= dG - Digital input (see digital inputs functions)
If probe Pr2 and/or Pr3 is/are not used, set the relative parameter
“P2”and/or “P3” = oF.
It is not possible to program more parameters for the same function
(priority goes to lowest input).
Using the parameter “Ft”, it is possible to set the time constant for
the software filter for measuring the input values to be able to
reduce the sensitivity to measurement disturbances (increasing the
time).
In addition to this filter are present two other similar filters but used
only for the display of the temperature Pr1 both as regards the in-
crease (par. "du") that the decrease (par. "dd") of the measure to
avoid display a rapid temperature change.
The filter blocks the decrease in maximum display to 0.1 °each
"dd" sec. and increase the maximum display each "du" sec ..
Every switch-on the filters are reset.
To see the temperature Pr1 filtered set par. "dS" = F1
Through the parameter “dS”, it is possible to fix the normal
visualisation on the display that can be the measurement of the
probe Pr1 (P1), the measurement of the probe Pr2 (P2), the
measurement of the probe Pr3 (P3), the active set point value (SP),
the label “Eco” when the instrument is in Eco mode (Ec) or it can
have the numerical display switched off (oF).
Through the parameter “CU”, it is possible to program an measure
offset that will be applied to the temperature show on the display
(only if dS”= P1, P2, P3, Ec, F1).
The normal visualisation on the display is established by par. “dS”,
but it is possible to visualise all the variables and the highest and
lowest Pr1 peak measurement values in rotation by quickly
pressing and releasing key U.
The display will alternately show the code that identifies the
variable and its value.
The variable are:
“P1” - Pr1 temperature
“P2” - Pr2 temperature ( on/oF state if is progr. as digital input )
“P3” - Pr3 temperature ( on/oF state if is progr. as digital input )
“Lt” and the lowest Pr1 peak temperature
“Ht” and the highest Pr1 peak temperature
If the main voltage alarms are activated in this mode will be
displayed the variable P5 that represents the main voltage with a
value decreased of 150 V.
The main voltage tension measured by the instrument will be
therefore V = P5 + 150.
If the voltage measure is not correct it is possible to modify it
through the par. "OU".
When the instrument is switched off, peak values are always
re-set. However, it is also possible to reset these values if the
instrument is switched on by using the DOWN key hold for 3 sec.
during peak visualization.
The display will show “---” and peak memory will be reset.
The exit of this visualisation mode occurs automatically 15 seconds
after the last pressing on the key U.
Please remember that visualisation of the Pr1 probe can be
changed by the defrosting display lock function, by using the
parameter “dL” (see defrost function).
4.4 - DIGITAL INPUTS
All the parameters concerning digital inputs are contained in the
group “-In”.
The instrument P03S / P05S
has 1 digital input for voltage free contacts whose function is
defined by the parameters “1F” and and whose action can be
delayed by the time period set in the parameter “1t”.
In addition, the instrument may have 2 further digital inputs for
voltage-free contacts as an alternative to the measurement inputs
Pr2 and Pr3.
In order to use these inputs digitally, the user must set the relevant
parameter “P2” or “P3” = dG.
The function performed by these digitally configured inputs is
defined by the parameters “2F” and “3F”
The Pr2 digital input action can be delayed by the time period set in
the parameter “2t” while the action of Pr3 digital input is instanta-
neous and cannot be delayed.
The parameters “i.1F” , “i.2F”, “i.3F” can be configured for the
following functions:
= 0 - No function
= 1 -Cell door opening by contact normally open: on closing the
digital input the instrument visualises oP and the variable set in
parameter “dS” alternately on the display. With this function mode,
the action of the digital input also activates the time that can be set
in parameter "oA" after which the alarm is activated to signal that
the door has been left open.
= 2 -Cell door opening with fan stop by contact normally open: on
closing the digital input the fans are stopped and the instrument
visualises oP and the variable set in parameter “dS” alternately on
the display. With this function mode, the action of the digital input
also activates the time that can be set in parameter "oA" after
which the alarm is activated to signal that the door has been left
open and the fan restart.
= 3 - Cell door opening with compressor and fan stop by contact
normally open: similar to “i.x” = 5 but with fan and compressor stop.
At the intervention of the door open alarm alarm compressor and
fan restarts.
= 4 - External alarm signal by contact normally open: on closing
the digital input the alarm is activated and the instrument visualises
AL and the variable set in parameter “dS” alternately on the
display.
= 5 - Signalling of external alarm with disablement of all the control
outputs by contact normally open: on closing the digital input all
the control outputs are disabled, the alarm is activated and the
instrument visualises AL and the variable set in parameter “dS”
alternately on the display.
= 6 - Selecting the active set point (SP/SE) with contact normally
open: on closing the digital input the temperature set point “SE” is
activated. When instead the input is open the set point “SP” is
active.
= 7 - Switching on/switching off (Stand-by) of instrument by contact
normally open: on closing the digital input the instrument is
switched on while it is placed in Stand-by when opened.
= 8 - "Turbo" cycle activation command with normally-open contact:
closing the input starts a "turbo" cycle.
= 9 - Remote command of auxiliary output AUX with normally-open
contact: closing the input activates the auxiliary output as
described in the "Fo" = 2 operating mode of the auxiliary output.
= 10 - Not used
= 11 - Not used
= 12 - External "Pr" alarm notified and "ot" output deactivated by
normally-open contact: closing the input deactivates the output
configured as "ot" and activates the alarm, and the instrument
display shows Pr alternating with the variable defined by the “dS”
parameter.
= 13 - External “HP” alarm notified and “ot” output deactivated by
normally-open contact: closing the input deactivates the output
configured as “ot” and activates the alarm, and the instrument
display shows HP alternating with the variable defined by the “dS”
parameter.
= 14 - External “LP” alarm notified and “ot” output deactivated by
normally-open contact: closing the input deactivates the output
configured as “ot” and activates the alarm, and the instrument
display shows LP alternating with the variable defined by the “dS”
parameter.
= -1, -2, -3, etc. - Like function with positive values but with
function logic reversed (contact normally closed)
Note: Where multiple digital inputs are configured for the same
function, the instrument will treat the contacts as if they were
parallel (and consequently regard the result as an OR function).
4.5 - OUTPUTS AND BUZZER CONFIGURATION
All the parameters concerning outputs configuration are contained
in the group “-Ou”.
The instrument outputs can be configured by the relative
parameters “o1” , “o2”, “o3”, “o4”.
The outputs can be configured for the following functions:
= ot - to control the compressor or however, the temperature
control device
ASCON TECNOLOGIC - B05-- OPERATING INSTRUCTIONS - PAG. 6