

Simrad IS40 installation manual

Simrad

Simrad IS40 installation manual

Garmin GSD 22 installation instructions

Garmin

Garmin GSD 22 installation instructions

Humminbird MEGA 360 UNIVERSAL installation guide

Humminbird

Humminbird MEGA 360 UNIVERSAL installation guide

Raymarine ST40 Owner's handbook

Raymarine

Raymarine ST40 Owner's handbook

AUTONAUTIC INSTRUMENTAL CMQ Instructions for use & warranty

AUTONAUTIC INSTRUMENTAL

AUTONAUTIC INSTRUMENTAL CMQ Instructions for use & warranty

Bodet Harmonys 907710 Installation and operating instructions

Bodet

Bodet Harmonys 907710 Installation and operating instructions

Kongsberg RV-2 Maintenance manual

Kongsberg

Kongsberg RV-2 Maintenance manual

E2S IS-pA1 instruction manual

E2S

E2S IS-pA1 instruction manual

Harken 3387 instructions

Harken

Harken 3387 instructions

B&G RAM T2 user manual

B&G

B&G RAM T2 user manual

Shockwave ICE Operation & service manual

Shockwave

Shockwave ICE Operation & service manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.