installation &
operating instructions
ips 4000 controller - Integrated pumping
system for variable primary applications
8
4.1.2 system overview Description
Shows a detailed view of the system. The screen adapts to the
configuration of the system (dedicated or headered) by showing
the number of pumps, chillers/boilers, system flow, bypass valve,
zone PVs or head and flow. If more than 6pumps or chillers/boil-
ers, use the grey arrow at the bottom right corner to scroll. Press
the x button on the top right corner to go back to the previous
screen.
Data
Pump 1to 8status The pump icons show the pump status:
grey - stopped; green - running; red - alarm
Pump 1to 8mode Shows each pump mode: Hand, O or Auto.
Pump 1to 8duty Shows each pump duty: Duty1, Duty2,
Duty3, Duty4, Duty5, Duty6, Duty7, Duty8,
or stand-by.
Pump 1to 8speed Shows each pump speed in percentage.
Chiller/boiler 1to 8
status
The icons show the device status:
grey - stopped; green - running
active zone Indicates which zone is assigned as Active.
Only visible if control type on Pump Setup
screen is Sensor or Hybrid.
deviation Indicates the active zone deviation. Only
visible if control type on Pump Setup screen
is Sensor or Hybrid.
setpoint Indicates the active zone setpoint in the
chosen unit. Only visible if control type on
Pump Setup screen is Sensor or Hybrid, or if
system valves control is enabled.
max open vlv Indicates the opening of the driving system
valve. Only visible if control type on Pump
Setup screen is Sensor or Hybrid, or if sys-
tem valves control is enabled.
flow Indicates both sensor and sensorless flow
values in the system based on the selection.
head Indicates the total head in the system. Only
visible if control type on Pump Setup screen
is Sensorless or Hybrid.
bypass valve Indicates valve position in percentage
(100% means fully open).
delta Indicates how far from the control curve the
pump(s) are operating. The ips regulates
the pump speed to achieve an error of zero.
ips status Indicates whether the ips is on or o.
Alarm A red bell indicates an alarm in the system.
minimum flow Indicates the rated minimum chiller/boiler
flow. Updates dynamically based on num-
ber of chillers/boilers enabled.
maximum flow Indicates the rated maximum chiller/boiler
flow. Updates dynamically based on num-
ber of chillers/boilers enabled.