Argus Security SGCP100-IS User manual

www.argussecurity.itARGUS SECURITY S.R.L., Via del Canneto, 14 - 34015 - Muggia (TS) - Italy
SGCP100-IS
INTRINSICALLY SAFE WIRELESS
CALL POINT
GENERAL DESCRIPTION
The intrinsically safe wireless call point is a wall mounted device that, when activated, initiates an alarm on the fire security system.
Its construction makes it suitable for installation in hazardous environment according to ATEX DIRECTIVE 2014/34/EU.
Table 1
TECHNICAL SPECIFICATIONS ***
Communication range with the wire to wireless translator or
wireless expander 200 m (in open space) *
Operating frequency 868 MHz
Modulation type FSK
Operating frequency channels 7
Radiated power 5 dBm (3 mW)
Main battery type CR123A (3V & 1.2 Ah) - Duracell Ultra
Secondary battery type CR2032А (3V & 250 mAh) - Maxell
Approved battery voltage range 2.75V - 3.20V
Main battery lifespan 3 years **
Secondary battery lifespan 2 months **
Dimensions 86 mm x 86 mm x 59 mm
Weight 186 grams (without batteries)
Operating temperature range from –10 °C to +55 °C
* Ideal operating range: may vary
according to environmental
conditions.
** When a low battery condition is
indicated, both main and
secondary batteries must be
changed together.
** If it is assumed that the device is
set with a message transmission
period of 60 seconds.
*** Check latest version of
document TDS-SCP1IS-0002 for
further data, obtainable from your
supplier.
Device’s removal holes
Insertion hole for
the reset key
Front operating
element
Visual LED indicator
Manual activation
point
Wall mounting
back box
Main battery
Secondary
battery
Tamper spring
Link - program
switch
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Reset key
PCB battery
contact
Picture 6 - primary battery, secondary battery, primary battery
housing and link - program switch
Picture 7 - correct
battery insertion
DEVICE’S POWER SUPPLY, PROGRAMMING AND LINKING
The linking operation will configure the call point onto the wireless system controlled by a Translator interface.
The linking method described below does not change and applies for operation with either the wire to wireless translator interface or
the Wirelex computer configuration program.
1) Move the link-program switch to position ON (picture 6).
2) Insert the secondary battery into its housing (picture 6).
3) Insert the primary battery into its housing then into the device terminals of the PCB making sure that these remain on the outer
part of the intrinsically safe battery contact as indicated in picture 7; the visual LED indicator will switch on accordingly (see “Power
up” in table 2 and picture 7).
Ensure that the polarity is correct for both batteries!!!
4) When the wire to wireless translator (locally or remotely via Wirelex) is searching for a new device to link to, move the link-program
switch to position 1 in order to initiate communication with the translator or the expander module; the visual LED indicator will switch
on accordingly (see “Programming and linking to the system” in table 2).
If the linking and programming operation fails, check if mistakes were made with the wire to wireless translator or the Wirelex link
process, remove the batteries, change over repeatedly the ON / 1 switch a few times in order to discharge the internal capacitor and
then start again from point 1 re-performing the linking procedure.
Call point status Green LED Red LED
Power up
Device not linked
Link - program switch on “ON”
0.5 second green, then blinking red until power up is completed
Programming and linking to the system Blinking until linking and program-
ming is completed -
Power up
Device linked
Link - program switch on “1”
Blinking until power up is complet-
ed -
Normal condition - -
Alarm activation - 1 second on and 1 second off
Main battery fault - 0.5 second on and
10 seconds off
Secondary battery fault 0.5 second on and
10 seconds off -
Both batteries fault 0.5 second green, 5 seconds off, 0.5 second red
Not communicating with the translator or
the expander
0.1 second green and red (amber) and
1 second off Table 2
1
2
Intrinsically
Safe battery
contact PCB
Battery positive
terminal
CALL POINT’S VISUAL LED INDICATOR
The wireless call point is equipped with a bi-colour LED (red / green) that provides visual indication for functional conditions and
battery levels as indicated in table 2. The indicator is positioned near the lower right corner of the device’s operating element (see
picture 2).
INTRODUCTION TO THE INTRINSICALLY SAFE FIRE DETECTION DEVICE
This wireless manual call point has been certified by Baseefa and has been awarded the ATEX Classification II 1 G ; Ex ia IIC
T5 Ga –10˚C ≤ Ta ≤ +55˚C making it suitable for Category 1, 2 or 3 hazardous atmospheres with a maximum ambient temperature
up to 55˚C.
The product has been assessed and certified for ATEX & IECEx requirements for hazardous applications according to the following
standards:
IEC 60079-0:2011 / EN 60079-0:2012+A11:2013
IEC 60079-11:2011 / EN 60079-11:2012
IEC 60079-28:2015 / EN 60079-28:2015
It is recommended that installation only be carried out by qualified personnel according to hazardous area safe working practice and
in conformity to the terms of the product certification. Note that the Translator Interface to which this device will be linked does not
form part of the ATEX/IECEx certified system and must be sited in the safe area which is not subject to hazardous conditions.
Baseefa16ATEX0111X
IECEx BAS 16.0050X

COMMUNICATION QUALITY ASSESSMENT
It is possible to assess the radio communication quality of the wireless call point with the translator or expander module by using a
test feature built into the device. After successful programming-linking operation, by changing the link-program switch to the ON
position the device’s LED indicator will start blinking according to table 3.
Always remember to return the switch to the 1 position after the assessment operation: the device will NOT function
correctly whilst the switch is set on the ON position.
Communication quality Assessment Device’s indication
No connection Fail Two red blinks
Link margin is less than 10 dB Poor One red blink
Robust communication with link margin from 10 dB to 20
dB Good One green blink
Robust communication with link margin over 20 dB Excellent Two green blinks Table 3
WIRELESS CALL POINT PLACEMENT
For specific information regarding call point’s spacing, placement and special applications
refer to your specific national standards.
It is strongly advised to mount the device away from metal objects, metal doors, metal
window openings, etc. as well as cable conductors, cables (especially data cables), other-
wise the operating distance may greatly drop. The device should not be installed near
electronic devices and computer equipment that can interfere with the reception quality.
1) Select the position of the call point before installing and fixing its wall mounting back box.
Verify, from that position, that the communication between the device and the wire
to wireless translator or the wireless expander is correctly established and
working (see the COMMUNICATION QUALITY ASSESSMENT paragraph).
2) Install and fix the correctly oriented back box, in the selected position, with the screws
provided (picture 8).
3) Insert the correctly oriented front operating element onto its back box; see below the INSTALLING THE FRONT OPERATING
ELEMENT paragraph.
Picture 8 - position of
the holes for the screws
TESTING THE CALL POINT
In order to test the functionality of the installed wireless call point just press where marked on the call point’s operating window (see
paragraph ACTIVATION). When the call point is activated the following events will occur:
1) a rectangular visual indicator drops into view under the left-top corner of the device's transparent front window
2) an activation message is sent by wireless to the wire to wireless translator module then, successively, through the wiring loop to
the alarm system’s control panel
3) an alarm condition is initiated by the control panel
4) the call point’s visual LED indicator starts blinking indicating its activated status (see “Alarm activation”, table 2).
After each test the device must be reset (see the CALL POINT RESET paragraph).
All devices must be tested after installation and, successively, on a periodic basis.
Picture 12 - operating
element reset
MAINTENANCE
1) Before starting any maintenance work (e.g. batteries substitution), disarm the system, in order to avoid accidental and unwanted
tamper detection conditions
2) remove the front operating element from its wall mounting back box
3) perform the necessary maintenance operations
4) after the device has been serviced, reinstall it correctly onto its back box, re-arm the system and check correct operation as
described under the TESTING THE CALL POINT paragraph.
FRONT OPERATING ELEMENT REMOVAL
In order to remove the call point’s front operating element from its wall mounting back box, the pegs on the top of the reset key must
be inserted into the two release holes located under the call point; push the pegs into the holes until the front unlocks (picture 10).
During this operation be careful not to twist the reset key or drop the device on the floor.
TAMPER DETECTION SPRING
The wireless call point front operating element has a tamper switch spring fitted on the rear, so that if it is removed from its wall box it
will send a tamper message to the control panel (see picture 4).
CALL POINT RESET
To reset the wire to wireless from an activated condition, it is necessary to:
1) insert the reset key into its entry situated under the front device block and turn it counter-clockwise until the operable front window
unlocks (picture 12)
2) send a reset command from the control panel.
DISCHARGED BATTERIES
If one or both batteries are discharged, this condition is signaled locally by visual LED indicator (table 2), by the wire to wireless
translator and, if implemented, by the system’s control panel. Both must be replaced together.
The device should be removed from its back box and transferred to the safe area before batteries are removed and
replaced to enhance safe handling.
INSTALLING THE FRONT OPERATING ELEMENT
In order to complete the installation, the front operating element must be securely installed onto the wall-mounted back box. In order
to assemble correctly fit the front as illustrated in picture 9.
ACTIVATION
The wireless call point is activated by pressing the where marked on the transparent window on the front of the device as shown in
picture 11.
Picture 9 - front
operating element
assembly to its
wall mounting
back box
Picture 10 -
front device
block removal
from its wall
mounting back
box
Picture 11 - call
point activation
www.argussecurity.itARGUS SECURITY S.R.L., Via del Canneto, 14 - 34015 - Muggia (TS) - Italy
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to
environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace
the devices in order to minimize the risk of reduced performance caused by external factors. Ensure that
this device is only used with compatible control panels.
Detection systems must be checked, serviced and maintained on a regular basis to confirm correct
operation. Smoke sensors may respond differently to various kinds of smoke particles, thus application
advice should be sought for special risks. Sensors cannot respond correctly if barriers exist between
them and the fire location and may be affected by special environmental conditions. Refer to and follow
national codes of practice and other internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updat-
ed periodically.
Care must be taken not to generate any electrostatic charge on the body of the device
Clean only with a lint-free damp cloth and do not use any cleaning solvents
WARRANTY
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manu-
facturing defects, effective from the production date indicated on each product. This warranty is invalidat-
ed by mechanical or electrical damage caused in the field by incorrect handling or usage. Product must
be returned via your authorized supplier for repair or replacement together with full information on any
problem identified. Full details on our warranty and product’s returns policy can be obtained upon re-
quest.
ARGUS SECURITY S.R.L.
Via del Canneto, 14
34015 Muggia (TS)
Italy
16
SG2210CPR
EN 54-25:2008
EN 54-11:2001 + A1:2005
SGCP100-IS
For use in compatible fire
detection and alarm system
Type A for indoor use only
3
4
0051 / 0598
II 1 G
IMPORTANT NOTES!
Programming is considered to be completed successfully only if there is an indication of programming success on the
device and on the wire to wireless translator module or on the window of the Wirelex program.
Do not fit the front operating element onto the back box, so to press the tamper spring, before programming and linking to
the wireless system is totally completed: communication problems may rise successively.
Generally speaking: make sure, during the programming-linking phase, that the tamper spring is not pressed at all!
See the TAMPER DETECTION SPRING paragraph for more information on the tamper spring.
Other Argus Security Security System manuals
Popular Security System manuals by other brands

Prestige
Prestige APS-25HT owner's manual

Response Electronics
Response Electronics miGuard G5 Installation and operating instructions

EnOcean
EnOcean EOSW installation guide

Pfannenberg
Pfannenberg DS Series Instructions for operating and installing

eTIGER
eTIGER S5 quick start guide

Cooper Security
Cooper Security Homelink 75 user guide